background image

8

 ACC-SVN67M-EN

Installation

1. Remove heater compartment access panel and unit 

control box access panel. See 

Figure 2

.

Note:

On downflow units with or without duct work 
installed or horizontal units without ductwork 
installed, remove horizontal supply cover from the 
rear of the heater compartment.

2. Remove insulation to expose perimeter of removable 

panel in the vestibule panel. Se

Figure 2

3. Clip or cut the retaining tabs around the perimeter of the 

removable panel.

4. Remove the panel.
5. Check the opening in the vestibule panel. Remove any 

metal burrs or slivers that could damage or pinch the 
heater elements resulting in a short circuit when elements 
are installed in the opening.

Note:

Locator tabs on the vestibule panel support the 
electric heat assembly and secure the inward edge 
of the electric heat accessory control panel. Slits in 
the insulation should allow the tabs to protrude 
through the insulation and be visible. However, it 
may be necessary to work the insulation back from 
the tabs and slightly bend the tabs outward if 
difficulty is encountered engaging the electric 
heater panel or the electric heat accessory control 
panel. See 

Figure 3

.

6. The electric heater element assembly has “BOTTOM” 

stamped in the mounting panel to identify the proper 
position for mounting. 

7. Refer to 

Table 2

. If the unit/heater combination being 

installed is the same as any in this table 

and the 

application is for horizontal airflow

, the limit control 

TCO-A must be replaced with the extra limit control 
shipped with the heater. Replace TCO-A following the 
instructions in 

Step 8

 and 

Step 9

. If the unit/heater 

combination being installed does not correspond to any in 
this table or if the application is for downflow airflow, skip 
steps 8 and 9 and go on to 

Step 10

.

WARNING

Hazardous Voltage w/Capacitors!

Failure to disconnect power and discharge capacitors 

before servicing could result in death or serious injury. 

Disconnect all electric power, including remote 

disconnects and discharge all motor start/run 

capacitors before servicing. Follow proper lockout/

tagout procedures to ensure the power cannot be 

inadvertently energized. For variable frequency drives 

or other energy storing components provided by Trane 

or others, refer to the appropriate manufacturer’s 

literature for allowable waiting periods for discharge of 

capacitors. Verify with a CAT III or IV voltmeter rated per 

NFPA 70E that all capacitors have discharged.

WARNING

Fire Hazard!

On BAYHTRA, BAYHTRB, BAYHTRD, BAYHTRU, and 

BAYHTRW heater kits, failure to allow a one inch 

clearance from the supply ductwork to any combustible 

materials could cause the combustible materials to 

catch on fire which could result in death, serious injury, 

or property damage.

Figure 2. Control covers and access panels

Horizontal
Supply
Cover

Control
Box
Access
Panel

Removable
Insulation

Removable
Panel

Heat
Section 
Access
Panel

Figure 3. Electric heater element panel

Summary of Contents for BAY24X042

Page 1: ...and requires specific knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe...

Page 2: ...ous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or prope...

Page 3: ...ment are the trademarks of their respective owners Revision History Updated Heater Model Number for WSC120H3 in Electrical Data chapter WARNING Follow EHS Policies Failure to follow instructions below...

Page 4: ...4 ACC SVN67M EN Table of Contents General Information 5 General 7 Inspection 7 Installation 8 Electrical Data 12...

Page 5: ...H3 a WHC074H3 WHC092H3 WHC102H3 THC102F3 WSC120H3 BAYHTRA327 TSC120H3 WSC090H3 a THC074F3 TZC072F3 WSC102H3 a WSC120H3 THC092F3 TZC090F3 THC102F3 TZC102F3 TSC092H3 TSC102H3 WSC092H3 a WHC074H3 WHC092H...

Page 6: ...HC120H4 BAYHTRB436 WHC120H4 BAYHTRB454 WHC120H4 BAYHTRBW18 TZC120FW WHC120HW BAYHTRBW36 WHC120HW BAYHTRBW54 WHC120HW BAYHTRD318 THC120E3 TZC120F3 BAYHTRD327 THC120E3 TZC120F3 BAYHTRD336 THC120E3 BAYHT...

Page 7: ...must be reported immediately and a claim made against the transportation company 3 Check the heater nameplate model number and compare with the electrical data tables Ensure that the available power s...

Page 8: ...the same as any in this table and the application is for horizontal airflow the limit control TCO A must be replaced with the extra limit control shipped with the heater Replace TCO A following the in...

Page 9: ...rt rod hanger The BAYHTRA BAYHTRB and BAYHTRD models will have a guide rod and a support bracket to help with the installation See Figure 5 Be very careful to avoid dragging the heater element on the...

Page 10: ...ush against center post and secure each door stop with 1 or 2 screws See zoom view in Figure 8 or Figure 9 14 Remove the wire nuts from W1 W2 and W3 15 For models with the control box in the outdoor s...

Page 11: ...with ohmmeter and verify that heater element terminals are electrically isolated from cabinet and ground infinite resistance On downflow units with or without duct work installed or horizontal units w...

Page 12: ...nimum allowable airflow for a TSC120EF TZC120F and THC120E with a 54 kW heater is 3400 cfm e The minimum allowable airflow for a WSC120 with a 54 kW heater is 4000 cfm Table 4 Unit wiring with electri...

Page 13: ...35 34 35 33 35 7 5 c TSC092H4 BAYHTRT427 BAYHTRA427 d 27 2 44 45 48 50 47 50 7 5 c TSC092H4 BAYHTRT436 BAYHTRA436 d 36 2 58 60 61 70 60 60 8 5 TSC102H4 BAYHTRT409 BAYHTRA409 d 9 1 21 25 23 25 22 25 8...

Page 14: ...er Model Number Heater kW Rating Control Stages Standard Indoor Fan Motor a Oversized Indoor fan Motor Optional EBM Fan Motor MCA Max Fuse Size or Max Circuit Breaker MCA MaxFuseSize or Max Circuit Br...

Page 15: ...1 34 40 35 40 34 40 8 5 WSC102H4 BAYHTRU418 BAYHTRA418 18 0 1 47 50 49 50 48 50 8 5 WSC102H4 BAYHTRU427 BAYHTRA427 27 0 2 61 70 62 70 61 70 8 5 WSC102H4 BAYHTRU436 BAYHTRA436 36 0 2 74 80 76 80 75 80...

Page 16: ...or Max Circuit Breaker MCA Max Fuse Size or Max Circuit Breaker 208 230 Volts Three Phase 6 WHC074H3 BAYHTRA309 6 8 9 0 1 66 69 70 70 6 WHC074H3 BAYHTRA318 13 5 18 0 1 89 96 90 100 6 WHC074H3 BAYHTRA...

Page 17: ...nnection high efficiency and eFlex 6 to 10 tons Standard Indoor Motor Oversized Indoor Motor Tons Unit Model Number Heater Model Number Heater kW Rating a Control Stages MCA Max Fuse Size or Max Circu...

Page 18: ...AYHTRA409 9 0 1 18 9 25 6 THC074F4 BAYHTRA418 18 0 1 32 5 35 6 THC074F4 BAYHTRA427 27 0 2 46 0 50 460 Volts Three Phase 6 THC074F4 BAYHTRA436 36 0 2 59 5 60 6 TZC072F4 BAYHTRA409A 9 1 10 8 26 6 TZC072...

Page 19: ...egrees C b Degrees F c 6 Ton 7 5 Ton 10 Ton 6 Ton 7 5 Ton 10 Ton kW Voltage Stages 4100 M3 H 5100 M3 H 6800 M3 H kW Voltage Stages 2400 cfm 3000 cfm 4000 cfm WSC072ED WSC090ED WSC120 ED WSC072ED WSC09...

Page 20: ...umCircuit Breaker TSC072ED BAYHTRS418 11 3 13 5 39 47 1 26 9 28 9 35 35 28 1 30 1 35 35 BAYHTRS427 16 9 20 2 58 69 2 37 5 40 5 40 45 38 8 41 8 40 45 BAYHTRS436 22 6 26 9 78 92 2 48 3 52 1 50 60 49 5 5...

Page 21: ...Notes ACC SVN67M EN 21...

Page 22: ...Notes 22 ACC SVN67M EN...

Page 23: ...Notes ACC SVN67M EN 23...

Page 24: ...cations without notice We are committed to using environmentally conscious print practices Trane and American Standard create comfortable energy efficient indoor environments for commercial and reside...

Reviews: