CVHH-SVX001G-EN
65
Terminal Clamps
N
NO
OT
TIIC
CE
E
U
Usse
e C
Co
op
pp
pe
err C
Co
on
nd
du
ucctto
orrss O
On
nlly
y!!
F
Fa
aiillu
urre
e tto
o u
usse
e cco
op
pp
pe
err cco
on
nd
du
ucctto
orrss cco
ou
ulld
d rre
essu
ulltt iin
n
e
eq
qu
uiip
pm
me
en
ntt d
da
am
ma
ag
ge
e a
ass tth
he
e e
eq
qu
uiip
pm
me
en
ntt w
wa
ass n
no
ott
d
de
essiig
gn
ne
ed
d o
orr q
qu
ua
alliiffiie
ed
d tto
o a
acccce
ep
ptt o
otth
he
err tty
yp
pe
ess o
off
cco
on
nd
du
ucctto
orrss..
X39003892001A
N
No
otte
e:: Graphic labels (shown above) are used for CE
application only.
IIm
mp
po
orrtta
an
ntt::
•
Before servicing, disconnect all power
sources and allow at least 30 minutes
for capacitors to discharge.
•
All electrical enclosures—unit or remote
—are IP2X.
Terminal clamps are supplied with the motor terminals
to accommodate either bus bars or standard motor
terminal wire lugs. Terminal clamps provide additional
surface area to minimize the possibility of improper
electrical connections.
Wire Terminal Lugs
N
NO
OT
TIIC
CE
E
C
Co
om
mp
po
on
ne
en
ntt D
Da
am
ma
ag
ge
e!!
F
Fa
aiillu
urre
e tto
o e
en
nssu
urre
e tth
he
e p
po
ow
we
err ssu
up
pp
plly
y w
wiirriin
ng
g a
an
nd
d
o
ou
uttp
pu
utt tto
o m
mo
otto
orr w
wiirriin
ng
g a
arre
e cco
on
nn
ne
ecctte
ed
d tto
o tth
he
e
p
prro
op
pe
err tte
errm
miin
na
allss cco
ou
ulld
d cca
au
usse
e cca
atta
assttrro
op
ph
hiicc ffa
aiillu
urre
e
o
off tth
he
e sstta
arrtte
err a
an
nd
d//o
orr m
mo
otto
orr..
Wire terminal lugs must be field supplied.
•
Use field-provided, crimp-type wire terminal lugs
properly sized for the application.
N
No
otte
e:: Wire size ranges for the starter line and load-
side lugs are listed on the starter submittal
drawings supplied by the starter
manufacturer or Trane. Carefully review the
submitted wire lug sizes for compatibility
with the conductor sizes specified by the
electrical engineer or contractor.
•
On 600V and below,
a terminal clamp with a
3/8-in. (9.525-mm) bolt is provided on each motor
terminal stud; use the factory-supplied Belleville
washers on the wire lug connections. The following
figure illustrates the junction between a motor
terminal stud and terminal lug.
•
Torque for this assembly is 24 ft·lb (32.5 N·m).
•
Install but do NOT connect the power leads
between the starter and compressor motor. (These
connections will be completed under supervision of
a qualified Trane service engineer after the pre-start
inspection.)