Electrical Data

Table 3. Air temperature rise (60 Hz)

(a)

6 Ton

7.5 Ton

7.5 Ton

8.5 Ton

10 Ton

2000 cfm

(b),(c)

 (2)

3000 cfm

3000 cfm

3400 cfm

4000 cfm

(d),(e)

Nominal 

kW Input

No. of 

Capacity 

Stages

T*C072E3
T*C072E4

T*C072EW

THC074F3
THC074F4

TZC072F3, 
TZC072F4, 

and 

TZC072FW

WSC072H3
WSC072H4

WSC072HW

TSC090E3
TSC090E4

TSC090EW 

WSC092H3 
WSC092H4 

WSC092HW 

TSC092E3 
TSC092E4 

TSC092EW

THC092F3,4

TZC090F3, 
TZC090F4, 

and 

TZC090FW

WSC090H3 
WSC090H4 

WSC090HW

T*C102E3 
T*C102E4

THC102F3,4

TSC102EW

TZC102F3, 
TZC102F4, 

and 

TZC102FW

WSC102H3W

SC102H4WS

C102HW

THC120E3 
THC120E4 
TSC120H3
TSC120H4

TSC120HW

TZC120F3, 
TZC120F4, 

and 

TZC120FW

WSC120H3
WSC120H4

WSC120HW

9.0

1

14.2

14.2

9.5

9.5

9.5

9.5

8.4

8.4

11.3

1

14.9

14.9

11.9

11.9

16.9

2

22.3

22.3

17.8

17.8

15.7

15.7

15.7

15.7

13.4

13.4

18.0

1

28.5

28.5

19.0

19.0

19.0

19.0

16.7

16.7

14.2

14.2

22.6

2

29.8

29.8

23.8

23.8

21.0

21.0

7.9

17.9

27.0

2

42.7

42.7

28.5

28.5

28.5

28.5

25.1

25.1

21.3

21.3

33.80

2

26.7

26.7

36.00

2

56.9

56.9

37.9

37.9

37.9

37.9

33.5

33.5

28.5

28.5

54.00

2

42.7

42.7

(a) The air temperature rise (F) across the heaters is: (Heater kW x 3414)/(1.08 x cfm).
(b) The minimum allowable airflow for TSC072E, TZC072F with a 36.0 kW heater is 2200 cfm.
(c) The minimum allowable airflow for WSC072H with a 36.0 kW heater is 2450 cfm.
(d) The minimum allowable airflow for a TSC120EF, TZC120F and THC120E with a 54 kW heater is 3400 cfm.
(e) The minimum allowable airflow for a WSC120 with a 54 kW heater is 4000 cfm.

Table 4. Unit wiring with electric heat (single point connection) - standard efficiency 

 

Standard Indoor Fan 

Motor

(a)

Oversized Indoor Fan 

Motor

(b)

Optional EBM Fan 

Motor

Tons

Unit Model

Number

Heater Model 

Number

Heater kW 

Rating

Control 

Stages

MCA

Max Fuse Size or 

Max Circuit 

Breaker

MCA

Max Fuse Size 

or Max Circuit 

Breaker

MCA

Max Fuse 

Size or Max 

Circuit 

Breaker

208/230 Volts Three Phase

6

TSC072H3

BAYHTRS309*

6.8/9.0

1

35/35

50/50

38/38

50/50

6

TSC072H3

BAYHTRS318*

13.5/18.0

1

53/60

60/60

56/64

60/70

6

TSC072H3

BAYHTRS327*

20.3/27.0

2

76/87

80/90

80/91

80/100

6

TSC072H3

BAYHTRS336*

27.0/36.0

2

100/114

110/125

103/118

110/125

7.5

TSC090H3

BAYHTRW309*

6.8/9.0

1

38/38

60/60

44/44

60/60

7.5

TSC090H3

BAYHTRW318*

13.5/18.0

1

53/60

60/60

60/67

60/70

7.5

TSC090H3

BAYHTRW327*

20.3/27.0

2

76/87

80/90

84/94

90/100

7.5

TSC090H3

BAYHTRW336*

27.0/36.0

2

99/114

100/125

107/122

110/125

7.5

(c)

TSC092H3

BAYHTRT309*

BAYHTRA309

(d)

6.8/9.0

1

39/39

50/50

45/45

50/50

43/43

50/50

7.5

(c)

TSC092H3

BAYHTRT318*

BAYHTRZ318

(d)

13.5/18.0

1

53/60

60/60

60/67

60/70

58/65

60/70

7.5

(c)

TSC092H3

BAYHTRT327*

BAYHTRA327

(d)

20.3/27.0

2

76/87

80/90

84/94

90/100

81/92

90/100

7.5

(c)

TSC092H3

BAYHTRT336*

BAYHTRZ336

(d)

27.0/36.0

2

99/114

100/125

107/122

110/125

104/119

110/125

8.5

TSC102H3

BAYHTRT309*

BAYHTRA309

(d)

6.8/9.0

1

44/44

50/50

47/47

60/60

45/45

60/60

Summary of Contents for BAY24X042

Page 1: ...and requires specific knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe...

Page 2: ...ous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or prope...

Page 3: ...ment are the trademarks of their respective owners Revision History Updated Heater Model Number for WSC120H3 in Electrical Data chapter WARNING Follow EHS Policies Failure to follow instructions below...

Page 4: ...4 ACC SVN67M EN Table of Contents General Information 5 General 7 Inspection 7 Installation 8 Electrical Data 12...

Page 5: ...H3 a WHC074H3 WHC092H3 WHC102H3 THC102F3 WSC120H3 BAYHTRA327 TSC120H3 WSC090H3 a THC074F3 TZC072F3 WSC102H3 a WSC120H3 THC092F3 TZC090F3 THC102F3 TZC102F3 TSC092H3 TSC102H3 WSC092H3 a WHC074H3 WHC092H...

Page 6: ...HC120H4 BAYHTRB436 WHC120H4 BAYHTRB454 WHC120H4 BAYHTRBW18 TZC120FW WHC120HW BAYHTRBW36 WHC120HW BAYHTRBW54 WHC120HW BAYHTRD318 THC120E3 TZC120F3 BAYHTRD327 THC120E3 TZC120F3 BAYHTRD336 THC120E3 BAYHT...

Page 7: ...must be reported immediately and a claim made against the transportation company 3 Check the heater nameplate model number and compare with the electrical data tables Ensure that the available power s...

Page 8: ...the same as any in this table and the application is for horizontal airflow the limit control TCO A must be replaced with the extra limit control shipped with the heater Replace TCO A following the in...

Page 9: ...rt rod hanger The BAYHTRA BAYHTRB and BAYHTRD models will have a guide rod and a support bracket to help with the installation See Figure 5 Be very careful to avoid dragging the heater element on the...

Page 10: ...ush against center post and secure each door stop with 1 or 2 screws See zoom view in Figure 8 or Figure 9 14 Remove the wire nuts from W1 W2 and W3 15 For models with the control box in the outdoor s...

Page 11: ...with ohmmeter and verify that heater element terminals are electrically isolated from cabinet and ground infinite resistance On downflow units with or without duct work installed or horizontal units w...

Page 12: ...nimum allowable airflow for a TSC120EF TZC120F and THC120E with a 54 kW heater is 3400 cfm e The minimum allowable airflow for a WSC120 with a 54 kW heater is 4000 cfm Table 4 Unit wiring with electri...

Page 13: ...35 34 35 33 35 7 5 c TSC092H4 BAYHTRT427 BAYHTRA427 d 27 2 44 45 48 50 47 50 7 5 c TSC092H4 BAYHTRT436 BAYHTRA436 d 36 2 58 60 61 70 60 60 8 5 TSC102H4 BAYHTRT409 BAYHTRA409 d 9 1 21 25 23 25 22 25 8...

Page 14: ...er Model Number Heater kW Rating Control Stages Standard Indoor Fan Motor a Oversized Indoor fan Motor Optional EBM Fan Motor MCA Max Fuse Size or Max Circuit Breaker MCA MaxFuseSize or Max Circuit Br...

Page 15: ...1 34 40 35 40 34 40 8 5 WSC102H4 BAYHTRU418 BAYHTRA418 18 0 1 47 50 49 50 48 50 8 5 WSC102H4 BAYHTRU427 BAYHTRA427 27 0 2 61 70 62 70 61 70 8 5 WSC102H4 BAYHTRU436 BAYHTRA436 36 0 2 74 80 76 80 75 80...

Page 16: ...or Max Circuit Breaker MCA Max Fuse Size or Max Circuit Breaker 208 230 Volts Three Phase 6 WHC074H3 BAYHTRA309 6 8 9 0 1 66 69 70 70 6 WHC074H3 BAYHTRA318 13 5 18 0 1 89 96 90 100 6 WHC074H3 BAYHTRA...

Page 17: ...nnection high efficiency and eFlex 6 to 10 tons Standard Indoor Motor Oversized Indoor Motor Tons Unit Model Number Heater Model Number Heater kW Rating a Control Stages MCA Max Fuse Size or Max Circu...

Page 18: ...AYHTRA409 9 0 1 18 9 25 6 THC074F4 BAYHTRA418 18 0 1 32 5 35 6 THC074F4 BAYHTRA427 27 0 2 46 0 50 460 Volts Three Phase 6 THC074F4 BAYHTRA436 36 0 2 59 5 60 6 TZC072F4 BAYHTRA409A 9 1 10 8 26 6 TZC072...

Page 19: ...egrees C b Degrees F c 6 Ton 7 5 Ton 10 Ton 6 Ton 7 5 Ton 10 Ton kW Voltage Stages 4100 M3 H 5100 M3 H 6800 M3 H kW Voltage Stages 2400 cfm 3000 cfm 4000 cfm WSC072ED WSC090ED WSC120 ED WSC072ED WSC09...

Page 20: ...umCircuit Breaker TSC072ED BAYHTRS418 11 3 13 5 39 47 1 26 9 28 9 35 35 28 1 30 1 35 35 BAYHTRS427 16 9 20 2 58 69 2 37 5 40 5 40 45 38 8 41 8 40 45 BAYHTRS436 22 6 26 9 78 92 2 48 3 52 1 50 60 49 5 5...

Page 21: ...Notes ACC SVN67M EN 21...

Page 22: ...Notes 22 ACC SVN67M EN...

Page 23: ...Notes ACC SVN67M EN 23...

Page 24: ...cations without notice We are committed to using environmentally conscious print practices Trane and American Standard create comfortable energy efficient indoor environments for commercial and reside...

Reviews: