20
CVHH-SVX001G-EN
Table 5.
Representative weights, 60 Hz chillers (kg)
Model
Comp Size
CPKW
Evap Size
Cond Size
Weights without Starters
NTON
EVSZ
CDSZ
Operating
Shipping
CVHH
900–1200
1228
100M
100M
21523
18629
900–1200
1228
100L
100L
22340
19218
900–1200
1340
100M
10HM
24947
21681
900–1200
1340
130M
130M
23981
20364
900–1200
1340
130M
13HM
28206
24221
900–1200
1340
160M
200M
28873
24322
900–1200
1340
200L
220L
32642
26731
900–1200
1340
220L
220L
35871
29331
1500–1700
1340
200L
200L
32169
26824
1500–1700
1340
200L
20HL
36406
30646
1500–1700
1340
220L
220L
35871
29331
1500–1700
1340
220L
22HL
42364
35407
Notes:
1
.
TECU tubes, 0.71 mm tube wall thickness.
2
.
2068.4 kPaG marine waterboxes.
3
.
Heaviest possible bundle and motor combination.
4
.
Operating weights assume the largest possible refrigerant charge.
5
.
Industrial Control Panel (INDP) option, add 23 kg.
6
.
Control Power Transformer (CPTR) option, add 127 kg.
7
.
Supplemental Motor Protection (SMP) option, add 227 kg.
8
.
To calculate the maximum chiller weight with starter/drive, add the starter/AFD weight from the following table (maximum weights, unit-mounted
starters/AFDs [kg]) to the chiller maximum weight from this table.
Table 6.
Representative weights, 50 Hz chillers (kg)
Model
Comp Size
CPKW
Evap Size
Cond Size
Weights without Starters
NTON
EVSZ
CDSZ
Operating
Shipping
CVHH
950–1050
1023
100M
100M
22237
19343
950–1050
1023
100L
100L
23053
19931
950–1050
1023
100M
10HM
25729
22463
950–1050
1023
130M
130M
24763
21146
950–1050
1023
130M
13HM
28988
25003
950–1050
1023
160M
200M
29655
25104
950–1050
1023
200L
220L
33424
27513
950–1050
1023
220L
220L
36653
30113
1550
1023
200L
200L
32815
27470
1550
1023
200L
20HL
37052
31292
1550
1023
220L
220L
36517
29977
1550
1023
220L
22HL
43010
36053
Notes:
1
.
TECU tubes, 0.71 mm tube wall thickness.
2
.
2068.4 kPaG marine waterboxes.
3
.
Heaviest possible bundle and motor combination.
4
.
Operating weights assume the largest possible refrigerant charge.
5
.
Industrial Control Panel (INDP) option, add 23 kg.
6
.
Control Power Transformer (CPTR) option, add 127 kg.
7
.
Supplemental Motor Protection (SMP) option, add 227 kg.
8
.
To calculate the maximum chiller weight with starter/drive, add the starter/AFD weight from the following table (maximum weights, unit-mounted