Trane ADD1B060A9H31B Installer'S Manual Download Page 10

10 

 18-CD21D1-12

Installer’s Guide

DUCT CONNECTIONS

Air duct systems should be installed in accordance 
with standards for air conditioning systems, National 
Fire Protection Association Pamphlet No. 90. They 
should be sized in accordance with ACCA Manual D 
or whichever is applicable.  Check on controls to make 
certain they are correct for the electrical supply.
Central furnaces, when used in connection with cool-
ing units, shall be installed in parallel or on the up-
stream side of the cooling units to avoid condensation 
in the heating element, unless the furnace has been 
specifically approved for downstream installation. 
With a parallel flow arrangement, the dampers or oth-
er means used to control flow of air shall be adequate 
to prevent chilled air from entering the furnace, and if 
manually operated, must be equipped with means to 
prevent operation of either unit unless the damper is 
in full heat or cool position.
On any job, flexible connections of nonflammable ma-
terial may be used for return air and discharge con-
nections to prevent transmission of vibration.  Though 
these units have been specifically designed for quiet, 
vibration free operation, air ducts can act as sounding 
boards and could, if poorly installed, amplify the slight-
est vibration to the annoyance level.
When the furnace is located in a utility room adjacent 
to the living area, the system should be carefully de-
signed with returns which minimize noise transmis-
sion through the return air grille. Although these 
winter air conditioners are designed with large blow-
ers operating at moderate speeds, any blower moving 
a high volume of air will produce audible noise which 
could be objectionable when the unit is located very 
close to a living area. It is often advisable to route the 
return air ducts under the floor or through the attic.  
Such design permits the installation of air return re-
mote from the living area (i.e. central hall).
When the furnace is installed so that the supply ducts 
carry air circulated by the furnace to areas outside the 
space containing the furnace, the return air shall also 
be handled by a duct(s) sealed to the furnace and ter-
minating outside the space containing the furnace.

Minimum return air “entering temperature” for 
the furnace is 55° F.

Where there is no complete return duct system, the re-
turn connection must be run full size from the furnace 
to a location outside the utility room, basement, attic, 
or crawl space.

NOTE:  DO NOT install return air through the 
back of the furnace cabinet.

RETURN AIR DUCT CONNECTION

NOTE:

On upflow 5 or 6 ton airflow models, if the airflow re-

quirement exceeds 1800 CFM, these models will re-

quire return air openings and  filters on both sides; OR 

1 side and the bottom; OR just the bottom.

WARNING

!

TO PREVENT INJURY OR DEATH DUE TO CONTACT 
WITH  MOVING  PARTS,  TURN  THE  POWER  TO  THE 
FURNACE OFF BEFORE SERVICING FILTERS.

inlet duct, add to cut where indicated by solid lines 
in  Figure 12. Cut corners diagonally and bend out-
ward to form flange.

 6. If flanges are not required, and a filter frame is 

installed, cut between the locating notches.  See 
Figure 12.

 7. 

Upflow Furnaces:

  Two clips are factory supplied 

for bottom or side return. Use the filter rack on ei-
ther side or on the bottom if the filter is to be used 
within the furnace cabinet.

WARNING

!

Do  NOT  install  the  filter  in  the  return  duct  directly 
above  the  furnace  in  horizontal  applications.  Install 
the  filter  remotely.  Installing  the  filter  directly  above 
the  furnace  in  horizontal  applications  may  cause 
property damage, serious injury or death.

All return air duct systems should provide for installa-
tion of return air filters.

PREPARATION FOR UPFLOW BOTTOM AND SIDE 
RETURN AIR FILTER INSTALLATION

All return air duct systems should provide for installa-
tion of return air filters.
  1.  Determine the appropriate postion to set the fur-

nace in order to connect to the supply and return 
ductwork.

  2.  The return air filter are shipped in either the 

bottom or side location.  Remove the filter by first 
turning the two latches on the blower door and tilt-
ing the door forward to remove.  Remove the filter 
by sliding it out.

  3.  For upflow side return installations, remove the 

 insulation around the opening in the blower com-
partment.

  4.  The side panels of the upflow furnace include 

locating notches that are used as guides for cutting 
an opening for return air, refer to Figure 12 and 
the outline drawing on page 5 for duct connection 
dimensions for various furnaces.

  5.  If  a  3/4"  flange  is  to  be  used  for  attaching  the  air 

Summary of Contents for ADD1B060A9H31B

Page 1: ...with this unit Please return to service information pack upon completion of work Installer s Guide UD1B100A9H31B UD1B100G9H31A UD1C100A9H51B UD1C100G9H51A UD1D120A9H51B UD1D120G9H51A UD1D140A9H51B UD1...

Page 2: ...ate mark ing e 100 of the furnace combustion air requirement must come from outside the structure SAFETY SECTION CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each ap...

Page 3: ...ty signal words are used to designate a degree or level of seriousness associated with a particular hazard The signal words for safety markings are WARNING and CAUTION a WARNING indicates a potentiall...

Page 4: ...avoid physical damage from vehicles GENERAL INSTALLATION INSTRUCTIONS The manufacturer assumes no responsibility for equip ment installed in violation of any code or regulation It is recommended that...

Page 5: ...D TUD1A040A9H21B TUD1A040G9H21A 14 1 2 9 5 8 13 1 4 13 TUD1B060A9H31B TUD1B060G9H31A TUD1B080A9H31B TUD1B080G9H31A TUD1B100A9H31B TUD1B100G9H31A 17 1 2 9 5 8 16 1 4 16 TUD1C080A9H41B TUD1C080G9H41A T...

Page 6: ...6 18 CD21D1 12 Installer s Guide From Dwg 21C341700 Sh 1 Rev 0 DD1 HF OUTLINE DRAWING ALL DIMENSIONS ARE IN INCHES...

Page 7: ...coil in the horizontal posi tion See Figure 4 IMPORTANT The 2 4TXC cased coil must be placed downstream of the furnace In horizontal installations the apex of the coil may point either toward or away...

Page 8: ...ir open ings provided in the furnace casing must be kept free of obstructions which restrict the flow of air Airflow restrictions affect the efficiency and safe operation of the furnace Keep this in m...

Page 9: ...rcial buildings Buildings with indoor pools Furnaces installed in commercial laundry rooms Furnaces installed in hobby or craft rooms Furnaces installed near chemical storage areas Exposure to the fol...

Page 10: ...the space containing the furnace Minimum return air entering temperature for the furnace is 55 F Where there is no complete return duct system the re turn connection must be run full size from the fur...

Page 11: ...Thin cloths should be placed over the registers and the furnace fan should be run for 10 minutes Don t forget to remove the cloths be fore you start the furnace FILTER REMOVE FILTER FROM UPFLOW FURNAC...

Page 12: ...ACK960 The following checklist should be used when installing a right or left side return filter on an upflow furnace a Remove the filter b Leave the bottom panel in place c Make side cutout by follow...

Page 13: ...stream of the fur nace See Figure 17 UPFLOW FILTER CLIP BRACKET INSTALLATION 1 Determine the location to be used The furnace cabinet has dimples for location of the alter nate furnace clips Side retur...

Page 14: ...4 or the CAN CGA B149 Installation Codes and these instructions Determine that there is no blockage or restriction leakage corrosion and other deficiencies which could cause an unsafe condition 3 As f...

Page 15: ...isions of ANSI Z21 47 and CAN CGA 2 3 standards Category I furnaces operate with a non positive vent static pressure and with a flue loss of not less than 17 percent NOTE If desired a side wall termin...

Page 16: ...ATIONS d ELECTRICAL CONNECTIONS WARNING The cabinet must have an uninterrupted or unbroken ground according to National Electrical Code ANSI NFPA 70 latest edition and Canadian Electrical Code CSA C22...

Page 17: ...SING A 1 STAGE HEATING THERMOSTAT NO COOLING From Dwg 21B341437 P01 OUTDOOR UNIT NO TRANSFORMER SEE NOTE 6 From Dwg B341436 Rev 1 SEE NOTE 8 FURNACE TWIN SEE NOTE 7 B C B C TO 115 V 1 PH 60 HZ POWER S...

Page 18: ...PERATION OF UNIT NO 2 IS SYNCRONIZED WITH UNIT NO 1 VIA SIGNALS FROM TWIN CONNECTION SEE NOTE 4 SEE NOTE 3 ISOLATION RELAY FIELD SUPPLIED SEE NOTE 4 ISOLATION RELAY SEE NOTE 4 B C B C B C From Dwg 21B...

Page 19: ...g by closing its individual manual shut off valve dur ing any pressure testing of the gas supply piping sys tem at test pressures equal to or less than 1 2 psig CAUTION Use a backup wrench on the gas...

Page 20: ...from the utility company and compare to the nameplate rating This must not exceed the nameplate rating Gas Valve Adjustment Changes can be made by adjusting the manifold pres sure See Table 12 or cha...

Page 21: ...the heating value obtained from the local utility supplier for the gas being delivered at the in stalled altitude Input rate changes can be made by adjusting the manifold pressure min 3 0 max 3 7 in...

Page 22: ...is satisfied TO SHUT OFF For complete shutdown Move the control switch on the main gas valve to the OFF position See Figures 25 and 26 Disconnect the electrical supply to the unit CAUTION If this is d...

Page 23: ...CONTROL AND SAFETY SWITCH ADJUSTMENT LIMIT SWITCH CHECK OUT The limit switch is a safety device designed to close the gas valve should the furnace become overheated Since proper operation of this swit...

Page 24: ...g cycle the pressure switch will cause the gas valve to close and shut the unit down Carbon monoxide fire or smoke can cause serious bodi ly injury death and or property damage A variety of potential...

Reviews: