6
TB/TI Thermistor Insertion Temperature Sensor Installation Instructions TG200727 Issue 5, 07-Mar-2016.
TB/TI
Installation Instructions
9
Configure controller
11
Test System
10
Set up IQ Sensor Type
2 InSTallaTIon
(continued)
IQ
IQ Configuration Manual (90-1533)
IQ3 Configuration Manual (TE200768)
IQ4 Configuration Manual (TE201263)
IQeco Configuration Manual (TE201089)
IQ
or
∆
T
IQ
Thermistor
(-30 °C to +110 °C, -22 °F to +230 °F)
It is recommended to use SET for the setting of the sensor
type module. For all IQ2 series controllers with firmware
version 2.1 or greater, or IQ3/4 series controllers, the following
SET Unique Sensor References should be used:
Thermistor:
Thermistor TBTI
(-30 °C to +110 °C)
Thermistor TBTI F
(-22 °F to +230 °F)
Alternatively set scaling mode to 5 (characterise) and enter
scaling manually as defined in the adjacent table.
Note that for IQ3/4, scaling mode and exponent do not need
to be set up.
For all other IQ controllers see Sensor Scaling Reference
Card (TB100521A).
Units:
°C
°F
Y
Input type
1 (therm V)
e
Exponent
3
U
Upper
115
239
l
Lower
-35
-31
P
Points
20
x
Ix
ox
1
0.480
110
230
2
0.549
105
220
3
0.630
100
212
4
0.724
95
203
5
0.833
90
194
6
0.961
85
185
7
1.110
80
176
8
1.484
70
158
9
1.985
60
140
10
2.641
50
122
11
3.470
40
104
12
4.460
30
86
13
6.663
10
50
14
7.668
0
32
15
8.102
-5
23
16
8.482
-10
14
17
8.807
-15
5
18
9.078
-20
-4
19
9.299
-25
-13
20
9.476
-30
-22