ADVANCED Setpoints Menu - Available Only On Dashboard
DASHBOARD DISPLAY
FULL NAME
MIN
MAX
DEFAULT
DESCRIPTION
MOTOR TYPE
EEV Motor Type
Unipolar or Bipolar
Unipolar
Unipolar if unipolar stepper used, Bipolar if bipolar stepper used
MOTOR STEP RATE
EEV Motor Step Rate
30
400
40
Motor Step rate for custom valve. Not available on Basic Display
MAX VALVE STEPS
Max Valve Steps
200
6400
500
Full stroke steps for custom valve. Not available on Basic Display
MAX OPERATING PRES
Max Operating Pres
10.0 psi
150.0
psi**
150.0 psi** **Max operating pressure. Max is 300 when R-410A selected and 500
when R-744 selected
FAN SPEED
Fan Speed
-100.0%
100.0%
0.0%
Fan speed %. Not available on Basic Display
MIN COMP RUN TIME
Min Comp Run Time
0 min
15 min
2 min
Minimum Compressor Run Time. Not available on Basic Display
MIN COMP OFF TIME
Min Comp Off Time
0 min
15 min
5 min
Minimum Compressor Off Time. Not available on Basic Display
REFRIG FAN MODE
Refrigeration Fan Mode
Manage, Permanent,
ON with Compressor,
Title 24
Permanent
Managed = manage fans during refrig cycle; Permanent = fans ON per-
manent during refrig cycle; On with Compressor = manage fans in OFF
then ON in refrig; Title 24 = cycle fans based on Title 24 regulations
1ST DEFROST DELAY
1st Defrost Delay
0 min
240 min
120 min
First Defrost Delay. Not available on Basic Display
DEFROST FAN STATE
Defrost Fan State
ON or OFF
OFF(E)/ON(A) OFF = fans off during defrost; ON = fans ON during defrost
FAN DELAY TEMP
-40.0 °F
35.0 °F
20.0 °F
Fan delay temp. Not available on Basic Display
MAX FAN DELAY TIME
Max Fan Delay Time
0 min
20 min
2 min
Max fan delay time. Not available on Basic Display
PUMP DOWN TIME
Pump Down Time
0 min
90 min
0 min
Minimum amount of time between de-energizing the liquid line sole-
noid/compressor relay and energizing the defrost relay.
MULTI AIR TEMP CTRL
Multi Air Temp Control Warmest or Average Warmest Air Warmest air = use the warmest air temp from bonded controls; Average
air = use the average air temp from bonded controls
MULTI EVAP COOL
Multi Evap Cooling
Synchronized or
Independent
Synchronized
Synchronized = synchronize bonded controller in refrigeration mode;
Independent = bonded controllers control temperature independently in
refrigeration mode.
MULTI EVAP DEFROST
Multi Evap Defrost
Synchronized or
Independent
Synchronized Synchronized = synchronize bonded controller in defrost mode; Inde-
pendent = bonded controllers defrost independently
MULTI EVAP SENSOR
Multi Evap Sensor
Shared or Unshared
Shared
Shared = share sensor readings from bonded controllers; Unshared =
use local sensor readings only
SUCT PRES OFFSET
Suct Pres Offset
-5.0 °F
5.0 °F
0.0 °F
An offset added or subtracted from the suction line pressure trans-
ducer reading, if needed
SUCT TEMP OFFSET
Suct Temp Offset
-5.0 °F
5.0 °F
0.0 °F
An offset added or subtracted from the suction temperature sensor
reading, if needed
COIL TEMP OFFSET
Coil Temp Offset
-5.0 °F
5.0 °F
0.0 °F
An offset added or subtracted from the coil temperature sensor read-
ing, if needed
AIR TEMP OFFSET
Air Temp Offset
-5.0 °F
5.0 °F
0.0 °F
An offset added or subtracted from the room temperature sensor read-
ing, if needed
AUX 1 OFFSET
AUX1 Temp Offset
-5.0 °F
5.0 °F
0.0 °F
When Aux1, Aux2, or Aux 3 are used as a temperature sensor, an offset
is added or subtracted from the reading.
AUX 2 OFFSET
AUX2 Temp Offset
-5.0 °F
5.0 °F
0.0 °F
AUX 3 OFFSET
AUX3 Temp Offset
-5.0 °F
5.0 °F
0.0 °F
PROPORTIONAL
Proportional
0
255
3
A coefficient to the valve control algorithm that increases valve respon
-
siveness as the value increases
INTEGRAL
Integral
0
255
5
A coefficient to the valve control algorithm that increases valve respon
-
siveness as the value increases
DERIVATIVE
Derivative
0
255
3
Should not be adjusted unless instructed by factory
AIR TEMP DIFF
Air Temp Differential
0.1
5.0
1.0 °F
The number of degrees above ROOM TEMP before the controller will go
into REFRIGERATION mode
DEFROST FAN STATE
Defrost Fan State
Off
Off
On
Fan state during the defrost cycle
MULTI AIR TEMP CTRL
Multi Evaporator Air
Temp Control
Average Warmest
Warmest
Select control method to use with multiple room temperature sensors
MULTI EVAP COOL
Multi Evaporator Cool
Control
Sync
Indepen-
dent
Sync
Select type of multi evaporator control - options are synchronous or
independent
MULTI EVAP DEFROST
Multi Evaporator
Defrost Control
Sync
Indepen-
dent
Sync
Select whether to have all bonded controllers initiate defrost mode at
the same time or independently.
MULTI EVAP SENSOR
Multi Evaporator Sen-
sor Sharing
Shared
Not
Shared
Not Shared Select whether or not to share room temperature, coil temperature and
suction pressure sensor data with bonded controllers.
MENUS AND PARAMETERS (cont’d)
T30-ESP-OM--1
11/09/20
- 5 -