Startup
RT-SVX34F-EN
73
Note:
To adjust the damper blade stops, refer to figures
Figure 51, p. 73
to
Figure 54, p. 74
If the fan speed needs to be changed from the current
operating speed, refer to the unit wiring diagram and the
XTB1 and XTB2 terminal strip located in the economizer
section.
Table 49. Power exhaust fan performance— 27.5-35 Ton
— 60 Hz
Power Exhaust Selection
50% (min)
100% (max)
Return Duct
Static
(in. wc)
Damper Blade Open Distance (in)
1.5 (min) 4.0 (max) 1.5 (min) 4.0 (max)
CFM
0.0
3812
6866
7624
13742
0.1
3497
5296
6995
10591
0.2
3190
4458
6325
9000
0.3
2884
3812
5768
7635
0.4
2621
3359
5241
6719
0.5
2342
2885
4683
5771
Table 50. Power exhaust fan performance — 40-50 Ton —
60 Hz
Power Exhaust Selection
50% (min)
100% (max)
Damper Blade Open Distance (in)
Return Duct
Static (in. wc)
1.5 (min) 4.0 (max) 1.5 (min) 4.0 (max)
CFM
0.0
4854
8035
9708
16069
0.1
4575
7410
9151
14820
0.2
4262
6450
8552
13496
0.3
4011
6027
8021
12054
0.4
3718
5526
7436
11051
0.5
3467
5186
6933
10373
Table 51.
Power exhaust fan performance — 22.9 - 29.2
Ton — 50 Hz
Power Exhaust Selection
50% (min)
100% (max)
Damper Blade Open Distance (mm)
Return Duct
Static (Pa)
38.1
(min)
101.6
(max)
38.1
(min)
101.6
(max)
L/s
0.0
1499
2701
2999
5405
24.9
1375
2083
2751
4166
49.8
1255
1753
2488
3540
74.7
1134
1499
2269
3003
99.6
1031
1321
2061
2643
124.5
921
1135
1842
2270
Table 52. Power exhaust fan performance — 33.3 - 41.7
Ton — 50 Hz
Power Exhaust Selection
50% (min)
100% (max)
Damper Blade Open Distance (mm)
Return Duct Static
(Pa)
38.1
(min)
101.6
(max)
38.1
(min)
101.6
(max)
L/s
0.0
1909
3160
3818
6321
24.9
1800
2915
3599
5829
49.8
1676
2537
3364
5308
74.7
1577
2371
3155
4741
99.6
1462
2173
2925
4347
124.5
1364
2040
2727
4080
Figure 51.
(Upflow) Tracking exhaust damper
adjustment
Figure 52.
(Horizontal) Tracking exhaust damper
adjustment
Tracking
Damper Minimum
Adjustment Linkage
Tracking Damper
Minimum
Adjustment
Linkage