TB/TI Thermistor Insertion Temperature Sensor Installation Instructions TG200727 Issue 5, 07-Mar-2016.

TB/TI 

Installation Instructions

9

Configure controller

11

Test System

10

Set up IQ Sensor Type

2 InSTallaTIon 

(continued)

IQ

IQ Configuration Manual (90-1533)

IQ3 Configuration Manual (TE200768)

IQ4 Configuration Manual (TE201263)

IQeco Configuration Manual (TE201089)

IQ

or

 

T

IQ

Thermistor 

(-30 °C to +110 °C, -22 °F to +230 °F)

It is recommended to use SET for the setting of the sensor 

type  module.  For  all  IQ2  series  controllers  with  firmware 

version 2.1 or greater, or IQ3/4 series controllers, the following 

SET Unique Sensor References should be used:

Thermistor: 

Thermistor TBTI 

(-30 °C to +110 °C)

 

   

Thermistor TBTI F 

(-22 °F to +230 °F)

Alternatively  set  scaling  mode  to  5  (characterise)  and  enter 

scaling manually as defined in the adjacent table. 

Note that for IQ3/4, scaling mode and exponent do not need 

to be set up.

For  all  other  IQ  controllers  see  Sensor  Scaling  Reference 

Card (TB100521A).

Units:

°C

°F

Y

Input type

1 (therm V)

e

Exponent

3

U

Upper

115

239

l

Lower

-35

-31

P

Points

20

x

Ix

ox

1

0.480

110

230

2

0.549

105

220

3

0.630

100

212

4

0.724

95

203

5

0.833

90

194

6

0.961

85

185

7

1.110

80

176

8

1.484

70

158

9

1.985

60

140

10

2.641

50

122

11

3.470

40

104

12

4.460

30

86

13

6.663

10

50

14

7.668

0

32

15

8.102

-5

23

16

8.482

-10

14

17

8.807

-15

5

18

9.078

-20

-4

19

9.299

-25

-13

20

9.476

-30

-22

Summary of Contents for Thermistor TBTI

Page 1: ...ature Sensor Installation Instructions TG200727 6 mm 0 24 400 mm 15 75 94 mm 3 70 57 mm 2 24 113 mm 4 45 50 mm 1 97 6 mm compression fitting 3 x 4 mm diam holes on a 30 mm 1 18 PCD Pitch Circle Diamet...

Page 2: ...therwise use averaging sensor 40 C 40 F 50 C 122 F to 40 C 40 F 110 C 230 F to Duct Duct H O 2 0 RH 95 RH Protection IP67 NEMA6 Ensure no stratification e g downstream of mixing valves junctions d 40...

Page 3: ...et length clip engages in groove probe is forced against end of pocket tighten screw over bush InSTall SenSoR InTo PoCKeT If using Universal Fitting Kit if pocket has clip retaining groove push clip o...

Page 4: ...ST DEPTH OF PROBE drill 3 holes screw on flange mounted flange 7 mm 0 28 42 5 mm 1 67 85 mm 3 35 2 off 2 off No 6 3 4 s s self tapping screws integral foam gasket compression fitting duct mounting fla...

Page 5: ...20x1 5 cable gland supplied Or use M20 flexible conduit not supplied Recommended cable TP 1 1 22 HP 200 600V Belden 8761 Terminal size 0 5 to 2 5 mm2 20 to 14 AWG Sensor IQ controller COM 0V IN polari...

Page 6: ...he following SET Unique Sensor References should be used Thermistor Thermistor TBTI 30 C to 110 C Thermistor TBTI F 22 F to 230 F Alternatively set scaling mode to 5 characterise and enter scaling man...

Page 7: ...7 Issue 5 07 Mar 2016 7 Installation Instructions TB TI There are no serviceable parts inside the unit Cleaning of the unit should be carried out in order to avoid buildup of dust or other containment...

Page 8: ...e Switzerland by its Authorized Representative Trend Control Systems Limited Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the conte...

Reviews: