background image

74

 VAV-SVP01A-EN

Sequence of Operations

Fan Off Delay

There is a 15-second fan OFF delay. When reheat is turned OFF, the controller turns the fan OFF 15 
seconds later.

Ventilation Flow Control

Ventilation flow control (VFC) is one of three supported control algorithms. It is applied to a VAV 
terminal and used to temper cold outdoor air (OA) that is brought into a building for ventilation 
purposes. The tempered air is intended to supply an air-handling unit (AHU), which provides 
comfort control to the zones it is serving. The VAV terminal supplies the correct amount of 
ventilation air and, when possible, tempers the ventilation air to reduce the load on the air handler. 
See 

Table 13, p. 74

 for ventilation flow control output control.

The ventilation flow control process is a constant volume, variable temperature process.

Single duct VAV units with either electric or hot water reheat are used. Fan-powered units are not 
used for ventilation flow control.

Ventilation flow control must have an auxiliary temperature sensor that is located and configured 
as a discharge air temperature (DAT) sensor. The required range of discharge air temperature 
setpoints is 45°F to 70°F (7.22°C to 21.11°C).

Ventilation flow control staged reheat control (electric or hot water) achieves a 30-minute average 
discharge air temperature to within ±5°F (±2.78°C) of the discharge air temperature setpoint when 
the inlet temperature is within the control range. Ventilation flow control modulating reheat control 
(hot water only) achieves a discharge air temperature to within ±5°F (±2.78°C) of the discharge air 
temperature setpoint when the inlet temperature is within the control range.

Air Valve Control

Ventilation flow control uses the air valve as a constant volume device. The unit is given a constant 
flow setpoint for air valve control (configured ventilation setpoint); the air valve only repositions 
itself in response to changes in inlet static pressure. By using pressure independent control for 
ventilation purposes, a constant volume of fresh air can be maintained, regardless of small 
fluctuations in inlet static pressure. Ventilation flow control unit can use a Ventilation Setpoint from 
a BAS system if it is valid. If unit is stand alone the ventilation flow control uses one of the following 
two airflow setpoints:

If no reheat being used, it uses the configured Ventilation Setup Occupied Setpoint;

If reheat being used, it uses the configured Local Heat Minimum Airflow.

Table 13. Ventilation flow control outputs

Occupancy mode Source temperature

Air valve control

Reheat control

Occupy standby 
bypass

Any

Constant volume (if valid, 
communicated ventilation 
setpoint; if not valid, 
configured ventilation 
setpoint)

Electric

VFC staged reheat control

Staged hot water

VFC staged reheat control

Modulating hot water

VFC modulating reheat 
control (same as STC 
capacity control)

Unoccupied

Communicated source temperature (if 
valid; if not valid, discharge air 
temperature) greater than configured 
OA low limit

Closed, 0%

Electric

Off

Staged hot water

Off

Modulating hot water

Off

Communicated source temperature (if 
valid; if not valid, discharge air 
temperature) less than configured OA 
low limit

Closed, 0%

Electric

Off

Staged hot water

On, 100% freeze 
protection

Modulating hot water

On, 100% freeze 
protection

Summary of Contents for VAV VV550 LonTalk

Page 1: ...May 2010 VAV SVP01A EN Installation Operation Programming VAV VV550 LonTalk Controller...

Page 2: ...al Protective Equipment PPE Required Installing servicing this unit could result in exposure to electrical mechanical and chemical hazards Before installing servicing this unit technicians MUST put on...

Page 3: ...copy of this document ships inside the control panel of each unit and is customer property It must be retained by the unit s maintenance personnel This booklet describes proper installation operation...

Page 4: ...D Operations 16 Communication Wiring 19 Wireless Zone Sensor 27 VAV VV550 Controller Programming and Operation 42 Chapter Overview 42 Accessing Rover Comm5 LonTalk 42 VV550 Controller Device Home Tabs...

Page 5: ...ered Units 72 Ventilation Flow Control 74 Flow Tracking 76 Air and Water Balancing 78 Chapter Overview 78 Air Balancing 78 Rover Air and Water Balancing Tool 79 Troubleshooting 83 Chapter Overview 83...

Page 6: ...ndependent of the duct pressure The damper modulates between operator set points depending on space conditions Additionally fan and heat outputs may be energized depending on the application The VAV V...

