11

Check plug outlet vohage

Power supply faulty

Plug lamp off

Plug lamp on

Check operation

Voltage 115V

No response

Chock main body 
terminal block voltage

Response to 
remote control

No response to remote control.
Response to main body switch only.

Synchronize remote control

(See page 6.)

Some response to remote controllor and main body switch

No voltage

NG

OK

Normal

Voltage 115V

Change each mode.

Main board malfunction

No voltage

Plug faulty

Plug in
Check plug lamp

Power supply cord faulty

When problem cannot be solved

Check in the following order:
(1) Remote control battery exhaustion
(2) Check junction circuit continuity o 

fmain board and switch board

(3) Remote control malfunction
(4) Main body switch board malfunction
(5) Main board manlunction

Criteria for judgment of main circuit board malfunction
(1) Load which should be moving is not moving. If voltage is not detected at the terminal, the problem is the main board.
(2) Load which should be moving is not moving. If voltage is detected at the terminal, the problem is the load.
(3) When it is not determinable, disconnect the wiring of the load that is not moving from the main board, apply voltage directly 

to the load to checkif the load is normal. If the load is normal, the problem is the main board.

Minimum set temperature.
Maximum fan speed.
Set the room temperature thermistor at 
86˚F (30˚C) or higher by warming up with 
body heat.

Compressor runs 
within five minutes.
Cool side air blower 
runs.
Warm side air 
blower runs.

Compressor does not run 
within five minutes. Cool 
side air blower runs.
Warm side air blower 
does not run.

Compressor does not run 
within five minutes.
Cool side air blower runs.
Warm side air blower 
runs.

Either cool side air blower 
or warm side air blower 
does not run.

(1) Thermistor 

malfunction

(2) Main board 

malfunction

(1) Malfunction of air 

blower which is not 
running

(2) Main board 

malfunction

Any of the previous 
three items does 
not run.

Evaporator cools 
down in approx. 
ten minutes.

Evaporator does 
not cool down 
after ten minutes.

(1) Blockage of refrigeration 

cycle

(2) No coolant
In the case of no coolant, 
evaporator inlet port cools 
down, but outlet port does not.

(1) OLP malfunction
(2) Compressor 

malfunction

(3) Main board 

malfunction

TROUBLESHOOTING

When problem is unclear (also when there is a cooling-down error)

  TAD-T32G  (Service  Manual)    07.1.17  3:03  PM    ページ 11

Summary of Contents for TAD-T32G

Page 1: ...SERVICE MANUAL MODEL TAD T32G Type A B TAD T32G Service Manual 07 1 17 3 03 PM b...

Page 2: ...if the unit is to be used exclusively in one space the cooling efficiency will be enhanced by using the venting kit accessory which is included with the unit 2 OPERATIONAL FEATURES 1 COOLING OPERATION...

Page 3: ...ertical louver Emergency ON OFF switch Front panel Air outlet grille Air intake grille HAF filter inside Charcoal filter inside Filter clamp inside Air intake opening Drain water outlet LCDI Power plu...

Page 4: ...r Clock indicator Timer setting indicator Timer ON OFF indicator C F indicator Set temp indicator Mode indicator Fan speed indicator Symbols Cooling mode High speed Dehumidify mode Fan only mode Auto...

Page 5: ...power cord in any way DO NOT apply any excessive force or pressure to the power supply cord Make sure that the plug is free of dust DO NOT use an extension cord DO NOT turn on and off by inserting or...

Page 6: ...R OPERATING CYCLE MODEL OUTPUT POWER UNIT in FT2 V Hz V B T U GAL H A W CFM W uF V A W uF V W uF V W mm R22 lbs F lbs TAD T32G 20 W 16 1 2 D 36 H 508 W 418 D 915 H mm 194 258 18 24m2 115 60 104 127 12...

Page 7: ...e The setting range is from 64 F 18 C to 90 F 32 C Note When choose AUTO DEHUMIDIFY or FAN MODE temperature setting button invalid Clock Set Controls Press CLOCK button LCD clock display flashes Press...

Page 8: ...pleted after one beep Default indicator Trouble shooting when environmental tempera ture indicator failures Please check the environmental temperature indi cator on PCB if it s assembled properly and...

Page 9: ...crews from the top of the rear panel I to remove the front cover Lift up the front cover and disconnect the connecters of the circuit board and the ionizer Type A only 2 Remove six 6 screws from the b...

Page 10: ...a power failure The plug is not connected The timer is unable to work The main switch has not been pressed The set temperature is too close to the room s temperature There is something blocking the s...

Page 11: ...as dirt on a cooling unit it is important to perform a visual check first Part replacement is not necessary and accurate analysis cannot be performed with an unclean condition Check the refrigeration...

Page 12: ...sconnect the wiring of the load that is not moving from the main board apply voltage directly to the load to checkif the load is normal If the load is normal the problem is the main board Minimum set...

Page 13: ...voltage It is not rotating It is rotating Normal Measure terminal voltage of main board Check drain motor rotation Drain motor malfunction Main board malfunction Operation stops due to full water TRO...

Page 14: ...l if it is operated Check if there is loose disconnection short circuiting on connector of Full Tank Switch Also check a loose disconnection and breakage of Float Malfunction of Drain Motor Replace it...

Page 15: ...again after 5 min of disconnection from power supply Normal if the unit is operated for 30 min after disconnection from power supply Operation Circuit Board is malfunctioned if the same problem happe...

Page 16: ...room temperature drops more than 2 F 1 C from the setting temperature the compressor stops D When the room temperature is 2 F 1 C lower than the setting temperature the compressor will not start E The...

Page 17: ...F 68 F 22 C 20 C C Less than 66 F 19 C Compressor ON 9min 3min 9min 3min 6min 3min Selected fan speed Low Low Low IONIZER INDOOR MOTOR SENSOR CN 3 CN 4 CN 5 P8 P1 R S T P2 P3 P4 P7 P6 P5 COM NO CN 2...

Page 18: ...fan Capacitor A Rear FM Front fan motor Front fan Capacitor B Compressor Main circuit board Capacitor C Front FM Indication lamp circuit Front panel Power supply cord Rear panel Intake air grille HAF...

Page 19: ...TOYOTOMI CO LTD 5 17 Momozono cho Mizuho ku Nagoya 467 0855 Japan www toyotomi jp New 12 06 Printed in Japan TAD T32G Service Manual 07 1 17 3 03 PM a...

Reviews: