Travis Industries, Inc.
Model: 44 Elite
Report Number:0028WF061E
OMNI-Test Laboratories, Inc.
Table 10 – Test Configurations
Run
Startup Procedures
Combustion Air
1
Fuel Loading: Kindling and start-up fuel loaded together, a torch was used
for 60 seconds to establish a fire. At 62 minutes placed fuel load into the
firebox and closed the loading door after 70 seconds. Loading required less
than 1 minute to complete.
Door: For kindling and start-up fuel, loading door was open for 3 minutes,
then closed. Test fuel load; fuel loading door was closed 70 seconds after
loading.
Primary Air: Air control fully open for the entire test.
Secondary: No user control for secondary air.
Fan: Fan was set to an automatic setting that turns on to a desired setting
after the firebox reaches a specified temperature. Fan turned on high at
approximately 28.5 minutes after fire was lit.
Bypass: Open for 1:00 minute after lighting kindling load. Not used while
loading fuel load.
Fully open for
entire test.
3
Fuel Loading: Kindling and start-up fuel loaded together, a torch was used
for 60 seconds to establish a fire. At 68 minutes placed fuel load into the
firebox and closed the loading door after 60 seconds. Loading required less
than 1 minute to complete.
Door: For kindling and start-up fuel, loading door was open for 3 minutes,
then closed. Test fuel load; fuel loading door was closed 50 seconds after
loading.
Primary Air: Air control fully open for the entire test.
Secondary: No user control for secondary air.
Fan: Fan was set to an automatic setting that turns on to a desired setting
after the firebox reaches a specified temperature. Fan turned on high at
approximately 31 minutes after fire was lit.
Bypass: Open for 1:00 minute after lighting kindling load. Not used during
fuel loading.
Fully open for
entire test.
4
Fuel Loading: Test fuel loaded onto coal bed generated by test number 1 in
45 seconds.
Door: Open for 2:00 minutes, then closed.
Primary Air: Fully open, then set to full closed by 15.0 minutes.
Secondary: No user control for secondary air.
Fan: Fan operates automatically, was set to high the entire test.
Bypass: Not used for loading test fuel load.
Fully open for first
15.0 minutes, then
set to full closed.
11 of 158
Summary of Contents for Xtrordinair 44 Elite
Page 36: ...36 of 158 ...
Page 37: ...37 of 158 ...
Page 49: ...49 of 158 ...
Page 59: ...59 of 158 ...
Page 60: ...60 of 158 ...
Page 69: ...69 of 158 ...
Page 70: ...70 of 158 ...
Page 84: ...84 of 158 ...
Page 85: ...85 of 158 ...
Page 89: ...89 of 158 ...
Page 90: ...90 of 158 ...
Page 91: ...91 of 158 ...
Page 92: ...92 of 158 ...
Page 93: ...93 of 158 ...
Page 94: ...94 of 158 ...
Page 95: ...95 of 158 ...
Page 96: ...96 of 158 ...
Page 97: ...97 of 158 ...
Page 98: ...98 of 158 ...
Page 99: ...99 of 158 ...
Page 101: ...101 of 158 ...
Page 102: ...102 of 158 ...
Page 103: ...103 of 158 ...
Page 104: ...104 of 158 ...
Page 106: ...7 20 18 106 of 158 ...
Page 109: ...7 20 18 109 of 158 ...
Page 111: ...111 of 158 ...
Page 112: ...112 of 158 ...
Page 113: ...113 of 158 ...
Page 115: ...115 of 158 ...
Page 130: ...130 of 158 ...
Page 151: ...Safety Label 21 Travis Industries 10 24 2018 93508094 44 Elite Owner s 151 of 158 ...