930-108-01-A.04
PowerHawk 6212, 6312 and 6412 meters
01/2011
Installation
© 2011 Triacta Power Technologies All Rights Reserved
23
3.
Press the Display button until the “Send” command appears on the
display.
4.
Press the center or the right arrow button to manually force the
PowerHawk meter to report metering data using the Ethernet or
modem connection. This clears data from the PowerHawk meter
memory, and ensures the time is set correctly.
Pulse Inputs
There are two pulse in terminal blocks in the PowerHawk meter, as shown in
Figure 11. Each terminal block has a negative terminal pin on the right and a
positive terminal pin on the left. The pulse inputs are compatible with both dry
form A contacts, and solid-state form A contacts. The inputs are not
polarity-sensitive to dry relay contacts. When the pulsing device provides
solid-state form A outputs, the negative terminal from the source device must
be connected to the negative terminal of the PowerHawk meter pulse in
terminal block.
Display Navigation
The PowerHawk meter has three buttons to control the information
presented on the LCD. The display has a normal and a diagnostics mode.
The PowerHawk meter starts in normal mode, and enters diagnostics mode
when the Display button is pressed and held for 5 seconds. To adjust the
contrast, hold down the Display button, and use the right and left arrow
buttons to increase and decrease the contrast respectively.
Normal Mode
In Normal mode, the Display button scrolls through the information for each
meter. The left and right arrow buttons select the previous or next meter
points respectively. The following information is available:
•
Real Energy Delivered kWh D
•
Real Energy Received kWh R
•
Real Power Watts
•
Reactive Energy Delivered KVarhD
•
Reactive Energy Received KVarhR
•
Reactive Power Var
In Normal mode, the right and left arrow buttons scroll the display from meter
points 1 to 8, 1 to 12, or 1 to 24, depending on your configuration.
Diagnostics Mode
Diagnostics mode is accessed by pressing and holding the Display button for
5 seconds. In Diagnostics mode, pressing the Display button will scroll
through the following additional information:
•
Send data command
•
CT Primary value and Real Power Watts per phase
•
Voltage per phase
•
Local IP address
•
Reset factory default IP address command
•
Date and time (UTC)