background image

22 

 

FAULT-FINDING 

 
If  the  appliance  fails  to  start  for  no  apparent  reason  and  an 
operating  parameter  code  (

page  21

)  is  not  displayed  on  the 

programmer, carry out the following checks: 
 
1.  Check for failure in the electrical supply. 
 
2.  Check for a blown fuse. 

 

3.  Check  the  circuit  breaker  (if  fitted). If  this  has  tripped  reset 

and restart the appliance. 

 

4. 

Ensure  there  is  a  current  ‘heat  demand’  from  the 
programmer.  Ensure  the  programmer  clock  and  timer 
controls  have  been  set  in  accordance  with  the  instructions 
on 

pages  6/7

  or  that  it  is  switched  on  (if  in  non-timed 

mode). 

 

5.  Check  the  programmer  settings  by  pressing  the 

SEARCH

 

button for five seconds. 

 

Setting 1 

- set at 26. 

 
Setting 2 

- set at 18. 

 
Setting 3 

- set at 14. 

 

These are factory-set and should not in normal 
circumstances  have  been  altered.  If  for  some  reason  the 
settings do not match the figures above, alteration is made 
via the

 TEMPERATURE ADJUSTMENT

 buttons (

+/-

). 

 

Note:

 if the appliance has been shut down due to a failure of the 

power supply, the programmer contains a battery backup, which 
will allow the preservation of all settings and timings. 

 

 
 

 

If the appliance is operating, but the water temperature is lower 
than expected: 
 
1.  Check that all isolation valves are fully open. 
 
2.  Check  the  water  temperature  setting  is  not  too  low.  This 

can be increased by following the instructions on 

page 7

 
3.  Check  that  the  vents  on  the  back  of  the  unit  and  the  coil 

have not become blocked, impeding the air flow. 

 
4.  Check  the  unit  has  not  entered  defrost  mode  (the 

DEFROST  symbol  will  appear  above  the  temperature 
display see

 fig. 1

). Should this occur, the heat output from 

the appliance will be diverted to the coil, until any ice build-
up has been removed. 

 

5.  Ensure  there  is  no  air  trapped  in  either  the  Activair  or  the 

heating/hot water system.

 

 
If  sounds  are  heard  from  the  appliance,  which  sound  like  the 
passage  of  water,  this  is  merely  the  normal  movement  of  the 
refrigerant within the unit. 
 
If  there  is  power  to  the  appliance  and  the  programmer  is 
providing  a  'heat  demand’  to  the  unit,  yet  the  unit  has  not 
entered  running  mode  (the  SUN  symbol  has  not  appeared 
above the temperature display), it may be that one of the safety 
cut-outs  (see 

page  8

)  has  operated.  These  will  typically  take 

several minutes to clear before the unit restarts. 
 

Summary of Contents for ActiveAir S1800 S

Page 1: ...AIR SOURCE HEAT PUMP S1800 S USER INSTALLATION COMMISSIONING SERVICING INSTRUCTIONS Please read these instructions carefully before installing commissioning and using this appliance To be retained by...

Page 2: ...g avoid inhalation and contact with the skin and eyes Suitable personal protective equipment must be worn gloves overalls eye protection and a comprehensive first aid kit containing eye wash should be...

Page 3: ...d risk of lightning strikes Do not attempt to move the appliance once installed this must be carried out by a qualified engineer Isolate the electrical supply to the appliance if an odour presents or...

Page 4: ...01 EN 50366 2003 EN 14511 2004 parts 1 to 4 EN 60335 2 40 2003 A11 2004 used in conjunction with EN 60335 1 2002 A11 2004 A1 2004 The Basis on Which Conformity is Being Declared The products identifie...

Page 5: ...e Information 10 Technical Information 11 Dimensions Clearances 11 Water Connection Dimensions 11 Mounting Dimensions 11 Technical Specification 12 Performance Data 12 Installation Instructions 13 Int...

Page 6: ...starting the appliance ensure that it has been installed in full accordance with these instructions and that all necessary safety checks have been carried out The diagram below fig 1 shows the progra...

Page 7: ...nning indicator display Please ensure that all other required parameters such as cylinder water temperature see adjacent column have been set before operating the appliance To cease operation in this...

Page 8: ...essure switch has operated Refer to the operating parameter descriptions page 21 for further details AMBIENT TEMPERATURE CUTOUT Should the ambient temperature around the appliance reach too high a lev...

Page 9: ...g hot water system page 20 If sounds are heard from the appliance which sound like the passage of water this is merely the normal movement of the refrigerant within the unit If there is power to the a...

Page 10: ...nical advisors are available to discuss any problem with the appliance which may occur In many cases the problem may be solved over the telephone eliminating the need for a service visit HOW TO REPORT...

Page 11: ...11 TECHNICAL INFORMATION FIG 3 CLEARANCES FRONT VIEW SIDE VIEW A 748 B 748 C 1030 D 619 E 753 F 72 5 G 130 H 285 ALL DIMENSIONS IN mm FIG 2 OVERALL DIMENSIONS...

Page 12: ...kg Noise Level 60 dB A Min Water Output Temperature 20 C Max Water Output Temperature 55 C Power Supply 230V 50Hz Fused at 32 amp Working Ambient Temperature Range 5 C to 43 C Flow Return Connections...

Page 13: ...upright position prior to installation it must be left standing for at least 24 hours before use The Activair can be fitted either internally or externally to the property being heated The appliance...

Page 14: ...y before accessing the inside of the appliance This appliance must be earthed and the earth cable must be of a greater length than the current carrying conductor cables i e live and neutral supply cab...

Page 15: ...15 FIG 4 INTERNAL WIRING DIAGRAM...

Page 16: ...linder central heating and underfloor heating sizing calculations must take this into account A chart of Activair heat outputs at various ambient air temperatures can be found on page 12 Should a back...

Page 17: ...ust be installed in compliance with current Building Regulations and any local directives which may apply Note a circulating pump is not included within the Activair unit FIG 5 ACTIVAIR SIDE SEALED SY...

Page 18: ...18 SYSTEM SCHEMATICS cont BUFFER TANK FOR STANDARD OR UNDERFLOOR HEATING CIRCUITS FIG 9 FIG 10 DHW HTG VIA TANK IN TANK WITH SOLAR COIL...

Page 19: ...rain The water will drain from holes in the base of the Activair If the unit is installed outside provision should be made to drain this water to a soakaway if the unit is installed indoors a collect...

Page 20: ...symbol will flash when the water reaches this temperature and the unit will cease operation 5 Explain all system controls and the maintenance procedure below to the end user Make adjustments to the p...

Page 21: ...nt temperature has returned to normal levels unit will automatically reset 06 Coil temperature cycle Coil temperature too high When coil temperature has returned to normal levels unit will automatical...

Page 22: ...will allow the preservation of all settings and timings If the appliance is operating but the water temperature is lower than expected 1 Check that all isolation valves are fully open 2 Check the wat...

Page 23: ...7 Transformer 224506 1 8 Relay 224542 1 9 Relay Cable 224543 1 10 NTC Sensor 224508 1 11 Fan Blades 224545 1 12 Auxiliary Starter 224520 1 13 Programmer Extension Cable 224535 1 14 NTC Sensor PCB Ada...

Page 24: ...strations contained within are vested in TR Engineering Ltd and neither the brochure or any part thereof may be reproduced without prior written consent TR Engineering s policy is one of continuous re...

Reviews: