Trade-wind H3200 Series Installation Instructions & Use & Care Manual Download Page 10

 

 

Revised 6/11/18                              Copyright ©  2018  Trade-Wind Manufacturing, LLC                      Proverbs 22:29                        Page 10 

 

 

 

Brands

 

Best Practices

 

 

Venting Installation Instructions for 

Range Hoods and Wood Hood Liners 

(All Models) 

 

—Addendum to Installation Instructions—

 

 

IMPORTANT:  

Problems caused by improper installations are not covered by the manufacturer’s warranty.

 

   

IMPORTANT:  

Undersized and improperly installed duct pipe and/or other ventilation components will cause 

excessive static pressure (air resistance), that may result in rattling, vibration and air buffeting noises, as well as 
inadequate ventilation. 
 

1.

 

Building Codes   -   

Kitchen Hood Ventilators should be installed by qualified technicians familiar  

 

 

 

        with state and local building codes. 

 

2.

 

Duct Pipe and Fittings (Elbows, Transitions, Roof & Wall Caps)

 

a.

 

Use round or rectangular rigid metal duct only.  Where possible, use round duct as it creates the least 
amount of static pressure.  DO NOT use flex duct. 

 

b.

 

All duct sections and fittings (EXCEPT DAMPERS, per Section 4), should overlap and be connected with 
at least 3 – 4 equally spaced screws and wrapped tightly with 2 – 3 layers of Aluminum Foil Metal Duct 
Tape.  This type of duct tape is more durable than traditional cloth duct tape.  DO NOT use butt joints.   

 

c.

 

For best air flow, elbows and pipe size transition fittings should not be directly connected to one 
another.  Where possible, always include at least 15 inches of straight pipe between fittings. 
 

3.

 

Duct Pipe and Fitting Sizes.  

(See 

Duct Sizing Chart and Area Calculations

 Section for more detail)

 

 

IMPORTANT:  

DO NOT use either of the following duct pipe sizes or fitting sizes for any kitchen hood 

ventilator installations: 
-  6” round duct pipe 
-  3.25” x 10” rectangular x 6” round transitions 
-  6” x 7” linear transitions 

 

IMPORTANT:  

No portion of any length of duct pipe or fitting should be smaller than the discharge port of the 

ventilator.  This is very important because any type of restriction anywhere in the ventilation system will 
cause increased static pressure (air resistance), that may result in rattling, vibration and air buffeting noises, 
as well as inadequate ventilation. 

 

Example:  For ventilator models with 3.25” x 10” discharge ports, no part of the roof cap or wall cap’s air path 
should be smaller than 3.25” x 10” (32.5 square inches) or 7” round (38.5 square inches).  See 

Roof Caps and 

Wall Caps

 section for more detail. 

 
Exception:  For some short duct runs inside walls framed with 2 x 4 studs, it is a common industry practice to 
transition a 7” round duct to a 3.25” x 10” rectangular duct.  If space allows, it is best to use a 3.25” x 14” 
rectangular duct with a 3.25” x 14” x 7” transition. 

 
 

 

Summary of Contents for H3200 Series

Page 1: ...Revised 6 11 18 Copyright 2018 Trade Wind Manufacturing LLC Proverbs 22 29 Page 1 ATTENTION PLEASE REMOVE THE RIGHT SIDE BAFFLE FILTER TO LOCATE YOUR NEW REMOTE CONTROL...

Page 2: ...Revised 6 11 18 Copyright 2018 Trade Wind Manufacturing LLC Proverbs 22 29 Page 2...

Page 3: ...lectrical inspector s use and for future reference WARNINGS Instructions must be followed carefully to avoid personal injury IMPORTANT Must be followed carefully to avoid damage or incorrect installat...

Page 4: ...ns 1 Consult a licensed ventilation contractor or qualified technician for proper installation of exhaust ducting Locate the cooking area for minimum cross drafts away from doors and windows when poss...

Page 5: ...and duct runs should be as short as possible Where turns are necessary keep turning radius as large and as smooth as possible 7 The ducting must be air tight Use a minimum of 2 sheet metal screws at...

Page 6: ...ity to ensure that a qualified person performs the electrical connection of this appliance The electrical installation including minimum supply wire size must comply with the National Electric Code AN...

Page 7: ...ds removes more air from the inside of the house that must be replaced by outside air This may be especially costly when your home s heating or air conditioning system is in operation Turn off the uni...

Page 8: ...ly If you press the 5 minute delay auto off button again the blinking on the speed button stops and the blower has returned to manual mode If you would like to mount the remote to any surface near you...

Page 9: ...ating to improperly sized ducting or restrictive roof caps is not covered and will by default be charged back to the Homeowner Light bulbs are not covered under warranty Trade Wind Manufacturing LLC d...

Page 10: ...NOT use butt joints c For best air flow elbows and pipe size transition fittings should not be directly connected to one another Where possible always include at least 15 inches of straight pipe betw...

Page 11: ...se carefully crafted tightly wrapped Aluminum Foil Metal Duct Tape on all connections and physically view and test the damper blades to make certain they are opening and closing correctly Make sure th...

Page 12: ...p may be properly sized roof caps or wall caps with built in dampers must be made so that when the damper is fully open the actual open area of the final air path is equal to or greater than the disch...

Reviews: