Proportional  Druckregelventil
Proportional  pressure  regulator

VPPM−...

741  073
0810b

nicht  für 
Typ  VPPM−...C1

not  for 
type  VPPM−...C1

Summary of Contents for VPPM Series

Page 1: ... de Bedienungs anleitung en Operating instructions Proportional Druckregelventil Proportional pressure regulator VPPM 741 073 0810b nicht für Typ VPPM C1 not for type VPPM C1 ...

Page 2: ... qualifi ziertem Fachpersonal gemäß Bedienungs anleitung Warnung Warning Caution Hinweis Please note Umwelt Antipollution Zubehör Accessories Fitting and commissioning to be carried out by qualified personnel only in accordance with the operating instructions Deutsch 3 English 23 ...

Page 3: ... Muffenventil 4 Pneumatische Anschlüsse des VPPM Flanschventil 5 Varianten des VPPM 6 2 Funktion und Anwendung 7 3 Voraussetzungen für den Produkteinsatz 7 4 Einbau 8 Mechanisch 8 Pneumatisch 11 Elektrisch 11 5 Inbetriebnahme 14 6 Bedienung und Betrieb 16 7 Wartung und Pflege 16 8 Ausbau 17 9 Zubehör 17 10 Sicherheitseinstellung 18 11 Störungsbeseitigung 18 12 Technische Daten 20 ...

Page 4: ...sse des VPPM Muffenventil 1 2 3 5 6 4 7 9 8 9 1 Stecker für elektrischen Anschluss 8 polig 2 LED Betriebs und Statusanzeigen 3 DOWN Taste 4 EDIT Taste 5 UP Taste 6 Druckluftanschluss 1 Druckeingang 7 Arbeitsluftanschluss 2 Druckausgang 8 Entlüftungsanschluss3 9 DurchgangsbohrungenzurBefestigung Bild 1 ...

Page 5: ...VPPM DE EN Festo VPPM 0810b Deutsch 5 Pneumatische Anschlüsse des VPPM Flanschventil 1 2 3 1 KanalDruckluft Druckeingang 2 Kanal Arbeitsluft Druckausgang 3 KanalEntlüftung Bild 2 ...

Page 6: ...stellunggeschlossen 5 Pneumatischer Anschluss Flansch Anschlussplatte ISO Gewinde NPT Gewinde F G12 1 2 G14 1 4 G18 1 8 N12 NPT 1 2 N14 NPT 1 4 N18 NPT 1 8 6 Standart Regelbereiche unterer Druckwert oberer Druckwert Alternative Regelbereiche unterer Druckwert oberer Druckwert 0L 0 bar 2H 2 bar 6H 6 bar 10H 10 bar L Wert zwischen 0 10 bar z B 4L H Wert zwischen 0 10 bar z B 8H 7 Sollwertvorgabe Sch...

Page 7: ... Sie sicher dass die folgenden Vorgaben stets eingehalten werden S Vergleichen Sie die Grenzwerte in dieser Bedienungsanleitung mit denen Ihres Ein satzfalls z B Betriebsmedium Drücke Kräfte Momente Temperaturen Massen Geschwindigkeiten Spannungen S Berücksichtigen Sie die Umgebungs bedingungen am Einsatzort S Berücksichtigen Sie die Vorschriften der Berufsgenossenschaft des Technischen Überwachun...

Page 8: ...erten Bewegungen auf 4 Einbau Mechanisch Hinweis S Der Einbau und die Inbetriebnahme darf nur gemäß der Bedienungsanleitung und von qualifiziertem Fachpersonal erfolgen S Behandeln Sie das VPPM so dass keine Schäden am elektrischen Anschluss auftreten Diese können zur Minderung der Funktionssicherheit führen S Achten Sie auf genügend Platz für den Kabelanschluss und die Schlauchan schlüsse Dadurch...

Page 9: ...ent 1 0 Nm Befestigung auf dem Anschlussblock S Befestigen Sie das VPPM 2 auf dem Anschlussplock 1 Typ VABM P1 SF G18 Lage der Befestigungsbohrungen siehe Position 3 im Bild rechts Anziehdrehmoment 1 5 Nm 1 2 3 Befestigung auf der Hutschiene siehe Bild 9 S Montieren Sie den Hutschienenadapter Typ VAME P1 T mit Hilfe der beigelegten Schrauben an das VPPM Anzugsdrehmoment ca 1 0 Nm für x M4 x 65 für...

Page 10: ...to VPPM 0810b Deutsch 10 1 2 ÓÓ ÓÓ ÓÓ ÓÓ ÓÓ ÓÓ ÓÓ ÓÓ ÓÓ ÓÓ ÔÔ ÔÔ 4 5 3 1 Befestigungsschrauben M4 Anziehdrehmoment siehe Bild 8 2 VPPM 3 Hutschiene 4 Hutschienen Klemmeinheit 5 Hutschienenadapter Typ VAME P1 T Bild 9 ...

Page 11: ...IN EN 60204 1 Hinweis Lange Signalleitungen reduzieren die Störfestigkeit S Stellen Sie sicher dass die Signalleitungen stets kürzer sind als 10 m S Überprüfen Sie anhand des Typenschildes welche Ventilvariante Ihnen vorliegt Bezeichnung auf dem Typenschild VPPM V1 VPPM A4 Benennung Spannungsvariante Stromvariante Elektrischer Sollwert DC 0 10 V 4 20 mA Bild 10 S Prüfen Sie die Verwendung folgende...

Page 12: ...M12G8 KD M12G5 an CPX E A Module ist die galvanische Trennung der E A Module nicht mehr gewährleistet S Verkabeln Sie das VPPM gemäß eines der entsprechenden Anschlussbilder Anschlussbilder VPPM Spannungsvariante Typ VPPM V1 Stromvariante Typ VPPM A4 8 4 3 D1 ext in D2 ext in 1 5 7 X GND 6 W W D3out Uv 0 10 V 2 PIN 7 8 4 3 D1 ext in D2 ext in 1 5 X GND 6 W D3out Uv 4 20 mA PIN W 2 Bild 12 ...

Page 13: ...rsorgungsspannung 1 2 8 3 grün GN Analoger Eingang W Sollwert 1 2 4 gelb YE AnalogerEingang W Sollwert 0 10 V AnalogerEingang W Sollwert 4 20 mA 3 7 5 grau GY Digitaler Eingang D2 3 6 rosa PK Analoger Ausgang X Istwert 6 4 7 blau BU DC 0 V oder GND 5 6 4 8 rot RD Digitaler Ausgang D3 3 5 PE Schirmgeflecht auf Gewinde 1 Bei Verwendung der Anschlussdose mit Kabel lt Zubehör 2 Das Anziehdrehmoment be...

Page 14: ...gelfunk tion Dazu wird der Sollwert mit dem Istwert verglichen Der digitale Schaltausgang D3 wird aktiv sobald die Regelabweichung 0 5 FS beträgt und wird inaktiv wenn die Regelabweichung 1 FS überschreitet Diagramm zur Schaltvariante PNP 1 2 3 4 1 Sollwert 2 Istwert 3 obere Toleranzgrenze 4 untere Toleranzgrenze Bild 14 P Variante PNP ...

Page 15: ...agramm zur Schaltvariante NPN 1 2 3 4 1 Sollwert 2 Istwert 3 obere Toleranzgrenze 4 untere Toleranzgrenze Bild 15 N Variante NPN Schaltbilder VPPM Schaltausgang PNP NPN 8 7 2 PNP P BN RD BU 0 V 24 V RL RD RL 2 8 7 NPN P BN BU 0 V 24 V Bild 16 ...

Page 16: ...die Kontakte 3 und 4 angelegt wobei das niedrigere Potenzial am Kontakt 3 und das höhere Potenzial an Kontakt 4 anzuschließen ist Kontakt 3 Sollwert kann mit Kontakt 7 GND verbunden werden S Bestromen Sie das VPPM mit Gleichstrom Versorgungsspannung UV 24 VDC 10 S Wählen Sie den Parametersatz für den Regler aus siehe tech Daten Drücken Sie die Taste EDIT für 3 sec Wählen Sie mit der Taste UP bzw D...

Page 17: ...üften Sie das VPPM mit einem mindestens um 1 bar höheren Eingangs druck als der maximal gewünschte Ausgangsdruck Es stellt sich ein dazu proportionaler Ausgangsdruck p2 ein Dem Sollwertsignal ist dann folgender Ausgangsdruck zugeordnet VPPM Ausgangsdruck beim Signal 1 FS 1 2 Ausgangsdruck beim Signal 100 FS 1 2 2 bar Typ 0 02 bar 2 bar 6 bar Typ 0 06 bar 6 bar 10 bar Typ 0 1 bar 10 bar 1 FS Full s...

Page 18: ... 6 Bedienung und Betrieb Hinweis S Stellen Sie sicher dass beim Abschalten des VPPM zuerst der Versorgungsdruck danach die Sollwertspannung und zuletzt die Versorgungsspannung abgeschaltet wird 7 Wartung und Pflege Zur Reinigung S Schalten Sie zur äußeren Reinigung folgende Energiequellen ab Betriebsspannung Druckluft S Reinigen Sie bei Bedarf das VPPM von außen mit einem weichen Lappen Die zuläss...

Page 19: ...hlüsse vom VPPM S Demontieren Sie das VPPM von der Befestigungsfläche Hutschiene 9 Zubehör Bezeichnung Typ Steckdosenkabel gerade Steckdosenkabelgewinkelt Y Anschlusskabel zum Anschließen des VPPM an analogeEin Ausgänge SIM M12 8GD PU NEBU M12W8 N LE8 NEBV M12G8 KD M12G5 Hutschienenbefestigung Winkel Anschlussblock VAME P1 T VAME P1 A VABM P1 SF G18 P3 Bild 21 ...

Page 20: ... wird gesichert Ausgangsdruck bleibt ungeregelt erhalten Mittelfristig kann sich der Druck am Ausgang erhöhen oder verringern Bild 22 11 Störungsbeseitigung Ursache Zustand der LED Anzeigen Power LED grün ERROR LED rot Unterspannungbzw Überspannung des Sollwertes leuchtet leuchtet Hardwarefehler Überspannung 30 V Interne Temperatur zuhoch leuchtet blinkt Unterspannung 18 V dunkel dunkel Bild 23 ...

Page 21: ...enkverschraubungen Anschlussalternativen einsetzen Druckanstieg zu langsam GroßesZylindervolumenund lange Schlauchlänge Anderen Parametersatz wählen Druck konstant trotz veränderter Sollwertvorgabe Bruch des Versorgungskabels Der zuletzt eingestellte Ausgangsdruck bleibt unge regelt erhalten Mittelfristig kann sich der Druck am Ausgang erhöhen oder verringern Zu geringer Versorgungs druck P1 Verso...

Page 22: ... 0 1 10 Eingangsdruck p1 mind 1 bar über Ausgangsdruckp2 Gesamtleckage im Neuzustand l h 5 Anschlüsse G1 8 1 8 NPT Nennweite Belüftung Entlüftung mm 6 4 5 Normalnenndurchfluss siehe Bild 26 Schutzart IP65 im montiertem Zustand mit angezogenen Befestigungsschrauben in Verbindungmit Anschlussdose laut Zubehör Zul Temperaturbereich Umgebungstemperatur Mediumstemperatur Lagertemperatur C C C 0 60 10 5...

Page 23: ...max 500 Elektromagnetische Verträglichkeit EMVStöraussendung und Störfestigkeit Siehe Konformitätserklärung è www festo com CE Konformität für Industriebereiche erfüllt Schwingung und Schock Schwingung Schock Nachfolgende Angaben gelten nicht bei Montage des VPPM an den Winkel VAME P1 A Geprüft nach DIN IEC 68 EN 60068 Teil 2 6 bei Wandmontage 0 35 mm Weg bei 10 60 Hz 5 g Beschleunigung bei 60 150...

Page 24: ...VPPM DE EN Festo VPPM 0810b Deutsch 24 Durchflusskennlinien 2 bar Ventilvariante TypVPPM 6L OL2H 6 bar Ventilvariante TypVPPM 6L OL6H 10 bar Ventilvariante TypVPPM 6L OL10H Bild 26 ...

Page 25: ...e valve 24 Pneumatic connections of the VPPM flanged valve 25 Variants of the VPPM 26 2 Function and application 27 3 Conditions of use 27 4 Fitting 28 Mechanical installation 28 Pneumatic installation 31 Electrical installation 31 5 Commissioning 34 6 Operation 36 7 Care and maintenance 36 8 Dismantling 37 9 Accessories 37 10 Safety setting 38 11 Eliminating faults 38 12 Technical specifications ...

