Troubleshooting
•
Measure voltage from green to red wires on 4 pin connector and document. See
Figure 59,
p. 107
to
Figure 66, p. 114
for correct unit wiring diagram.
•
Should measure less than previous reading
•
Continue process until all selector switch positions have been checked to find any dead spots
in selector switches
•
If unit ECM board fails any of these tests replace board. If ECM is found to be good but motor
still does note operate, change out motor.
VAV Electric Heat Stage(s) Failure Procedures
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary
to work with live electrical components. Have a qualified licensed electrician or other individual
who has been properly trained in handling live electrical components perform these tasks.
Failure to follow all electrical safety precautions when exposed to live electrical components
could result in death or serious injury.
In the event that the heat outputs are not energizing, properly inspect the following:
1.
Zone temperature is at or above the heating set point
•
Increase the VV550 heating set point.
2. Verify the output configuration in the VV550 setup menu.
•
Unit needs to be configured as 3 stage Electric heat.
3. Tracer Summit has the electric heat output disabled
•
Check group, global, and/or Tracer overrides to make sure they are not inhibiting heat
operation.
4. Minimum heating CFM is not being met, airflow is too low
•
Increase the airflow or lower the minimum heating flow.
5. Heat relays have failed
•
If VAV VV550 is calling in the status menu for the electric heat and the light bulb is on for
correct Binary output(s) for stage(s) of heat to be on and it is not on then check VV550 Triac
output; wiring; and Relay output.
Figure 58. ECM controller
Summary of Contents for VAV VV550 LonTalk
Page 1: ...May 2010 VAV SVP01A EN Installation Operation Programming VAV VV550 LonTalk Controller...
Page 17: ...VAV SVP01A EN 17 VAV Start Up Check Out Procedure Figure 2 VV550 single duct control diagram...
Page 18: ...18 VAV SVP01A EN VAV Start Up Check Out Procedure Figure 3 VV550 fan powered control diagram...
Page 107: ...VAV SVP01A EN 107 Troubleshooting Figure 59 VV550 single duct control diagram...
Page 108: ...108 VAV SVP01A EN Troubleshooting Figure 60 VV550 fan powered control diagram...
Page 110: ...110 VAV SVP01A EN Troubleshooting Figure 62 Single duct with three phase voltage electric heat...
Page 115: ......