Söllnerstr. 9 92637 Weiden
+49 (0)961 48 23 0 0
MPI-USB user manual
47 / 93
2022/01/21 01:28
• Mode:
Choose this menu to configure the cable mode.
Mode
Meaning
MPI SER MPI-communication over RS232-interface
MPI USB MPI-communication with PLCVCom/Step7-driver over USB-interface
PPI 9K6
PPI-communication with 9600 baud over RS232-interface
PPI 19K2 PPI-communication with 19200 baud over RS232-interface
PPIUSB96
SPEC SER
Specialmode RS232 (complies RS232-RS485-converter, interface-parameter must be separately
parameterized)
SPEC USB
Specialmode USB (complies RS232-RS485-converter with PLCVCom, interface-parameter must
be separately parameterized)
PPIUSB19 PPI-communication only with PLCVCom and 19200 baud over USB-interface
PPIMulti
PPI-communication (MultiMaster 9K6 - 187,5K) over RS232- or USB-interface (with PLCVCom)
HINT: „MPI SER“, „SOND SER“, „PPI 19K2“ and „PPI 9K6“ doesn't fit with the MPI-USB cable (Ord. No. 9352
USB).
• Password:
Choose this menu to change the configuration password. (Standard: „0“)
• Reset:
The cable reset.
• Default settings:
Press the enter-key to change the cable configuration to default.
• Language:
In this menu you can choose the language of your choice. Choose between „German“ and „English“.
• Protocol:
Change the protocol version. Choose „Auto“ if you want that the cable takes the configuration from the PG.
If you experience any trouble on the bus with the protocol version „V 5.1“ set the configuration to „V5.0
Old“. The 5.0 version is more stable but slower than the „V 5.1“ protocol version.
• PG/PC:
In this menu you can change the connection speed between the programming device and the computer.
This works only by using a MPI – II (Ord. No. 9352) cable with the serial device connected to the computer.
Available baud rates: „2400“, „4800“, „9.6k“, „19.2k“, „38.4k“, „57.6k“, „115.2k“.
If you are using the cable takes the PD configuration.
• MPI-BUS:
You have to choose between these sub menus.
Baudrate
Master
lokalNo
HSA
- Baudrate
Change the speed of the MPI - Bus. Available baud rates: „Auto“, „19,2k“, „45,45k“, „93,75k“, „187,5k“,
„500k“, „1,5M“, „3M“, „6M“, „12M“
HINT: The baud rates„3M“, „6M“ and „12M“ can only be configured by cable. These higher baud rates
(from “3M“) will be overwritten by the PC. To get sure that this will not happen configure (in the cables