Page 7: ...Outputs Air valve close maximum output rating 12 VA Air valve open maximum output rating 12 VA Heat stage 1 maximum output rating 12 VA Heat stage 2 maximum output rating 12 VA Heat stage 3 Fan on of...

Page 8: ...e With a discharge air temperature sensor this feature exercises the air valve fan and heat in the box and records the temperature before and after the action This allows the installer to more easily...

Page 9: ...UPCM was much less cost effective Drive Min and Max from Zone Sensor When applied with a Trane zone sensor module that includes a thumbwheel setpoint the VV550 controller can easily be overridden to m...

Page 10: ...uced ventilation CO2 sensor for demand controlled ventilation Note CO2 sensor input not available on VV550 Temperature Statistics As a part of the standard application VAS calculates the minimum space...

Page 11: ...V550 board layout VAV VV550 controller and VAV 4 2 controller comparisons VAV VV550 VAV 4 2 Supports Comm5 Supports only Comm4 or Comm3 VariTrac or VariTrane No local CO2 sensor input Uses only a comm...

Page 12: ...tpoint SNVT_temp_p Heat cool mode input nviHeatCool SNVT_hvac_mode Discharge air temperature nvoDischAirTemp SNVT_temp_p Fan speed command nviFanSpeedCmd SNVT_switch Terminal load nvoTerminalLoad SNVT...

Page 13: ...2 limit nciSpaceCO2Lim SNVT_ppm SCPTlimitCO2 42 Nominal air flow nciNomFlow SNVT_flow SCPTnomAirFlow 57 Air flow measurement gain nciFlowGain SNVT_multiplier SCPTsensConstVAV 67 Minimum air flow nciMi...

Page 14: ...al safety precautions when exposed to live electrical components could result in death or serious injury Check the supply voltage at TB1 Proper polarity must be maintained TB1 1 is the hot side and TB...

Page 15: ...AC is required to power the VAV VV550 Controller and has an acceptable voltage tolerance of 18 to 32 VAC Refer to Figure 2 p 17 and Figure 3 p 18 for the VAV VV550 Controller terminal locations Replac...

Page 16: ...4 p 16 shows and describes the green status LED activity Table 4 Green status LED activity Green status LED activity Description On Power On normal operation Off One of the following Power Off Contro...

Page 17: ...VAV SVP01A EN 17 VAV Start Up Check Out Procedure Figure 2 VV550 single duct control diagram...

Page 18: ...18 VAV SVP01A EN VAV Start Up Check Out Procedure Figure 3 VV550 fan powered control diagram...

Page 19: ...ors on all links 105 at each end for Level 4 wire Use daisy chain topology Limit zone sensor communication stubs to 8 per link 50 ft each maximum Use one repeater for an additional 4 500 ft 60 devices...

Page 20: ...C dc resistance unbalance maximum 5 Mutual capacitance of a pair maximum 17 pF foot Pair to ground unbalance maximum 1 000 pF foot 1 000 ft Characteristic impedence 772 kHz 102 15 1 0 MHz 100 15 4 0...

Page 21: ...mm5 link Link repeater connections The recommended shield connections are shown in Figure 6 p 22 Use these connections for instances where shielded communication wire is used For an example of using a...

Page 22: ...ntire configuration is 4 500 ft 1 400 m 2 Comm5 wire length limitations can be extended through the use of a link repeater see Comm5 physical link repeater Figure 5 Alternate daisy chain configuration...

Page 23: ...the zone sensor The zone sensor options are Zone sensor only 2 wires Part Number X13511528010 Sensor with night set back Part Number X13511530010 Zone sensor with external adjustable Part Number X135...

Page 24: ...surfaces behind the sensor such as outside walls Air flows from adjacent zones or other units Wiring Each unit must be controlled by a zone sensor that is designated specifically for use with the VAV...

Page 25: ...ts and 24VAC with closed contacts It is activated by a dry contact switch closure Must be 14 to 18 AWG Refer to Figure 2 p 17 and Figure 3 p 18 and the sensor instructions for terminal connections Occ...

Page 26: ...stalled Auxilary sensor will be located at the discharge of the VAV unit Flow Tracking Control Two controls are used in Flow tracking controller One is configured with the Space temperature control pr...

