152
Address Setting-Umatch ODU
SW6 dip switch setting
Unit address for
central control
SW6-1
SW6-2
SW6-3
SW6-4
SW6-5
SW6-6
SW6-7
SW6-8
0
0
0
0
0
0
0
0
Address 0
0
0
0
0
0
0
0
1
Address 1
0
0
0
0
0
0
1
0
Address 2
0
0
0
0
0
0
1
1
Address 3
0
0
0
0
0
1
0
0
Address 4
0
0
0
0
0
1
0
1
Address 5
0
0
0
0
0
1
1
0
Address 6
0
0
0
0
0
1
1
1
Address 7
0
0
0
0
1
0
0
0
Address 8
0
0
0
0
1
0
0
1
Address 9
0
0
0
0
1
0
1
0
Address 10
0
0
0
0
1
0
1
1
Address 11
0
0
0
0
1
1
0
0
Address 12
……
…..
1
1
1
1
1
1
1
1
Address 256
Indoor unit Central Control Address
Set Address by Outdoor PCB
Indoor connect port
3U***
A
B
C
4U***
A
B
C
D
5U***
A
B
C
D
E
4
3
2
1
Indoor central control address
SW06
0
0
0
0
1
2
3
4
5
0
0
0
1
6
7
8
9
10
0
0
1
0
11
12
13
14
15
0
0
1
1
16
17
18
19
20
0
1
0
0
21
22
23
24
25
0
1
0
1
26
27
28
29
30
0
1
1
0
31
32
33
34
35
0
1
1
1
36
37
38
39
40
1
0
0
0
41
42
43
44
45
1
0
0
1
46
47
48
49
50
1
0
1
0
51
52
53
54
55
1
0
1
1
56
57
58
59
60
1
1
0
0
61
62
63
64
65
1
1
0
1
66
67
68
69
70
1
1
1
0
71
72
73
74
75
1
1
1
1
76
77
78
79
80
Address Setting-Multi ODU