8
RT-SVX34F-EN
Model Number Description
Digit 20
D
=
Factory-Powered 15A GFI
Convenience Outlet and
Non-Fused Disconnect Switch
w/External Handle
Digit 21
E
=
Field-Powered 15A GFI
Convenience Outlet
Digit 22
F
=
Trane Communication
Interface (TCI)
Digit 23
G
=
Ventilation Override
Digit 24
H
=
Hinged Service Access
Digit 25
H
=
Tool-less Condenser Hail Guards
J
=
Condenser Coil Guards
Digit 26
K
=
LCI (LonTalk)
B
=
BACnet Communications
Interface (BCI)
Digit 27
*
=
Unused Digit
Digit 28
M
=
Stainless Steel Drain Pans
Digit 29 — Condenser Coil
Options
0
=
Standard Efficiency
Condenser Coil
J
=
Corrosion Protected Condenser
Coil
Digit 30-31 — Miscellaneous
Options
P
=
Discharge Temperature
Sensor
R
=
Clogged Filter Switch
Digit 32 — Dehumidification
Option
T
=
Modulating Hot Gas Reheat
Model Number Notes
1.
All voltages are across the line
starting only.
2.
Option includes Liquid, Discharge,
Suction Valves.
3.
Supply air fan drives A thru G are
used with 27½-35 ton units only and
drives H thru N are used with 40 & 50
ton units only.
4.
Electric Heat KW ratings are based
upon voltage ratings of 208/240/480/
600 V. For a 240 V heater derated to
208 V, the resulting kW rating
decreases from 36 kW to 27 kW, and
from 54 kW to 41 kW. Voltage
offerings are as follows: (see
Table 17,
p. 46
for additional information):
5.
The service digit for each model
number contains 32 digits; all 32
digits must be referenced.
6.
Ventilation override exhaust mode is
not available for the exhaust fan with
fresh air tracking power exhaust. VOM
is available for the exhaust fan
without fresh air tracking power
exhaust.
Tons
Electric
Heater
Rated
Voltage
KW
27/
36
41/
54 72 90 108
27½
to 35
208
x
x
240
x
x
480
x
x
x
x
600
x
x
x
40
and
50
208
x
240
x
480
x
x
x
x
600
x
x
x
x