Page 26: ...s and connections of the VPPM in line valve 1 2 3 5 6 4 7 9 8 9 1 Plug for electrical connection 8 pin 2 LED for operational and status displays 3 DOWN button 4 EDIT button 5 UP button 6 Supply port 1 pressure input 7 Air port 2 pressure output 8 Valve exhaust port 3 9 Through holes for fastening Fig 1 ...

Page 27: ...VPPM DE EN Festo VPPM 0810b English 27 Pneumatic connections of the VPPM flanged valve 1 2 3 1 Compressed air channel pressure input 2 Air channel pressure output 3 Exhaust channel Fig 2 ...

Page 28: ...normally closed 5 Pneumatic connection Flange sub base ISO thread NPT thread F G12 1 2 G14 1 4 G18 1 8 N12 NPT 1 2 N14 NPT 1 4 N18 NPT 1 8 6 Standard control ranges Lower pressure value Upper pressure value Alternative control ranges Lower pressure value Upper pressure value 0L 0 bar 2H 2 bar 6H 6 bar 10H 10 bar L value between 0 10 bar e g 4L H value between 0 10 bar e g 8H 7 Setpoint specificati...

Page 29: ... the following specifications are always observed S Compare the limit values contained in these operating instructions with those of your application e g operating medium pressures forces moments temperatures loads speeds voltages S Take into consideration the ambient conditions at the location of use S Please comply with national and local safety laws and regulations S Remove all transport packin...

Page 30: ...l installation Please note S Fitting and commissioning are to be carried out by qualified personnel only in accordance with the operating instructions S Handle the VPPM with care so that the electrical connection is not damaged This can result reduce the operational reliability S Make sure there is sufficient space for the cable connection and the tube coupling This prevents kinks in the connectin...

Page 31: ...ghtening torque 1 0 Nm Fastening on the sub base S Fasten the VPPM 2 on the sub base 1 type VABM P1 SF G18 Position of the mounting holes see Item 3 in the figure to the right Tightening torque 1 5 Nm 1 2 3 Fastening on the H rail see Fig 9 S Mount the H rail adapter type VAME P1 T to the VPPM with the aid of the enclosed screws Tightening torque approx 1 0 Nm for x M4 x 65 for M4 x 75 S Hang the ...

Page 32: ... DE EN Festo VPPM 0810b English 32 1 2 ÓÓ ÓÓ ÓÓ ÓÓ ÓÓ ÓÓ ÓÓ ÓÓ ÓÓ ÓÓ ÔÔ ÔÔ 4 5 3 1 M4 mounting screws tightening torque see Fig 8 2 VPPM 3 H rail 4 H rail clamping unit 5 H rail adapter type VAME P1 T Fig 9 ...

Page 33: ...rference S Make sure that the signal cable is not longer than 10 m S Check which valve variant you have using the rating plate Designation on the rating plate VPPM V1 VPPM A4 Designation Voltage variant Current variant Electrical setpoint value 0 10 V DC 4 20 mA Fig 10 S Check the use of the following options on the VPPM Measurement of the actual value of voltage or current S Make sure that the ca...

Page 34: ...al isolation of the I O modules can no longer be guar anteed S Wire the VPPM according to the appropriate connection diagrams VPPM connection diagrams Voltage variant type VPPM V1 Current variant type VPPM V4 8 4 3 D1 ext in D2 ext in 1 5 7 X GND 6 W W D3out Uv 0 10 V 2 PIN 7 8 4 3 D1 ext in D2 ext in 1 5 X GND 6 W D3out Uv 4 20 mA PIN W 2 Fig 12 ...

Page 35: ... 1 2 8 3 Green GN Analogue input W setpoint value 1 2 4 Yellow YE Analogueinput W setpoint value 0 10 V Analogueinput W setpoint value 4 20 mA 3 7 5 Grey GY Digital input D2 3 6 Pink PK Analogue output X actual value 6 4 7 Blue BU 0 V DC or GND 5 6 4 8 Red RD Digital output D3 3 5 PE braided screen on thread 1 Using the connection socket with cable as specified in the chapter Accessories 2 The max...

Page 36: ... compared here with the actual value The digital switching output D3 becomes active as soon as the deviation from the target value amounts to 0 5 FS full scale and becomes inactive when the deviation from the target value exceeds 1 FS Diagram of switching variant PNP 1 2 3 4 1 Target value 2 Actual value 3 Upper tolerance limit 4 Lower tolerance limit Fig 14 P variant PNP ...

Page 37: ...of switching variant NPN 1 2 3 4 1 Target value 2 Actual value 3 Upper tolerance limit 4 Lower tolerance limit Fig 15 N variant NPN VPPM circuit diagrams Switch output PNP NPN 8 7 2 PNP P BN RD BU 0 V 24 V RL RD RL 2 8 7 NPN P BN BU 0 V 24 V Fig 16 ...

Page 38: ...0 10 V is applied to contacts 3 and 4 The lower potential must be connected at contact 3 and the higher potential at contact 4 Contact 3 setpoint value can be connected to contact 7 GND S Supply the VPPM with direct current power supply UV 24 VDC 10 S Select the parameter set for the regulator see Technical specifications Press the EDIT button for 3 sec Use the UP or DOWN button to select the requ...

Page 39: ...ig 18 S Pressurise the VPPM with an input pressure at least 1 bar higher than the maximum required output pressure An output pressure propotional to this p2 is reached The following output pressure is assigned to the setpoint signal VPPM Output pressure for signal 1 FS 1 2 Output pressure for signal 100 FS 1 2 2 bar type 0 02 bar 2 bar 6 bar type 0 06 bar 6 bar 10 bar type 0 1 bar 10 bar 1 FS Full...

Page 40: ... 6 Operation Please note S When switching off the VPPM make sure that first the supply pressure then the setpoint voltage and finally the supply voltage are switched off 7 Care and maintenance Cleaning S Switch off the following sources of energy before cleaning the exterior of the unit operating voltage compressed air S If the VPPM is dirty clean the exterior with a soft cloth The approved cleani...

Page 41: ...relevant connections from the VPPM S Remove the VPPM from the mounting surface H rail 9 Accessories Designation Type Plug socket with cable straight Plug socket with cable angled Y cable to connect the VPPM to analogue inputs outputs SIM M12 8GD PU NEBU M12W8 N LE8 NEBV M12G8 KD M12G5 H railmounting Bracket Sub base VAME P1 T VAME P1 A VABM P1 SF G18 P3 Fig 21 ...

Page 42: ...utput pressure is maintained but without closed loop control The pressure at the output can increase or decrease over the medium term Fig 22 11 Eliminating faults Cause Status of the LED displays Power LED green ERROR LED red Undervoltage or overvoltage of the setpoint value Lights up Lights up Hardware fault Overvoltage 30 V Internal temperature too high Lights up Flashing Undervoltage 18 V Out O...

Page 43: ...onnection alternatives Pressure rises too slowly Large cylinder volume and long tube length Select different parameter set Pressure constant despite modified setpoint specification Fracture of the supply cable The output pressure last set is maintained but without closed loop control The pressure at the output can increase or decrease over the medium term Supply pressure P1 too low Replace supply ...

Page 44: ...t pressure p1 at least 1 bar above output pressure p2 Overall leakage in new condition l h 5 Connections G1 8 1 8 NPT Nominalsize Ventilation Exhaust mm 6 4 5 Standardnominalflow rate see Fig 26 Protection class IP65 when mounted with tightened mounting screws in connection with connection socket according to Accessories Permissible temperature range Ambient temperature Medium temperature Storage ...

Page 45: ...x 500 Electromagneticcompati bility EMC interference emissionandimmunity to interference See declaration of conformity è www festo com CE conformity fulfilled for industrial areas Vibration and shock Vibration Shock The following data does not apply to mounting the VPPM to the bracket VAME P1 A tested as per DIN IEC 68 EN 60068 parts 2 6 for wall mounting 0 35 mm path at 10 60 Hz 5 g acceleration ...

Page 46: ...VPPM DE EN Festo VPPM 0810b English 46 Characteristic curves for flow rate 2 bar valve variant type VPPM 6L OL2H 6 bar valve variant type VPPM 6L OL6H 10 bar valve variant type VPPM 6L OL10H Fig 26 ...

Page 47: ...VPPM DE EN Festo VPPM 0810b 47 ...

Page 48: ...en Fall der Patent Gebrauchsmuster oder Geschmacks mustereintragung vorbehalten Phone 49 711 347 0 Fax 49 711 347 2144 e mail service international festo com The reproduction distribution and utilization of this docu ment as well as the comunication of its contents to others without express authorization is prohibited Offenders will be held liable for the payment of damages All rights re served in...