34
CHILLED WATER UNIT - RADIAL FANS WITH E.C. TECHNOLOGY
Technical characteristics
1) Unit in complete version (including packaging)
2) 0060B units available only in versions without electrical heaters
3) Nominal air flow – Maximum fan power supply
4) Minimum air flow only allowed for unit without electrical resistances
1) Unit in complete version (including packaging)
2) 0060A units available only in versions with standard or improved electrical heaters
3) Nominal air flow – Maximum fan power supply
4) Minimum air flow only allowed for unit with electrical resistances
Model
0020B
0025B
0030B
0040B
0060B2
Height
mm
1740
1740
1740
1740
1740
Width
mm
550
550
550
550
850
Depth
mm
450
450
450
450
450
Weight1
kg
120
145
145
170
225
Air Flow
m
3
/h
1610
2280
2305
3265
4490
e.S.P Maximum 3
Pa
106
53
34
63
20
Minimum air flow
m
3
/h
10404
11504
19404
19404
3020
Power supply voltage
V/ph/Hz
230/1n/50
230/1n/50
230/1n/50
230/1n/50
230/1n/50
Model
0020A
0025A
0030A
0040A
0060A2
Height
mm
1740
1740
1740
1740
1740
Width
mm
550
550
550
550
850
Depth
mm
450
450
450
450
450
Weight 1
kg
120
145
145
170
225
Air Flow
m
3
/h
1610
2280
2305
3265
4490
e.S.P Maximum 3
Pa
106
53
34
63
20
Minimum air flow
m
3
/h
10404
21504
21504
21504
3200
Power supply voltage
V/ph/Hz
400/3n/50
400/3n/50
400/3n/50
400/3n/50
400/3n/50