BAS-SVX065E-EN
49
Table
17.
Output
test
states
State
Mode
(a)
ECM
Fan
Speed
Fan
Enable
/
High
Water
Side
Econo-
mizer
Fan
Low
Comp
1
Comp
2
Electric
Heat/Hot
Gas
Reheat
Electric
Heat
(Units
With
Both
HGR
and
EH)
Revers-
ing
Valve
Isola-
tion
Valve
Outdoor
Air
Damper
AO1
BO1
BO2
BO3
BO4
BO5
BO6
XM32
BO1
BO7
BO8
BO9
1
Off
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
2
Isolation
V
alve
Open
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
3
F
an
Low
MIN
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
4
F
an
High
MAX
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
5
W
ater
Side
Economizer
MAX
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
6
Compressor
Cool
Stage
1
MAX
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
7
Compressor
Cool
Stage
2
MAX
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
8
Hot
Gas
R
eheat
MAX
ON
OFF
OFF
ON
OFF
ON
OFF
ON
ON
OFF
Units
Without
Hot
Gas
R
eheat
MAX
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
9
Elec
Heat
Only
(Boilerless)
MAX
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
Concurrent
(DX
Heat
+
Elec
Heat)
MAX
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
Elec
Heat
Only
(Boilerless)
Units
Equiped
With
Both
HGR
and
EH
MAX
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
OFF
Concurrent
(DX
Heat
+
Elec
Heat)
Units
Equiped
With
Both
HGR
and
EH
MAX
ON
OFF
OFF
ON
ON
OFF
ON
OFF
ON
OFF
Units
Without
Elec
Heat
MAX
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
10
Compressor
Heat
Stage
1
MAX
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
11
Compressor
Heat
Stage
2
MAX
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
OFF
12
Outside
Air
Damper
MAX
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
13
Normal
Operation
Turn
All
Outputs
OFF,
Then
Release
to
Normal
Control
Immediately
(a)
A
60
minute
time
limit
will
be
imposed
on
each
Mode
step.
Once
the
timer
expires,
the
unit
will
transition
back
to
normal
control.
If
the
unit
is
actively
operating
when
a
T
est
Mode
is
requested,
the
unit
will
follow
all
startup
and
shutdown
requirements
to
energize/de-energize
the
compressor
and
supply
fan
outputs.
If
an
optional
output
is
not
present
then
the
current
step
is
the
same
as
the
prior
step
unless
otherwise
stated
in
the
table.