RLC-SVX14H-GB
12
General data
Table 3 - RTWD Extra High Effi ciency - R134a
RTWD
RTWD
RTWD
160
180
200
Indicative performances
Cooling Capacity (1)
(kW)
598
659
709
Total Power input in cooling (1)
(kW)
114
126
136
Heating Capacity (2)
(kW)
629
691
744
Total Power input in heating (2)
(kW)
138
153
166
Compressor
Compressor Number per Circuit
#
1/1
1/1
1/1
Type
Screw
Model
M2/M2
M2/N1
N1/N1
Evaporator
Quantity
#
1
1
1
Type
Flooded shell and tube heat exchanger
Evaporator model
E4AM1
E4AMJ
E5AMJ
Evaporator Water Content volume
(l)
72.6
77.0
84.5
Two pass evaporator
Evap. Water Flow rate - Minimum (3)
(l/s)
11.7
12.7
15.1
Evap. Water Flow rate - Maximum (3)
(l/s)
43.0
46.6
55.3
Nominal water connection size (Grooved coupling)
(in) - (mm)
611
(168.3 mm)
611
(168.3 mm)
611
(168.3 mm)
Three pass evaporator
Evap. Water Flow rate - Minimum (3)
(l/s)
7.8
8.5
10.1
Evap. Water Flow rate - Maximum (3)
(l/s)
28.6
31
36.9
Nominal water connection size (Grooved coupling)
(in) - (mm)
411
(114.3 mm)
411
(114.3 mm)
411
(114.3 mm)
Condenser
Quantity
#
1
1
1
Type
Shell and Tube Heat Exchanger
Condenser model
C4AM2
C4AMJ
C5AMJ
Condenser Water Content volume
(l)
Two pass condenser
113.4
130.6
148.2
Cond. Water Flow rate - Minimum
(l/s)
12.9
15.4
20.5
Cond. Water Flow rate - Maximum
(l/s)
47.5
56.4
75.1
Nominal water connection size (Grooved coupling)
(in) - (mm)
6” (168.3)
6” (168.3)
6” (168.3)
Dimensions (4)
Unit Length
(mm)
3830
3830
3490
Unit Width
(mm)
1280
1310
1310
Unit Height
(mm)
2010
2010
2010
Weights (5)
Shipping Weight
(kg)
3954
4175
4357
Operating Weight
(kg)
4172
4408
4625
System data (6)
Nb of refrigerant circuit
#
2
2
2
Minimum cooling load %
%
30
30
30
Standard unit
R134a refrigerant charge Circuit1 / Circuit 2 (6)
(kg)
80/80
79/81
80/79
Oil charge Circuit1 / Circuit 2
(l)
9.9/9.9
9.9/9.9
9.9/9.9
POE Oil type
OIL048E or OIL023E
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser water temperature 30°C/35°C - for detailed performances consult
order write up.
(2) Indicative performance at Evaporator water temperature: 10°C / 7°C - Condenser water temperature 40°C/45°C - for detailed performances consult
order write up.
(3) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(4) These dimensions are the maximum for a specifi c size, they may vary from one confi guration to another within a same size. For accurate
dimensions of a specifi c confi guration, refer to relevant submittal drawings.
(5) All w/-5% and are the maximum for each size and may vary from one confi guration to another for the same size (add 62kg for unit with
acoustic package) and refer to relevant drawing for a specifi c confi guration.
(6) System data are indicative and subject to change without notice. Please refer to unit nameplate data.