Trade-wind H3200 Series Installation Instructions & Use & Care Manual Download Page 11

 

 

Revised 6/11/18                              Copyright ©  2018  Trade-Wind Manufacturing, LLC                      Proverbs 22:29                        Page 11 

 

 

Duct Pipe and Fitting Sizes 

(Continued)

 

Duct Runs – Length 

a.

 

Configure the ventilation duct run to be as short and as direct to the outside as possible.  Minimize 
the number of elbows and transition fittings used.  Complex or long runs should be reviewed by a 
qualified installer. 

 

b.

 

No portion of the ducting should be run so that the exhaust air flows downward.  Since exhaust heat 
rises, forcing the air to flow downward will cause increased static pressure.  As previously mentioned, 
improperly installed duct pipe will cause excessive static pressure (air resistance), that may result in 
rattling, vibration and air buffeting noises, as well as inadequate ventilation. 

 

c.

 

Duct runs for 390CFM ventilator models should not exceed 20 linear feet with two 90-degree elbows 
(or four 45-degree elbows), a damper and a roof or wall cap.  Longer runs or additional elbows will 
result in decreased ventilation performance.   Each 90-degree elbow is the equivalent of 8 linear feet 
of duct pipe; each 45-degree elbow is equivalent to 4 linear feet of duct pipe. 

 

d.

 

Always run ventilator ducts to the outdoors.  DO NOT terminate a duct into an attic, basement, 
garage, crawl space under a house, a chimney, other ducting or an enclosed room. 

 

 

4.

 

Dampers 

IMPORTANT:

  DO NOT USE SCREWS TO ATTACH ANY TYPE OF DAMPER AS THE SCREWS MAY BLOCK THE 

DAMPER BLADES. 
 

IMPORTANT:

  DO NOT USE MORE THAN ONE DAMPER IN THE VENTILATION SYSTEM.  

NOTE

:  Many styles of 

roof caps and wall caps have built-in dampers.  See 

Roof Caps and Wall Caps

 section for more detail. 

 

Always use carefully crafted, tightly wrapped Aluminum Foil Metal Duct Tape on all connections and physically 
view and test the damper blades to make certain they are opening and closing correctly.  Make sure that the 
damper blades do not touch the duct walls and that there is no debris blocking the free movement of the 
damper mechanism.  Common things to look for include screws protruding into the blade’s path, overspray of 
paint, plaster and insulation.  If using rectangular duct, be sure that all four sides of the duct are on the 
outside of the damper’s start collar or frame. 

 

390CFM Models 

390CFM models have a 7" round duct.   
DO NOT USE SCREWS TO ATTACH THE DUCT TO THE DAMPER FRAME AS THE SCREWS MAY BLOCK 
THE DAMPER BLADE.  ALWAYS use Aluminum Foil Metal Duct Tape on all connections and physically 
view the damper blade to make certain it is operating correctly.  On ventilator installations designed 
to recirculate the exhaust air back into the kitchen, be sure to remove the aluminum damper blade 
before attaching the duct to the damper frame. 

 

Damper in Roof Cap or Wall Cap 

In ventilation systems utilizing a roof cap or wall cap 

with

 a built-in damper, do not install an 

additional in-line damper. Two dampers are unnecessary and will cause increased static pressure (air 
resistance), that may result in rattling, vibration and air buffeting noises, as well as inadequate 
ventilation. 

 
In-line Damper

 (for ventilation systems utilizing a roof cap or wall cap 

without

 a built-in damper)

 

In cold weather areas, installing an “in-line” damper may be the preferred type of installation.  This is 
because in-line dampers installed just above the perimeter of the heated space (the ceiling) will 
reduce the amount of cold air traveling down the duct into the heated space and into the kitchen 
through the ventilator. 

Summary of Contents for H3200 Series

Page 1: ...Revised 6 11 18 Copyright 2018 Trade Wind Manufacturing LLC Proverbs 22 29 Page 1 ATTENTION PLEASE REMOVE THE RIGHT SIDE BAFFLE FILTER TO LOCATE YOUR NEW REMOTE CONTROL...

Page 2: ...Revised 6 11 18 Copyright 2018 Trade Wind Manufacturing LLC Proverbs 22 29 Page 2...

Page 3: ...lectrical inspector s use and for future reference WARNINGS Instructions must be followed carefully to avoid personal injury IMPORTANT Must be followed carefully to avoid damage or incorrect installat...

Page 4: ...ns 1 Consult a licensed ventilation contractor or qualified technician for proper installation of exhaust ducting Locate the cooking area for minimum cross drafts away from doors and windows when poss...

Page 5: ...and duct runs should be as short as possible Where turns are necessary keep turning radius as large and as smooth as possible 7 The ducting must be air tight Use a minimum of 2 sheet metal screws at...

Page 6: ...ity to ensure that a qualified person performs the electrical connection of this appliance The electrical installation including minimum supply wire size must comply with the National Electric Code AN...

Page 7: ...ds removes more air from the inside of the house that must be replaced by outside air This may be especially costly when your home s heating or air conditioning system is in operation Turn off the uni...

Page 8: ...ly If you press the 5 minute delay auto off button again the blinking on the speed button stops and the blower has returned to manual mode If you would like to mount the remote to any surface near you...

Page 9: ...ating to improperly sized ducting or restrictive roof caps is not covered and will by default be charged back to the Homeowner Light bulbs are not covered under warranty Trade Wind Manufacturing LLC d...

Page 10: ...NOT use butt joints c For best air flow elbows and pipe size transition fittings should not be directly connected to one another Where possible always include at least 15 inches of straight pipe betw...

Page 11: ...se carefully crafted tightly wrapped Aluminum Foil Metal Duct Tape on all connections and physically view and test the damper blades to make certain they are opening and closing correctly Make sure th...

Page 12: ...p may be properly sized roof caps or wall caps with built in dampers must be made so that when the damper is fully open the actual open area of the final air path is equal to or greater than the disch...

Reviews: