RLC-SVX14H-GB
10
General data
Table 2 - RTWD High Effi ciency - R134a
RTWD
RTWD
RTWD
RTWD
RTWD
RTWD
RTWD
60
70
80
90
100
110
120
Indicative performances
Cooling Capacity (1)
(kW)
235.0
276.0
317.0
365.0
390.0
417.0
452.0
Total Power input in cooling (1)
(kW)
48.0
57.0
65.0
74.0
79.0
84.0
91.0
Heating Capacity (2)
(kW)
250.3
299.2
340.1
386.8
414.1
443.9
477.4
Total Power input in heating (2)
(kW)
57.9
70.1
80.0
90.4
96.1
102.4
109.2
Compressor
Compressor Number per Circuit
#
1/1
1/1
1/1
1/1
1/1
1/1
1/1
Type
Screw
Model
K1/K1
K2/K2
K2/L1
L1/L1
L1/L2
L2/L2
L2/M1
Evaporator
Quantity
#
1
1
1
1
1
1
1
Type
Flooded shell and tube heat exchanger
Evaporator model
E1AM2
E1AM1
E1AMJ
E2AM2
E2AM2
E2AM1
E2AMJ
Evaporator Water Content volume
(l)
37.0
40.2
45.2
57.9
57.9
62.3
65.4
Two pass evaporator
Evap. Water Flow rate - Minimum (3) (l/s)
4.5
5.0
5.7
7.0
7.0
7.7
8.2
Evap. Water Flow rate - Maximum
(3)
(l/s)
16.6
18.4
21.1
25.7
25.7
28.2
30.0
Nominal water connection size
(Grooved coupling)
(in) -
(mm)
411
(114.3 mm)
411
(114.3 mm)
411
(114.3 mm)
5 1”
(139.7 mm)
5 1”
(139.7 mm)
5 1”
(139.7 mm)
5 1”
(139.7 mm)
Three pass evaporator
Evap. Water Flow rate - Minimum (3) (l/s)
3.0
3.3
3.8
4.7
4.7
5.1
5.4
Evap. Water Flow rate - Maximum
(3)
(l/s)
11
12.2
14.1
17.2
17.2
18.8
20
Nominal water connection size
(Grooved coupling)
(in) -
(mm)
3"
(88.9 mm)
3"
(88.9 mm)
3"
(88.9 mm)
4"
(114.3 mm)
4"
(114.3 mm)
4"
(114.3 mm)
4"
(114.3 mm)
Condenser
Quantity
#
1
1
1
1
1
1
1
Type
Shell and Tube Heat Exchanger
Condenser model
C1AM2
C1AM2
C1AMJ
C2AM3
C2AM2
C2AM2
C2AMJ
Condenser Water Content volume
(l)
45.1
45.1
52.2
58.1
62.7
62.7
68.3
Two pass condenser
Cond. Water Flow rate - Minimum
(l/s)
5.4
5.4
6.6
7.3
8.1
8.1
9.1
Cond. Water Flow rate - Maximum
(l/s)
19.9
19.9
24.4
26.9
29.8
29.8
33.2
Nominal water connection size
(Grooved coupling)
(in) -
(mm)
5 1”
(139.7 mm)
5 1”
(139.7 mm)
5 1”
(139.7 mm)
5 1”
(139.7 mm)
5 1”
(139.7 mm)
5 1”
(139.7 mm)
5 1”
(139.7 mm)
Dimensions (4)
Unit Length
(mm)
3320
3320
3320
3320
3320
3320
3320
Unit Width
(mm)
1070
1070
1070
1060
1060
1060
1060
Unit Height
(mm)
1940
1940
1940
1960
1960
1960
1960
Weights (5)
Shipping Weight
(kg)
2568
2573
2637
2812
2849
2883
3065
Operating Weight
(kg)
2650
2658
2673
2928
2970
3008
3198
System data (6)
Nb of refrigerant circuit
#
2
2
2
2
2
2
2
Minimum cooling load %
%
30
30
30
30
30
30
30
Standard unit
R134a refrigerant charge Circuit1 /
Circuit 2 (6)
(kg)
45/45
45/45
44/44
55/55
55/56
55/55
54/54
Oil charge Circuit1 / Circuit 2
(l)
6.8/6.8
6.8/6.8
6.8/6.8
6.8/6.8
6.8/9.9
9.9/9.9
9.9/9.9
POE Oil type
OIL048E or OIL023E
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser water temperature 30°C/35°C - for detailed performances consult
order write up.
(2) Indicative performance at Evaporator water temperature: 10°C / 7°C - Condenser water temperature 40°C/45°C - for detailed performances consult
order write up.
(3) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(4) These dimensions are the maximum for a specifi c size, they may vary from one confi guration to another within a same size. For accurate
dimensions of a specifi c confi guration, refer to relevant submittal drawings.
(5) All w/-5% and are the maximum for each size and may vary from one confi guration to another for the same size (add 62kg for unit with
acoustic package) and refer to relevant drawing for a specifi c confi guration.
(6) System data are indicative and subject to change without notice. Please refer to unit nameplate data.