ELECTRICAL REQUIREMENTS AND SAFETY
GROUNDING INSTRUCTIONS
IN THE EVENT OF A MALFUNCTION OR
BREAKDOWN
, grounding provides a path of least resistance
for electric current and reduces the risk of shock. This tool is
equipped with an electric cord that has an equipment grounding
conductor and grounding plug. The plug MUST be plugged into
a matching receptacle that is properly installed and grounded in
accordance with ALL local codes and ordinances.
DO NOT MODIFY THE PLUG PROVIDED
. If it will not fit
the receptacle, have the proper receptacle installed by a
qualified electrician.
IMPROPER CONNECTION
of the equipment grounding
conductor can result in risk of electric shock. The conductor
with the green insulation (with or without yellow stripes) is the
equipment grounding conductor. If repair or replacement of the
electric cord or plug is necessary, DO NOT connect the
equipment grounding conductor to a live terminal.
CHECK
with a qualified electrician or service personnel if you
do not completely understand the grounding instructions, or if
you are not sure the tool is properly grounded.
USE ONLY 3-WIRE EXTENSION CORDS THAT HAVE
3-PRONG GROUNDING PLUGS AND 3-POLE
RECEPTACLE THAT ACCEPT THE TOOL’S PLUG.
REPAIR OR REPLACE DAMAGED OR WORN CORD
IMMEDIATELY.
GUIDELINES FOR EXTENSION CORDS
Make sure your extension cord is in good condition. When using
an extension cord, be sure to use one heavy enough to carry the
current your product will draw. An undersized cord will cause a
drop in line voltage resulting in loss of power and overheating.
The table below shows the correct size to use according to cord
length and nameplate ampere rating. If in doubt, use the next
heavier gauge. The smaller the gauge number, the heavier the
cord.
Be sure your extension cord is properly wired
and in good
condition. Always replace a damaged extension cord or have it
repaired by a qualified person before using it. Protect your
extension cords from sharp objects, excessive heat and damp or
wet areas.
Use a separate electrical circuit for your tools. This circuit must
not be less than #12 wire and should be protected with a 15
Amp time lag fuse. Before connecting the motor to the power
line, make sure the switch is in the OFF position and the electric
current is rated the same as the current stamped on the motor
nameplate. Running at a lower voltage will damage the motor.
This tool is intended for use on a circuit that has a receptacle
like the one illustrated in FIGURE A.
FIGURE A
shows a 3-prong electrical plug and receptacle that
has a grounding conductor. If a properly grounded receptacle is
not available, an adapter
(FIGURE B)
can be used to
temporarily connect this plug to a 2-contact ungrounded
receptacle. The adapter
(FIGURE B)
has a rigid lug extending
from it that MUST be connected to a permanent earth ground,
such as a properly grounded receptacle box.
THE
TEMPORARY ADAPTER SHOULD BE USED ONLY
UNTIL A PROPER GROUNDED OUTLET CAN BE
INSTALLED BY A QUALIFIED ELECTRICIAN.
The
Canadian Electrical Code prohibits the use of adapters.
CAUTION:
In all cases, make certain the receptacle in question
is properly grounded. If you are not sure have a certified
electrician check the receptacle.
CAUTION!
This drill press is for indoor use only. Do not expose to rain or
use in damp locations.
CAUTION!
This tool must be grounded while in use to protect the operator
from electrical.
MINMUN GAUGE FOR EXTENSION CORDS (AWG)
(When using 120 volts only)
Ampere Rating
Total length of cord in feet
more than not more than
25’ 50’ 100’ 150’
0 6
18 16 16 14
6 10
18 16 14 12
10 12
16 16 14 12
12 16
14 12 Not recommended
5
3-Prong Plug
Grounding Prong
Properly Grounded
3-Prong Receptacle
Grounding Lug
Adapter
Make Sure This
Is Connected to a
Known Ground
2-Prong
Receptable
Summary of Contents for DP12LW
Page 7: ...CARTON CONTENTS 7 L M N O ...
Page 22: ...22 ...