SPECIFICATIONS AND FEATURES (50 Hz Models)
Note: All specifications are subject to change without notice.
MODEL
SW2612E SW3024E SW3048E SW4548E SW3024J SW4048J SW4548A
General Specifications
Nominal DC Input Voltage
12 vdc
24 vdc
48 vdc
48 vdc
24 vdc
48 vdc
48 vdc
AC Output Voltage (RMS)
230 vac
230 vac
230 vac
230 vac
105 vac
105 vac
240 vac
Nominal Frequency
50 Hz
50 Hz
50 Hz
50 Hz
50 Hz
50 Hz
50 Hz
Continuous Power @ 20
°
C
2600 VA
3300 VA
3300 VA
4500 VA
3300 VA
4000 VA
4500 VA
Continuous Output (@ 25
°
C)
11 amps AC
14 amps AC
14 amps AC
20 amps AC
31 amps AC
33 amps AC
20 amps AC
Maximum Output (RMS)
28 amps AC
34 amps AC
34 amps AC
34 amps AC
78 amps AC
78 amps AC
34 amps AC
Efficiency (peak)
90%
94%
95%
96%
94%
95%
96%
Automatic Transfer Relay
30 amps AC
30 amps AC
30 amps AC
30 amps AC
60 amps AC
60 amps AC
30 amps AC
Maximum Charging Rate
150 amps DC
100 amps DC
50 amps DC
60 amps DC
100 amps DC
60 amps DC
60 amps DC
Charger Regulation Method
3 stage
3 stage
3 stage
3 stage
3 stage
3 stage
3 stage
DC Input Requirements
Search Mode
0.08 A (1 W)
0.04 A (1 W)
0.025 A (1 W)
0.04 A (1 W)
0.04 A (1 W)
0.025 A (1 W)
0.04 A (1 W)
On Mode (no load - idle)
1.6 A (12 W)
0.66 A (16W)
0.33 A (16 W)
0.40 A (20 W)
0.40 A (20 W)
0.33 A (16 W)
0.40 A (20 W)
At Full Rated Power
300 amps
166 amps
83 amps
137 amps
137 amps
83 amps
137 amps
Short Circuited Output
700 amps
320 amps
160 amps
180 amps
180 amps
160 amps
180 amps
Input Voltage Range (VDC)
11.8 to 16.5 vdc
22 to 33 vdc
44 to 66 vdc
44 to 66 vdc
44 to 66 vdc
44 to 66 vdc
44 to 66 vdc
AC Output Characteristics
AC Output Waveform
Sinewave, 34 to 52 steps per cycle
Voltage Regulation
± 2%
Total Harmonic Distortion
3 to 5% (stand alone operation)
Power Factor Allowed
-1 to 1
Frequency Regulation
± 0.04% (crystal regulated)
Load Sensing Range
16 to 240 Watts
Standard Features
Control Panel
Built-in 2 line back-lit alphanumeric liquid crystal display with eight LED status indicators
Low Battery Protection
Adjustable low battery cut out and cut in with current compensation
Battery Temperature Sensor
15 foot plug in battery temperature sensor with phone type jack (can be extended)
Auto Generator Control system
Automatic generator control system for two and three wire start generators (no glow-plug control)
Auxiliary Relays
Three user adjustable voltage controlled signal relays for control of loads or charging sources
Fan Cooling
Variable speed brushless DC fans
Options
Remote Control Panel
SWRC
SWRC
SWRC
SWRC
SWRC
SWRC
SWRC
Stacking Interface for 2X power
(*requires two inverters)
No
No
No
No
No
No
No
Conduit Box
SWCB
SWCB
SWCB
SWCB
SWCB
SWCB
SWCB
Environmental Limitations
Enclosure Type
Indoor, ventilated, steel chassis with powdercoat finish
Specified Temp Range
32
°
F to 104
°
F (0
°
C to +40
°
C) (output will meet specified tolerances)
Allowed Temperature Range
-40
°
F to 140
°
F (-40
°
C to +60
°
C) (output may not meet specified tolerances)
Non-operating Temperature
-67
°
F to 284
°
F (-55
°
C to +75
°
C)
Altitude Limit Operating
15,000 feet (5000 meters)
Altitude Limit Non-operating
50,000 feet (16,000 meters)
Dimensions - Inverter Only
15” (38 cm) high, 22.5” (57 cm) wide, 9” (23 cm) deep (when wall mounted)
Dimensions - Shipping
20.5” (52 cm), 27” (69 cm), 15.5” (40 cm)
Mounting
Wall or Shelf Mount
Weight - Inverter Only
95 lbs (43 kg ) 105 lbs (48 kg) 105 lbs (48 kg) 136 lbs (63 kg) 105 lbs (48 kg) 105 lbs (48 kg) 136 lbs (63 kg)
Weight - Shipping
110 lbs (50 kg) 111 lbs (50 kg) 111 lbs (50 kg) 143 lbs (65 kg) 111 lbs (50 kg) 111 lbs (50 kg) 143 lbs (65 kg)