4 Installation / Preparation for Commissioning
PROFINET supports linear, tree or star structures. The bus or linear structure used in
the field buses is thus also available for Ethernet.
For transmission according to the 100Base-TX Fast Ethernet standard, network
cables and plug connectors in category STP CAT5 must be used (2 x 2 shielded
twisted pair copper wire cables). The cables are designed for bit rates of up to 100
Mbit/s. The transmission speed is automatically detected by the measuring system
and does not have to be set by means of a switch.
Addressing by switch is also not necessary, this is done automatically using the
addressing options of the PROFINET-Controller.
The cable length between two subscribers may be max. 100 m.
In case of IRT communication the topology is projected in a connection table.
Thereby you must pay attention on a right connection of the ports 1 and 2.
With RT communication this is not the case, it can be cabled freely.
To ensure safe and fault-free operation, the
-
PROFINET Design Guideline, Order-No.: 8.062
-
PROFINET Installation Guideline for Cabling and Assembly, Order-No.: 8.072
-
PROFINET Installation Guideline for Commissioning, Order-No.: 8.082
-
and the referenced Standards and PNO Documents contained in it must be
observed!
In particular the EMC directive in its valid version must be observed!