Page 27: ...emperature setpoint functions timed override Occupied On and timed override Unoccupied Cancel information to the receiver The receiver electrically reproduces the zone temperature resistance all zone...

Page 28: ...the Sensor Setting the Rotary Address Switches on the Receiver and on the Sensor Replacing and Securing the Receiver Cover Powering the Sensor and Associating the Sensor to the Receiver Applying Powe...

Page 29: ...s of direct sunlight Avoid areas in the direct air stream of air diffusers Avoid exterior walls and other walls that have a temperature differential between their two sides Avoid areas close to source...

Page 30: ...sed for the receiver it is to be associated with 2 Make a notation of the address and location where this sensor is to be mounted Note Do not use 000 as an address for installation If you set the addr...

Page 31: ...the Receiver to the VAV Unit Controller The required power for the receiver is 24VAC or 24 Vdc and is less than 1 VA The receiver is designed to be powered by the VAV VV550 Controller See Figure 12 p...

Page 32: ...rity screw into the bottom of the receiver Figure 13 p 32 Table 8 Wiring harness wire identification Wire Label Color Function HEATING SET Brown Space temperature heating setpoint WDS only FAN SYSTEM...

Page 33: ...on which to operate LED1 LED2 and LED3 flash rapidly in succession round robin style while the channel scan is in progress Note Do not attempt association until the channel scan is finished After the...

Page 34: ...association attempt is unsuccessful the sensor will automatically reattempt association with the receiver every 10 minutes Note A disassociated sensor will transmit an association request every 10 mi...

Page 35: ...r removes all stored association information conducts a channel scan and restarts itself if any of the following are true The receiver address is changed from its current setting 001 999 The receiver...

Page 36: ...nant from making changes Configuration Procedure To configure settings on the model WDS sensor follow this procedure in the order presented 1 Press the configuration button for 3 seconds The display w...

Page 37: ...1 Wireless configuration Setting Configuration options Temperature Choose Fahrenheit or Celsius Choose the degree resolution whole degrees half degrees or tenths of degrees Setpoint Deadband available...

Page 38: ...not available on VAV units Occupancy timed override Setting Configuration options emergency heat heat cool off heat cool auto off emergency heat heat cool auto off no system options enabled auto off...

Page 39: ...t the bottom of the display between the occupancy symbols as shown in below SeeTable 20 p 92 for error code definitions Figure 22 Configuration options The example shows a display that has been config...

Page 40: ...n lock or unlock the setpoint system or fan setting to prevent changes To lock or unlock the settings 1 Verify that the sensor is in operating mode and at the home screen 2 Choose a setting to lock or...

Page 41: ...om the zone sensor 3 Press the left and right arrows for 4 seconds If you try to access a feature that is locked the lock symbol will appear on the displays If you press a keypad button to try and cha...

Page 42: ...or Instructions on how to use Rover Comm5 refer to the Rover Comm5 online Help by clicking Contents and Index on the Help menu Laptop Requirements and Complete Connection Instructions For instructions...

Page 43: ...s means that you can configure setpoints and other controller parameters but cannot create bindings or set up peer to peer Comm5 networks All other Rover Comm5 features are available 5 Rover Comm5 wil...

Page 44: ...in configuration as either Primary Air or Discharge air temperature depending on unit control strategies See Configuration section for more details Airflow Measured in CFM When a valid flow value is p...

Page 45: ...ll be located in troubleshooting section of this manual Use the Reset Diagnostic button to reset the diagnostic from this point A reset clears latching diagnostics and enables the controller to try to...

Page 46: ...ly resumes pressure independent control Initiate Calibration button The calibration sequence enables the controller to calibrate the air valve position and the water valve position Unit Description De...

Page 47: ...io limit is not sufficient the controller can raise its minimum airflow setpoint as long as the space temperature remains under control Effective Ventilation Setpoint The Tracer Summit BAS uses the ef...

Page 48: ...sting of the fan and the reheat The fan and the reheat are not tested if the discharge air temperature sensor is not present The fan is not tested if there is no fan Local reheat is tested if it is pr...

Page 49: ...Record the auxiliary temperature at the configured maximum airflow 2 Close the primary air valve 3 Turn on the fan if present 4 Monitor auxiliary temperature for 3 minutes or until it changes by 10 F...

