104
4MXC2324BF0W0AA
PCB code 0151800208CF (manufactured after 6th May 2021)
SW3-5
SW3-6
SW3-7
SW3-8
Indoor unit Address
(Indoor unit address for one wired
controller control more than one
unit)
OFF
OFF
OFF
OFF
0 (master)
OFF
OFF
OFF
ON
1(slave)
OFF
OFF
ON
OFF
2(slave)
OFF
OFF
ON
ON
3(slave)
OFF
ON
OFF
OFF
4(slave)
OFF
ON
OFF
ON
5(slave)
OFF
ON
ON
OFF
6(slave)
OFF
ON
ON
ON
7(slave)
ON
OFF
OFF
OFF
8(slave)
ON
OFF
OFF
ON
9(slave)
ON
OFF
ON
OFF
10(slave)
ON
OFF
ON
ON
11(slave)
ON
ON
OFF
OFF
12(slave)
ON
ON
OFF
ON
13(slave)
ON
ON
ON
OFF
14(slave)
ON
ON
ON
ON
15(slave)
Wired controller communication address
SW3-2
SW3-3
Unit Type
ON
ON
Cassette
SW1 (1-ON, 0-OFF)
Capacity (SW1-1→SW1-3) Room
card
SW1-4
Running
mode
Fresh air
/Trouble alarm
Filter
remindng
Location
Description
SW1-1
SW1-2 SW1-3
SW1-5
SW1-6
SW1-7
SW1-8
1
0
1
---
---
---
---
---
Capacity: 10.5kW
0
1
1
---
---
---
---
---
Capacity: 12.5kW
1
1
1
---
---
---
---
---
Capacity: 14.0kW
1
1
1
---
---
---
1
---
Capacity: 16.0kW
---
---
---
0
---
---
---
---
Room card invalid (default)
---
---
---
1
---
---
---
---
Room card valid
---
---
---
---
0
---
---
---
Heat pump (default)
---
---
---
---
1
---
---
---
Cooling only
---
---
---
---
---
0
---
---
Fresh air function
---
---
---
---
---
1
---
---
Trouble alarm
---
---
---
---
---
---
0
---
Without filter reminding
---
---
---
---
---
---
1
---
With filter reminding
---
---
---
---
---
---
---
0
Used in American
---
---
---
---
---
---
---
1
Not used in
American(default)