Parameterization via TRWinProg
TR-Electronic GmbH 2018, All Rights Reserved
Printed in the Federal Republic of Germany
Page 54 of 67
TR-ECE-BA-DGB-0141 v03
03/19/2021
5.1.3 Preset value
The parameter defines the position value, on which the measuring system is adjusted
when the preset-adjustment-function is executed via the Preset-input.
programmed
Origin Type
Preset value
< programmed Total number of steps
lower limit
–1 073 741 824
upper limit
1 073 741 823
default
0
5.1.4 Preset function
Risk of injury and damage to property by an actual value jump when the
Preset adjustment function is performed!
The preset adjustment function should only be performed when the
measuring system is at rest, otherwise the resulting actual value jump must
be permitted in the program and application!
If the Preset inputs are not used, they should be disabled to suppress interference.
Selection
Description
Default
In use
Preset adjustment function active
user-specific
Not in use
Preset adjustment function inactive
5.1.5 Origin Type
The parameter defines the measuring system origin (start of counting). A value
different of "0" causes a zero shift and it results a negative or positive offset. If a
negative origin was defined, in the section
"SSI"
the type of representation
(Complement or Sign + value) for the negative values must be specified.
lower limit
–1 073 741 824
upper limit
1 073 741 824
default
0