Page 50: ...ce State Mode This point indicates if Rover is communicating with controller The two states are Configured On line or Not Communicating Manufacturer ID Trane will be the manufacture displayed for the...

Page 51: ...g Wait for 15 minutes Rover Comm5 does not need to be online with the controller For each controller in the service mode click the Exit Service Mode button Overriding VAVs When you override a controll...

Page 52: ...e menu and click Save As 3 The Save As dialog box will appear Name unit and click Save Downloading Program Files from PC to VAV VV550 Controller 1 Select the Configure button and the Configuration scr...

Page 53: ...on 2 Click the File menu and click Open 3 The Open dialog box will appear Select the file you wish to open and click the Open button 4 Download to DDC VAV controller 5 Program is now in controller Fig...

Page 54: ...ke adjustments find the correct parameter change it and download to VV550 Setpoints Tab In Rover the setpoints can be changed by selecting the Configure button Following are descriptions of each line...

Page 55: ...de the active space heating setpoint is the occupied stand by heating setpoint The controller can be placed in the occupied standby mode when a communicated occupancy mode request from a communicated...

Page 56: ...ally generated overrides maximum flow or minimum flow are not possible Enable Thumbwheel Star and Double Star Function Single star and double star airflow override capability can be disabled through c...

Page 57: ...switches to the desired mode based on the primary air temperature Note It can also be done with a communicated request Primary Air Setup Auto Changeover Setpoint The auto change over set point allows...

Page 58: ...Control This entry will determine if a parallel fan will be controlled based on zone temperature or on flow conditions The entry field on this line will disappear if the unit does not have a parallel...

Page 59: ...to calculate this value and balance the VAV box Normally you should not need to change this value here Tracking Offset This field is available only if the controller is using flow tracking control Ty...

Page 60: ...the unoccupied mode this setpoint is the active setpoint for ventilation Space CO2 Setup CO2 sensor communicated value only Low Limit The controller adjusts the ventilation setpoint only when the CO2...

Page 61: ...rooftop unit with staged heat that needs a Max constant volume of air movement to keep the heat exchanger from overheating and tripping the heat in the rooftop unit tripping on a high limit safety Lo...

Page 62: ...is connected to a zone sensor This input can be used only to read the local space temperature setpoint from the zone sensor Analog Input 3 This area displays Airflow Sensor when the analog input is co...

Page 63: ...utput 2 to modulate the air valve Binary Output 2 Binary output 1 is used to drive the air valve open It works in conjunction with binary output 1 to modulate the air valve Output Configuration Wizard...

Page 64: ...answers in the Output Configuration Wizard Device Contacts Normally Open Select this check box if the device contacts are normally open This check box is available only for hot water on off control Te...

Page 65: ...t value In the Offset field type a negative or positive number to add to the hardwired setpoint After calibration the effective value should match the value indicated on the zone sensor thumbwheel Str...

Page 66: ...er will calibrate during power up control wait Overrides To access the data fields for each tab and to make adjustments select the Overrides button In the Override list select the valve or fan you wan...

Page 67: ...ible for the staggering of the calibration sequence that is needed between units When autocalibration is enabled and a transition from occupied to unoccupied occurs the calibration sequence starts aft...

Page 68: ...e is unoccupied It can be activated for a classroom currently not in use The controller can be placed in the occupied standby mode when a communicated occupancy mode request from a communicated occupa...

Page 69: ...control positions the modulating air valve to deliver the desired airflow cooling or heating capacity Cooling Operation Under space temperature control during the coolingmode communicated heat coolmod...

Page 70: ...le For local reheat only the fan if present is not being overridden to Off communicated fan speed command The primary air temperature is less than the configured reheat enable setpoint 5 F 2 78 C Loca...

Page 71: ...Hydronic heat is enabled if there is no valid primary air temperature Hydronic heat is disabled if the primary air temperature is greater than the configured reheat enable setpoint ON Off Hot Water He...

Page 72: ...apacity Valve drive Incrementally open closed Total capacity limited by communicated auxiliary heat enable Not applicable Note Abbreviations Zt Zone temperature HSP Heating setpoint Table 12 Local hea...

Page 73: ...or occupied standby mode Cycles ON with a call for heat during unoccupied mode When the primary air temperature is warm or hot the parallel fan is OFF unless the local reheat is ON Two methods of cont...

Page 74: ...within 5 F 2 78 C of the discharge air temperature setpoint when the inlet temperature is within the control range Air Valve Control Ventilation flow control uses the air valve as a constant volume de...

Page 75: ...trol Units equipped with hot water coils should be sized so the maximum temperature of air leaving the coil does not exceed 140 F 60 C F Since only one stage of hot water reheat is available staged ho...

Page 76: ...rol algorithms Two VAV VV550 Controllers work together to provide flow tracking control See Figure 50 p 77 The space temperature controller outputs the airflow reported airflow The space temperature c...

Page 77: ...working together space temperature controller and flow tracking controller The space temperature controller outputs the airflow as reported airflow The airflow is determined by the airflow setpoint i...

Page 78: ...t diameter long run of straight ducting into the VAV units inlet System Setup Set the outside air dampers to their minimum position Start the supply and return air fan s Before balancing the system en...

Page 79: ...e overridden to Drive MAX in the Override menu in Rover However this will be more time consuming Rover Air and Water Balancing Tool The Rover Air and Water Balancing tool assists with air and water ba...

Page 80: ...his option select a job from the list then click the Delete Job button to delete a job Select Job to Open Shows a list of existing jobs Use this list to select an existing job to open or delete Create...

Page 81: ...ent job names for each link Job Name The name of the currently open job You cannot change this name on the Job tab Address 1 and 2 Type the street address of the job City Type the name of the city whe...

Page 82: ...ancing tool they do not affect the units used in the controller or in Rover Comm5 Change Airflow Units button This button appears only if you select to use SI units Click this button to select one of...

Page 83: ...edures Wired Zone Sensor Failure Procedures Wired Zone Setpoint Failure Procedures Wireless Zone Sensor Failure Procedures Airflow Failure Procedures Duct Temperature Sensor Failure Procedures VAV Dam...

Page 84: ...s reported are listed to aid in understanding current operation Reported items are 1 Timed Override Exists 2 Cancel Timed Override 3 Auxiliary Temperature Sensor Not Present 4 Unoccupied Request from...

Page 85: ...int Unoccupied closed Series fan enabled parallel fan Off Off Space temperature fail ventilation flow control c Normal Don t care Normal Space temperature fail flow tracking control c Normal Don t car...

Page 86: ...tore the unit to normal operation Refer the Rover product literature for more information The Service push button can be used as one of several methods to install the controller in a communication net...

Page 87: ...power Check device using Rover service tool to see if the VAV VV550 is operating properly If VV550 does operate properly check inputs outputs for a short 3 For final step check program by downloading...

Page 88: ...sult in system instability If no voltage check up stream of controller to see were voltage has been interrupted See complete wiring diagrams Figure 59 p 107 to Figure 66 p 114 2 Communication link sig...

Page 89: ...Startup Check out Procedure chapter for the wiring specifications for VV550 3 Defective zone sensor Disconnect the zone sensor terminal plug from the VV550 and using an Ohmmeter measure the resistance...

Page 90: ...l of the recommended safety warnings provided could result in death or serious injury In the event that the VV550 reports an incorrect zone setpoint properly inspect the following 1 Zone sensor setpoi...

Page 91: ...3 replace VV550 4 Zone sensor setpoint is shorted out Check the resistance across the wires Disconnect wires from VV550 and zone sensor making sure the ends are not touching each other and measure re...

Page 92: ...or 1 4s Off for 1 4s with 2s OPff between repetitions Table 21 Diagnostics on the receiver LED state Indicates LED1 Off LED2 Off LED3 1 blink pattern repeated continuously a Disassociated Receiver is...

Page 93: ...ction LED Display Indicates None LED1 Off LED2 Off LED3 Off Normal state No Test button press Press Test Button SS LED1 Off LED2 Off LED3 Off Associated no communication with receiver Associated but n...

Page 94: ...gnal quality The LEDs can be observed on both the sensor Table 26 p 95 and the receiver Table 27 p 95 Table 24 Output failure modes of operation Situation Zone Temperature Output Zone Setpoint Output...

Page 95: ...LED3 Off Associated no communication with receiver Associated but no signal from the receiver after pressing Test button LED1 On LED2 On LED3 On Displays for 5 seconds then constantly off Excellence...

Page 96: ...e VAV board will automatically cause the unit to calibrate however following the procedure outlined below will provide a more accurate calibration It is only necessary to perform this procedure in ins...

Page 97: ...oged If no voltage indicated replace the VAV VV550 Controller Remove the high and low tubes from the transducer to simulate no flow Read the transducer output voltage on P1 of the VAV VV550 Controller...

Page 98: ...check incoming power to the VV550 board on TB1 1 24VAC input and TB1 2 Voltage should measure 24VAC 10 If you measure the proper voltage at TB1 1 24VAC input and TB1 2 and no voltage at TB3 5 and TB3...

Page 99: ...24VAC directly to common blue and jumper closed red wire to a ground to drive damper closed Damper should drive closed Note VV550 Outputs are switched to ground Do not jumper 24VAC to J1 3 of J1 4 bec...

Page 100: ...ecause damage will occur 6 After all checks have been completed check motor fan winding integrity and bearing failure VAV Parallel Fan Failure Procedures WARNING Hazardous Service Procedures The maint...

Page 101: ...it is not then check the VAV VV550 Controller Triac output wiring and Relay output Check J8 to common TB1 2 Should have 24VAC if it does not measure the power input to on TB1 1 24VAC input and TB1 2 o...

Page 102: ...n exposed to live electrical components could result in death or serious injury If ECM is not controlling Fan Motor properly inspect the following Note The ECM controller has 4 wire pin connector that...

Page 103: ...trical components perform these tasks Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury In the event that the heat...

Page 104: ...ual who has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical safety precautions when exposed to live electrical components could result...

Page 105: ...valve or if tapped with a tool while still on the valve Note Actuator indicator on the side of the actuator should be positioned at the top of the actuator when valve is closed VAV Two Position Hot Wa...

Page 106: ...power input to TB1 1 24VAC input and TB1 2 of the VV550 board The supply voltage should be between 20 and 28 VAC 24VAC cataloged However voltages at either extreme may result in system instability Not...

Page 107: ...VAV SVP01A EN 107 Troubleshooting Figure 59 VV550 single duct control diagram...

Page 108: ...108 VAV SVP01A EN Troubleshooting Figure 60 VV550 fan powered control diagram...

Page 109: ...DAMPER PRESSURE 24V HEATER TERMINAL BOX OPTIONAL TRANSFORMER 208 240 480 FUSE OPTIONAL SEE NAMEPLATE LINE VOLTAGE V O AIR FLOW SWITCH BL Y OPTIONAL THERMAL BR CUTOUT R Y BL Y AUTO RESET CUTOUT MANUAL...

Page 110: ...110 VAV SVP01A EN Troubleshooting Figure 62 Single duct with three phase voltage electric heat...

Page 111: ...R BK DISCONNECT OPTIONAL FUSE BK R 1 2 3 4 SWITCH RELAY MOTOR BK BK BR BK W W CONTROL BOX VV550 BL 24V Y BR W MOTOR W W L1 L2 N 208 240 480 L1 N 277 347 OPTIONAL DISCONNECT SWITCH HEATER TERMINAL BOX...

Page 112: ...112 VAV SVP01A EN Troubleshooting Figure 64 SCR PSC fan powered with three phase voltage electric heat...

Page 113: ...LD INSTALLED DIGITAL DISPLAY ZONE SENSOR W COMM JACK 11 10 7 6 TB1 2 TB1 1 TB2 6 3 2 1 TB3 1 TB3 3 TB3 2 CONTACTORS HEAT 1 277 347 240 STAGES 1 CLOSE BOARD ECM TRANSDUCER TB3_1 TB3_2 TB3_3 TB3_5 TB3_6...

Page 114: ...114 VAV SVP01A EN Troubleshooting Figure 66 ECM fan powered with three phase voltage electric heat...

Page 115: ......

Page 116: ...r e mail us at comfort trane com Literature Order Number VAV SVP01A EN Date May 2010 Supersedes VAV SVP01A EN February 2010 Trane has a policy of continuous product and product data improvement and re...

Reviews: