Trane ADD1B060A9H31B Installer'S Manual Download Page 15

Installer’s Guide

18-CD21D1-12

TABLE 7

MASONRY CHIMNEY VENTING

Type Furnace

Tile Lined Chimney

Chimney Lining

Internal

External

“B” Vent

Flexible  

Metal Liner

Single Fan  

Assist

No

No

Yes

Yes*

Fan Assist

+

Fan Assist

No

No

Yes

Yes*

Fan Assist 

Natural

Yes

No

Yes

Yes*

* Flexible chimney liner size is determined by using the type “B” vent size 

for the available BTUH input, then reducing the maximum capacity by 20% 

(multiply maximum capacity times 0.80).  The minimum capacity is the same 

as shown in the “B” vent tables.

 
External Masonry Chimney

Venting of fan assisted appliances into external chim-
neys (one or more walls exposed to outdoor tempera-

tures),  requires  the  chimney  be  lined  with  type  “B”, 

double wall vent or suitable flexible chimney liner 
material. This applies in all combinations of common 
venting as well as for fan assisted appliances vented 
alone.

WARNING

!

CARBON MONOXIDE POISONING HAZARD

Failure to follow the installation instructions for the 

venting system being placed into operation could re-

sult in carbon monoxide poisoning or death.

 
The following installation practices are recommended 
to minimize corrosion caused by condensation of flue 
products in the furnace and flue gas system.
  1.  Avoid an excessive number of bends.

  2.  Horizontal  runs  should  pitch  upward  at  least  1/4" 

per foot.

  3.  Horizontal runs should be as short as possible.
  4. All vent pipe or connectors should be securely sup-

ported and must be inserted into, but not beyond 
the inside wall at the chimney vent.

  5.  When vent connections must pass through walls or 

partitions of combustible material, a thimble must 
be used and installed according to local codes.

  6.  Vent pipe through the roof should be extended to 

a height determined by National Fuel Gas Code or 
local codes. It should be capped properly to prevent 
rain water from entering the vent. Roof exit should 
be waterproofed.

  7.  Use type “B” double wall vent when vent pipe is 

routed through cool spaces (below 60° F.).

VENT PIPING

These furnaces have been classified as Fan-Assisted 
Combustion System, Category I furnaces under the 

“latest edition” provisions of ANSI Z21.47 and CAN/ 

CGA 2.3 standards. Category I furnaces operate with a 
non-positive vent static pressure and with a flue loss of 
not less than 17 percent.

NOTE:

If desired, a side wall termination can be accomplished 

through the use of an “add-on” draft inducer. The in-

ducer must be installed according to the inducer man-

ufacturer’s instructions. Set the barometric pressure 

relief to achieve -0.02 inch water column.

NOTE: When the downflow furnace is vented through 

the left side of the furnace cabinet using the provided 

cutout, Type B vent piping must be used.

The furnace shall be connected to a factory built chim-

ney or vent complying with a recognized standard, or a 

masonry or concrete chimney lined with a lining mate-

rial acceptable to the authority having jurisdiction.

WARNING

!

Furnace venting into an unlined masonry chimney or 

concrete chimney is prohibited.

Failure to follow this warning could result in property 

damage, personal injury, or death.
 
VENTING INTO A MASONRY CHIMNEY

If the chimney is oversized, the liner is inadequate, or 
flue-gas condensation is a problem in your area, con-
sider using the chimney as a pathway or chase for type 

“B” vent or flexible vent liner. If flexible liner material 
is  used,  size  the  vent  using  the  “B”  vent  tables,  then 

reduce the maximum capacity by 20% (multiply 0.80 

times  the  maximum   capacity).  Masonry  Chimney  Kit 
BAYVENT800B may be used with these furnaces 

(Up-

flow model furnaces only)

 to allow venting into a 

masonry chimney. Refer to the BAYVENT800B Install

-

er’s Guide for application  requirements.

INTERNAL MASONRY CHIMNEYS

Venting of fan assisted appliances into a lined, inter-
nal masonry chimney is allowed only if it is common 
vented with at least one natural draft appliance; 

OR

if the chimney is lined with type “B”, double wall vent 

or suitable flexible liner material (See Table 7).

WARNING

!

The chimney liner must be thoroughly inspected to 

insure no cracks or other potential areas for flue gas 

leaks are present in the liner. Liner leaks will result in 

early deterioration of the chimney.

Failure to follow this warning could result in carbon 

monoxide poisoning or death.

NOTE:

The following section does not apply if BAYVENT800B 

(Masonry Chimney Vent Kit) is used. All instructions 

with the kit must be followed.

Summary of Contents for ADD1B060A9H31B

Page 1: ...with this unit Please return to service information pack upon completion of work Installer s Guide UD1B100A9H31B UD1B100G9H31A UD1C100A9H51B UD1C100G9H51A UD1D120A9H51B UD1D120G9H51A UD1D140A9H51B UD1...

Page 2: ...ate mark ing e 100 of the furnace combustion air requirement must come from outside the structure SAFETY SECTION CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each ap...

Page 3: ...ty signal words are used to designate a degree or level of seriousness associated with a particular hazard The signal words for safety markings are WARNING and CAUTION a WARNING indicates a potentiall...

Page 4: ...avoid physical damage from vehicles GENERAL INSTALLATION INSTRUCTIONS The manufacturer assumes no responsibility for equip ment installed in violation of any code or regulation It is recommended that...

Page 5: ...D TUD1A040A9H21B TUD1A040G9H21A 14 1 2 9 5 8 13 1 4 13 TUD1B060A9H31B TUD1B060G9H31A TUD1B080A9H31B TUD1B080G9H31A TUD1B100A9H31B TUD1B100G9H31A 17 1 2 9 5 8 16 1 4 16 TUD1C080A9H41B TUD1C080G9H41A T...

Page 6: ...6 18 CD21D1 12 Installer s Guide From Dwg 21C341700 Sh 1 Rev 0 DD1 HF OUTLINE DRAWING ALL DIMENSIONS ARE IN INCHES...

Page 7: ...coil in the horizontal posi tion See Figure 4 IMPORTANT The 2 4TXC cased coil must be placed downstream of the furnace In horizontal installations the apex of the coil may point either toward or away...

Page 8: ...ir open ings provided in the furnace casing must be kept free of obstructions which restrict the flow of air Airflow restrictions affect the efficiency and safe operation of the furnace Keep this in m...

Page 9: ...rcial buildings Buildings with indoor pools Furnaces installed in commercial laundry rooms Furnaces installed in hobby or craft rooms Furnaces installed near chemical storage areas Exposure to the fol...

Page 10: ...the space containing the furnace Minimum return air entering temperature for the furnace is 55 F Where there is no complete return duct system the re turn connection must be run full size from the fur...

Page 11: ...Thin cloths should be placed over the registers and the furnace fan should be run for 10 minutes Don t forget to remove the cloths be fore you start the furnace FILTER REMOVE FILTER FROM UPFLOW FURNAC...

Page 12: ...ACK960 The following checklist should be used when installing a right or left side return filter on an upflow furnace a Remove the filter b Leave the bottom panel in place c Make side cutout by follow...

Page 13: ...stream of the fur nace See Figure 17 UPFLOW FILTER CLIP BRACKET INSTALLATION 1 Determine the location to be used The furnace cabinet has dimples for location of the alter nate furnace clips Side retur...

Page 14: ...4 or the CAN CGA B149 Installation Codes and these instructions Determine that there is no blockage or restriction leakage corrosion and other deficiencies which could cause an unsafe condition 3 As f...

Page 15: ...isions of ANSI Z21 47 and CAN CGA 2 3 standards Category I furnaces operate with a non positive vent static pressure and with a flue loss of not less than 17 percent NOTE If desired a side wall termin...

Page 16: ...ATIONS d ELECTRICAL CONNECTIONS WARNING The cabinet must have an uninterrupted or unbroken ground according to National Electrical Code ANSI NFPA 70 latest edition and Canadian Electrical Code CSA C22...

Page 17: ...SING A 1 STAGE HEATING THERMOSTAT NO COOLING From Dwg 21B341437 P01 OUTDOOR UNIT NO TRANSFORMER SEE NOTE 6 From Dwg B341436 Rev 1 SEE NOTE 8 FURNACE TWIN SEE NOTE 7 B C B C TO 115 V 1 PH 60 HZ POWER S...

Page 18: ...PERATION OF UNIT NO 2 IS SYNCRONIZED WITH UNIT NO 1 VIA SIGNALS FROM TWIN CONNECTION SEE NOTE 4 SEE NOTE 3 ISOLATION RELAY FIELD SUPPLIED SEE NOTE 4 ISOLATION RELAY SEE NOTE 4 B C B C B C From Dwg 21B...

Page 19: ...g by closing its individual manual shut off valve dur ing any pressure testing of the gas supply piping sys tem at test pressures equal to or less than 1 2 psig CAUTION Use a backup wrench on the gas...

Page 20: ...from the utility company and compare to the nameplate rating This must not exceed the nameplate rating Gas Valve Adjustment Changes can be made by adjusting the manifold pres sure See Table 12 or cha...

Page 21: ...the heating value obtained from the local utility supplier for the gas being delivered at the in stalled altitude Input rate changes can be made by adjusting the manifold pressure min 3 0 max 3 7 in...

Page 22: ...is satisfied TO SHUT OFF For complete shutdown Move the control switch on the main gas valve to the OFF position See Figures 25 and 26 Disconnect the electrical supply to the unit CAUTION If this is d...

Page 23: ...CONTROL AND SAFETY SWITCH ADJUSTMENT LIMIT SWITCH CHECK OUT The limit switch is a safety device designed to close the gas valve should the furnace become overheated Since proper operation of this swit...

Page 24: ...g cycle the pressure switch will cause the gas valve to close and shut the unit down Carbon monoxide fire or smoke can cause serious bodi ly injury death and or property damage A variety of potential...

Reviews: