Trade-wind H3200 Series Installation Instructions & Use & Care Manual Download Page 12

 

 

Revised 6/11/18                              Copyright ©  2018  Trade-Wind Manufacturing, LLC                      Proverbs 22:29                        Page 12 

 

In-line dampers must be installed so that the exhaust air flow will open the butterfly blades.   
For 

horizontal duct runs

, the in-line damper must be installed so that the hinge between the two 

butterfly blades is 

vertical

—the hinge pin must point up and down.  Otherwise, because of gravity, 

the damper’s blades will not close and the damper will not prevent backdrafts.   
 
For 

vertical duct runs

, the in-line damper’s hinge will be 

horizontal

 (sideways), which is correct for 

vertical duct runs.  Gravity will help close the damper blades after each use.  
 
For 

upward slanted duct runs

, the in-line damper’s hinge must point to the top and bottom sides of 

the duct.  In his position, gravity will help close the damper blades after each use.  Otherwise, because 
of gravity, the damper’s blades will not close and the damper will not prevent backdrafts.   
 

5.

 

Roof Caps and Wall Caps 

The roof cap or wall cap is the termination point of the venting system that allows the exhaust air to exit to 
the outdoors.  All sections of this fitting must have an equal or greater air path area than the ventilator’s 
discharge port.   If any section of the roof cap or wall cap is smaller than the ventilator’s discharge port, the 
entire ventilation system will lose efficiency and the restriction will cause increased static pressure. 
 

IMPORTANT:

  Even though the intake side of the roof cap or wall cap may be properly sized, roof caps or wall 

caps with built-in dampers must be made so that when the damper is fully open, the actual open area of the 
final air path is equal to or greater than the discharge port of the ventilator.  Any undersized portion of a roof 
cap or wall cap will cause excessive static pressure that may result in rattling, vibration and air buffeting 
noises, as well as inadequate ventilation.   

***Roof caps and wall caps must have an integral bird screen. 

6.

 

Attaching Duct to House Framework 

The ventilation system should be attached to the framework in such a manner that the weight of the duct and 
fittings is supported with no stress on the duct joints, fittings or on the ventilator.  All ducting should be attached 
so as to avoid any possible duct vibration from being transferred to the house’s framework.

 

7.

 

 Duct Sizing Chart and Area Calculations

  

 

Ventilator Discharge Port 

Types & Sizes 

Duct Type Required 

Duct Size 

(in Square Inches) 

Minimum Discharge Size 

of Roofcap or Wallcap 

Outside Opening 

  

 

 

 

6” Diameter, Round 

28.3” 

6” Round Metal Duct 

28.3” 

28.3” 

7” Diameter, Round 

38.5” 

7” Round Metal Duct 

38.5” 

38.5” 

8” Diameter, Round 

50.25” 

8” Round Metal Duct or 
6” x 9” Rectangular Metal Duct 

50.25” 

54” 

50.25”                      

54” 

10” Diameter, Round 

78.5” 

10” Round Metal Duct 

78.5” 

78.5” 

3.25” x 10” Rectangular 

32.5” 

3.25” x 10” Rectangular Metal Duct 

32.5” 

32.5” 

 
Calculating Square Inches of Various Duct Sizes & Types

   

ROUND DUCT 

 

RECTANGULAR DUCT 

Radius  x  Radius  x  3.1416  =  Area (Sq. Inches)   

Width 

Depth 

Area (Sq. Inches) 

 

x   

x   

 

=   

 

 

  x   

  =   

The “radius” is one-half the diameter of a round duct, 
e.g., ½ of a 10” round duct is 5”.  3.1416 is “Pi”, the 
“constant” used when calculating the area of a circle. 

 

 
 

 

Summary of Contents for H3200 Series

Page 1: ...Revised 6 11 18 Copyright 2018 Trade Wind Manufacturing LLC Proverbs 22 29 Page 1 ATTENTION PLEASE REMOVE THE RIGHT SIDE BAFFLE FILTER TO LOCATE YOUR NEW REMOTE CONTROL...

Page 2: ...Revised 6 11 18 Copyright 2018 Trade Wind Manufacturing LLC Proverbs 22 29 Page 2...

Page 3: ...lectrical inspector s use and for future reference WARNINGS Instructions must be followed carefully to avoid personal injury IMPORTANT Must be followed carefully to avoid damage or incorrect installat...

Page 4: ...ns 1 Consult a licensed ventilation contractor or qualified technician for proper installation of exhaust ducting Locate the cooking area for minimum cross drafts away from doors and windows when poss...

Page 5: ...and duct runs should be as short as possible Where turns are necessary keep turning radius as large and as smooth as possible 7 The ducting must be air tight Use a minimum of 2 sheet metal screws at...

Page 6: ...ity to ensure that a qualified person performs the electrical connection of this appliance The electrical installation including minimum supply wire size must comply with the National Electric Code AN...

Page 7: ...ds removes more air from the inside of the house that must be replaced by outside air This may be especially costly when your home s heating or air conditioning system is in operation Turn off the uni...

Page 8: ...ly If you press the 5 minute delay auto off button again the blinking on the speed button stops and the blower has returned to manual mode If you would like to mount the remote to any surface near you...

Page 9: ...ating to improperly sized ducting or restrictive roof caps is not covered and will by default be charged back to the Homeowner Light bulbs are not covered under warranty Trade Wind Manufacturing LLC d...

Page 10: ...NOT use butt joints c For best air flow elbows and pipe size transition fittings should not be directly connected to one another Where possible always include at least 15 inches of straight pipe betw...

Page 11: ...se carefully crafted tightly wrapped Aluminum Foil Metal Duct Tape on all connections and physically view and test the damper blades to make certain they are opening and closing correctly Make sure th...

Page 12: ...p may be properly sized roof caps or wall caps with built in dampers must be made so that when the damper is fully open the actual open area of the final air path is equal to or greater than the disch...

Reviews: