background image

 

                                                           Page 19

Installer’s Guide

Starting the Unit in Cooling Mode

Control Wiring (Class II)

Low voltage control wiring should not be run in conduit with power 
wiring unless Class 1 wire of proper voltage rating is used.  Route 
the thermostat cable or equivalent single leads of No. 18 AWG 
colored wire from the thermostat subbase terminals through the 
rubber grommet on the unit. See Figures 2, 4, 6, or  8

 

 for the  

control entry (24V Entry) location.  Make connections as shown 
on the unit wiring diagram.
Do not short thermostat wires since this will damage the control 
transformer.
Refer to Table 2 for recommended wire sizes and lengths for install-
ing the unit thermostat. The total resistance of these low voltage 
wires must not exceed one (1) ohm. Any resistance in excess of 1 
ohm may cause the control to malfunction because of the exces-
sive voltage drop.

IMPORTANT:  

Upon completion of wiring, check all electrical con-

nections, including factory wiring within the unit.
Make sure all connections are tight. Replace and secure all electri-
cal box covers and access panels before leaving the unit or turning 
on the power to the unit.

Pre-Start Quick Checklist

 

Is the unit properly located and level with the proper 
  clearance? See Figures 1 to 6. See Step 3-Review  
  Location and Recommendation Information on page 10.

 Is the duct work correctly sized, run, taped, insulated, and 

  weatherproofed with proper unit arrangement? See  
  Ductwork Installation section on page 16.

 Is the condensate line properly sized, run, trapped, and  

  pitched? See Condensate Drain Piping section on page 
 16.

 Is the filter of the correct size and quantity?  Is it clean and in  

  place? See Air Filter Installation section on page 16.

 Is the wiring properly sized and run according to the unit  

  wiring diagram? See Electrical Wiring section on page 17.

 Are all the wiring connections, including those in the unit,  

  tight? See Electrical Wiring section on page 17.

 Has the unit been properly grounded and fused with the  

  recommended fuse size? See Electrical Wiring section on 
  page 17.

 Is the thermostat well located, level, and correctly wired?  

 

  See Electrical Wiring section on page 17.

 Have the air conditioning systems been checked at the service  

  ports for charge and leak tested if necessary?

Step 5—Unit Startup

Table 2. Thermostat Wire Size and Maximum Length

 Do the condenser fan and indoor blower turn free without  

  rubbing, and are they tight on the shafts?

 Has all work been done in accordance with applicable local  

  and national codes?

 Are all covers and access panels in place to prevent air loss and  

  safety hazards?

Thermostat Heat Anticipator

Set the thermostat heat anticipators to equal the amperage draw 
of the W1 thermostat circuit. 

CAUTION

Before starting the system on the cooling cycle, turn the comfort 
control  to 

OFF

 and close the unit disconnect switch.  This is 

a precaution against foaming at startup which could damage 
the compressor bearings.  

Safety Hazard. Do not operate the unit without the evapora-
tor fan access panel or evaporator coil access panel in place. 
Reinstall the access panels after performing maintenance 
procedures on the fan. Operating the unit without the access 
panels properly installed may result in severe personal injury 
or death.

s

s

WARNING

NOTE: See the section on “Sequence of Operation” for a de-

scription of the cooling operating sequence.

To start the unit in the cooling mode, set the comfort control to 

COOL 

and  to a setting below room temperature. The condenser fan motor, 
compressor and evaporator fan motor will operate automatically.

Operating Pressure Checks

After the unit has operated in the cooling mode for a short period of 
time, install pressure gauges on the gauge ports of the discharge 
and suction line valves (behind the Compressor access panel).  
Check the suction and discharge pressures and compare them to the 
normal operating pressures provided in the unit’s 

SERVICE FACTS.

NOTE:  Do not use the PRESSURE CURVES from the unit's 

SERVICE FACTS to determine the unit refrigerant charge. The 

correct charge is shown on the unit nameplate. To charge the 

system accurately, weigh in the charge according to the unit 

nameplate and check subcooling against the Subcooling Charg-

ing Table in the SERVICE FACTS.

Voltage Check

With the compressor operating, check the line voltage at the unit 
(contactor is located behind the Control  access panel). The volt-
age should be within the range shown on the unit nameplate. If low 
voltage is encountered, check the size and length of the supply line 
from the main disconnect to the unit. The line may be undersized 
for the length of the run.

Cooling Shut Down

Set the comfort control to 

OFF 

or to a setting above room temperature.

IMPORTANT:

 De-energize the main power disconnect ONLY when 

servicing the unit.  Power may be required to keep the heat pump 
compressor warm and to boil off refrigerant in the compressor.

WIRE SIZE

MAXIMUM LENGTH (Ft)

18

75

16

125

14

200

Summary of Contents for 4TCY4024

Page 1: ...be disconnected and the main gas valve must be turned off If operating checks must be performed with the unit operating it is the technician s responsibility to recognize these hazards and proceed sa...

Page 2: ...dditional respiratory protection Use the appropriate NIOSH approved respirator in these situations FIRST AID MEASURES Eye Contact Flush eyes with water to remove dust If symptoms persist seek medical...

Page 3: ...e Curb 13 Ductwork Installation 16 Attaching Downflow Ductwork to Roof Curb 16 Attaching Downflow Ductwork to Roof Frame 16 Attaching Horizontal Ductwork to Unit 16 Condensate Drain Piping 16 Air Filt...

Page 4: ...Step 2 Determine Unit Clearances Figure 1 4TCY4024 through 4TCY4036 1 of 3 Figures 1 to 6 show the unit critical dimensions NOTE The view labeled Bottom Side represents the Base as viewed looking up...

Page 5: ...Page 5 Installer s Guide Figure 2 4TCY4024 through 4TCY4036 2 of 3...

Page 6: ...Page 6 Installer s Guide Figure 3 4TCY4024 through 4TCY4036 3 of 3...

Page 7: ...Page 7 Installer s Guide Figure 4 4TCY4042 through 4TCY4060 1 of 3 NOTE The view labeled Bottom Side represents the Base as viewed looking up from underneath the unit...

Page 8: ...Page 8 Installer s Guide Figure 5 4TCY4042 through 4TCY4060 2 of 3...

Page 9: ...Page 9 Installer s Guide Figure 6 4TCY4042 through 4TCY4060 3 of 3...

Page 10: ...unit installations are illustrated in Figures 1 through 6 pages 4 9 2 Any reduction of the unit clearances indicated in these figures may result in condenser coil starvation or the recircula tion of...

Page 11: ...ast two 2 inches of insulation and weatherproof There must be a weather proof seal where the duct enters the structure 5 Do not expose the unit to direct roof water runoff 6 Seal all holes through ext...

Page 12: ...includes a kit of four 4 lifting lugs See Figure 10 inset B on page 14 2 Insert the four lifting lugs in the openings provided in the drip lip on each end of the unit See Figure 10 inset B on page 14...

Page 13: ...top applications using field fabricated ducts and sleeper rails rather than a curb or frame use the following procedure 1 Locate and secure the sleeper rails to the roof by bolting Three 3 sleeper ra...

Page 14: ...drawing The manufacturer is not responsible for the unauthorized use of this drawing and expressly disclaims any liability for damages resulting from such unauthorized use Gasket Seal Spreader Bars B...

Page 15: ...rizontal Airflow Application with Frame Supply Air Return Air Roof Flashing Channel Iron Center Support Center Support required on all Frame Applica tions Angle Iron Frame Roof Flashing Return Air Ang...

Page 16: ...s to minimize noise and vibration transmission Elbows with turning vanes or splitters are recommended to minimize air noise and resistance The first elbow in the ductwork leaving the unit should be no...

Page 17: ...the only one considered Over Current Protection The branch circuit feeding the unit must be protected as shown on the unit s rating plate Power Wiring The power supply lines must be run in weather ti...

Page 18: ...Page 18 Installer s Guide Figure 20 Typical 4TCY4 Field Wiring Diagram...

Page 19: ...blower turn free without rubbing and are they tight on the shafts Has all work been done in accordance with applicable local and national codes Are all covers and access panels in place to prevent air...

Page 20: ...s are closed If two stages of heat are provided and additional heat is required the comfort control s second stage W2 circuit is energized power ing the BH contactor coil Maintenance Final Installatio...

Page 21: ...rvice routines described at the beginning of each heating season Visually inspect the unit to ensure that the airflow required for combustion and condenser coil is not obstructed from the unit Inspect...

Page 22: ...Page 22 Installer s Guide Notes...

Page 23: ...Page 23 Installer s Guide Notes...

Page 24: ...installing dealer if the unit is inoperative Before you call always check the following to be sure service is required a Be sure the main switch that supplies power to the unit is in the ON position b...

Reviews: