INSTRUCTION MANUAL
UG30 CONTROL
18 (44)
mP30-UG30 - Rev. 1.5 - Date: 18-03-2004
EN
The functions associated with the keys can be disabled by setting the USER
Hi=1
parameter (see paragraph
“ACCESS TO PARAMETERS WHILE CONSULTING OR PROGRAMMING”).
GLb
G
ENERAL INFORMATION
Minimum Maximum
Measurement
unit
Default
Hi
Prevents unauthorised operators from modifying parameters (the “padlock”
symbol is shown).
0 = no lock
1= lock out of all functions for modifying parameters, and resetting alarms
and hour-counters (except access to the USER password and keyboard
power down) – the padlock symbol is shown on the display).
0 1 flag 0
INFORMATION ON DISPLAY WHEN UNIT IS OFF
STATUS MASK
When the unit is powered up
but not running
, the STATUS MASK is shown on the display indicating the following
active fields:
A.
Room temperature, room relative humidity (with humidity sensor only);
B.
The indication:
•
“ ” and "
": unit turned OFF from a remote contact or a
Supervisor;
•
"
unit turned OFF according to set hour bands.
C.
Unit turned OFF due to alarm status:
MENU
PARAMETER
DESCRIPTION