background image

20 

 

INSTALLATION (continued)

 

 

SYSTEM FILLING

 

 

Sealed Systems

 

 
Before  filling  the  system,  ensure  that  all fittings  and  joints have 
been  made.  Thoroughly  flush  out  the  system  to  remove  any 
swarf  and  residue  from  the  pipework  and  associated 
components. 
 
Fill  the  system  to  the  pressure  required  (recommended  1  bar), 
via an approved filling loop. Ensure all air has been vented from 
the system before operating the appliance. 
 

Open Vent Systems 

 
Fill via mains pressure to flush air out of the system (see 

fig. 11

 

below

 

for  further  details).  There  must  be  no  permanent 

connection between the appliance and the mains water supply. 
 

Air Removal 

 
If  the  air  is  not  fully  removed  from  the  system,  a  lockout  will 
occur within the unit (operating parameter 

8

), causing it to cease 

operation.  To  remove  excess  air,  open  the  isolation  valves  to 
the  heating/hot  water  system  and  fill  using  one  of  the  above 
methods  until  the  air  has  been  removed  via  the  automatic  air 
vent.  Should  air  remain  within  the  Activair,  close  the  isolation 
valves  to  the  system  and  use  mains  pressure  to  expell  air  as 
shown in 

fig. 11 

below.

 

 
 

 

 
 
 
 
 
 
 
 
 

 
 
COMMISSIONING 

 
After  the  safe  installation  of  the  heat  pump  in  full  accordance 
with  these  instructions,  it  is  important  that  the  unit  is 
commissioned to ensure reliable operation: 
 
1)  Fill the system, in accordance with the filling guide above. 
 
2)  Switch  power  on  to  the  unit and  set  the  water  temperature 

on  the  programmer  to  40°C  (see  operating  instructions, 

page 7

). 

 

 

 

 

3)  The  SUN  symbol  will  appear  at  the  top-right  of  the 

programmer  display  (

fig  1

)  as  the  unit  operates.  Run  the 

heat  pump  until  the  water  temperature  has  reached  40°C. 
The  SUN  symbol  will  flash  when  the  water  reaches  this 
temperature and the unit will cease operation. 

 
5)  Explain  all  system  controls  and  the  maintenance  procedure 

(below)  to  the  end-user.  Make  adjustments  to  the 
programmer settings as requested. 

 

 

SERVICING & MAINTENANCE 

 
While  it  is  not  necessary  to  carry  out  an  annual  service  on  the 
appliance, regular inspections may be required, depending upon 
where the unit is sited. 
 

Note:

  Isolate  the  electrical  supply  to  the  appliance  before 

accessing the interior of the unit. 
 

INTERNAL INSTALLATION 

 
A visual inspection of the fan and coil should be made once per 
year. Clean as often as is necessary (e.g. when dirt build-up is 
visible) and remove any obstructions.   
 
Ensure  the  supporting  base  remains  stable  and  capable  of 
supporting  the  full  weight  of  the  appliance,  including  its  water 
content. 
 

EXTERNAL INSTALLATION 

 

Every Three Months 

 
Visually inspect the appliance, and remove any leaves, plant life 
or debris from around or inside the unit. 
 

Every Twelve Months 

 
A visual inspection should be made of the fan and coil. Clean as 
often  as  is  necessary  (e.g.  when  dirt  build-up  is  visible)  and 
remove any obstructions.  
 
Ensure  the  supporting  base  remains  stable  and  capable  of 
supporting  the  full  weight  of  the  appliance,  including  its  water 
content. 
 
If  the  appliance  is  installed  in  a  coastal  area,  the  periodic 
removal of salt may be required from the coil. 

 
Panels

 

 
Periodically  clean  the  panels  by  wiping  with  a  damp  cloth.  Do 
not  use  alcohol,  benzine,  thinners,  glass  cleaner,  household 
polish  or  powders.  It  may  be  appropriate  to  apply  a  protective 
wax to the casings, especially in coastal areas. 
 
 

FIG 11

 

4)  Press and release the search button and check readings

     1 to 4. The temperature diffrerence between 1 and 4

     should be no more than 25 deg C. If the difference is 

     higher check for impaired water flow.

Summary of Contents for ActiveAir S1800 S

Page 1: ...AIR SOURCE HEAT PUMP S1800 S USER INSTALLATION COMMISSIONING SERVICING INSTRUCTIONS Please read these instructions carefully before installing commissioning and using this appliance To be retained by...

Page 2: ...g avoid inhalation and contact with the skin and eyes Suitable personal protective equipment must be worn gloves overalls eye protection and a comprehensive first aid kit containing eye wash should be...

Page 3: ...d risk of lightning strikes Do not attempt to move the appliance once installed this must be carried out by a qualified engineer Isolate the electrical supply to the appliance if an odour presents or...

Page 4: ...01 EN 50366 2003 EN 14511 2004 parts 1 to 4 EN 60335 2 40 2003 A11 2004 used in conjunction with EN 60335 1 2002 A11 2004 A1 2004 The Basis on Which Conformity is Being Declared The products identifie...

Page 5: ...e Information 10 Technical Information 11 Dimensions Clearances 11 Water Connection Dimensions 11 Mounting Dimensions 11 Technical Specification 12 Performance Data 12 Installation Instructions 13 Int...

Page 6: ...starting the appliance ensure that it has been installed in full accordance with these instructions and that all necessary safety checks have been carried out The diagram below fig 1 shows the progra...

Page 7: ...nning indicator display Please ensure that all other required parameters such as cylinder water temperature see adjacent column have been set before operating the appliance To cease operation in this...

Page 8: ...essure switch has operated Refer to the operating parameter descriptions page 21 for further details AMBIENT TEMPERATURE CUTOUT Should the ambient temperature around the appliance reach too high a lev...

Page 9: ...g hot water system page 20 If sounds are heard from the appliance which sound like the passage of water this is merely the normal movement of the refrigerant within the unit If there is power to the a...

Page 10: ...nical advisors are available to discuss any problem with the appliance which may occur In many cases the problem may be solved over the telephone eliminating the need for a service visit HOW TO REPORT...

Page 11: ...11 TECHNICAL INFORMATION FIG 3 CLEARANCES FRONT VIEW SIDE VIEW A 748 B 748 C 1030 D 619 E 753 F 72 5 G 130 H 285 ALL DIMENSIONS IN mm FIG 2 OVERALL DIMENSIONS...

Page 12: ...kg Noise Level 60 dB A Min Water Output Temperature 20 C Max Water Output Temperature 55 C Power Supply 230V 50Hz Fused at 32 amp Working Ambient Temperature Range 5 C to 43 C Flow Return Connections...

Page 13: ...upright position prior to installation it must be left standing for at least 24 hours before use The Activair can be fitted either internally or externally to the property being heated The appliance...

Page 14: ...y before accessing the inside of the appliance This appliance must be earthed and the earth cable must be of a greater length than the current carrying conductor cables i e live and neutral supply cab...

Page 15: ...15 FIG 4 INTERNAL WIRING DIAGRAM...

Page 16: ...linder central heating and underfloor heating sizing calculations must take this into account A chart of Activair heat outputs at various ambient air temperatures can be found on page 12 Should a back...

Page 17: ...ust be installed in compliance with current Building Regulations and any local directives which may apply Note a circulating pump is not included within the Activair unit FIG 5 ACTIVAIR SIDE SEALED SY...

Page 18: ...18 SYSTEM SCHEMATICS cont BUFFER TANK FOR STANDARD OR UNDERFLOOR HEATING CIRCUITS FIG 9 FIG 10 DHW HTG VIA TANK IN TANK WITH SOLAR COIL...

Page 19: ...rain The water will drain from holes in the base of the Activair If the unit is installed outside provision should be made to drain this water to a soakaway if the unit is installed indoors a collect...

Page 20: ...symbol will flash when the water reaches this temperature and the unit will cease operation 5 Explain all system controls and the maintenance procedure below to the end user Make adjustments to the p...

Page 21: ...nt temperature has returned to normal levels unit will automatically reset 06 Coil temperature cycle Coil temperature too high When coil temperature has returned to normal levels unit will automatical...

Page 22: ...will allow the preservation of all settings and timings If the appliance is operating but the water temperature is lower than expected 1 Check that all isolation valves are fully open 2 Check the wat...

Page 23: ...7 Transformer 224506 1 8 Relay 224542 1 9 Relay Cable 224543 1 10 NTC Sensor 224508 1 11 Fan Blades 224545 1 12 Auxiliary Starter 224520 1 13 Programmer Extension Cable 224535 1 14 NTC Sensor PCB Ada...

Page 24: ...strations contained within are vested in TR Engineering Ltd and neither the brochure or any part thereof may be reproduced without prior written consent TR Engineering s policy is one of continuous re...

Reviews: