![Toyotomi CCT 100HINVi Service Manual Download Page 57](http://html1.mh-extra.com/html/toyotomi/cct-100hinvi/cct-100hinvi_service-manual_1143300057.webp)
Troubleshooting
120
Electrical Control System
2.4.4.6. E5 malfunction (For three phases units)
Voltage protection
Check whether the voltage
range of P-N on IPM module is
normal? DC277-356V for 18K/
24KBtu/h; DC277-410V for
36KBtu/h
Check the power supply
Check whether the voltage
range of P-N on IPM module is
normal? DC 350-650V
Replace bridge rectifiers,
and then check whether the
system can run normally
Replace IPM board, and
then check whether the
system can run normally
Replace outdoor main board
Yes
No
No
No
No
Yes
Trouble is solved
Yes
Yes
E5 display
Replace the power board,
then check whether the
system can run normally
No
Yes
Summary of Contents for CCT 100HINVi
Page 1: ...Service Manual MODEL CCT 50HINVi o CCT 70HINVi o CCT 100HINVi o...
Page 7: ...Indoor Units 6 Indoor Units Part 2 Indoor Units Super Slim Cassette Type 7...
Page 13: ...Dimensions 12 Indoor Units 2 Dimensions Model A H 18 205 235 24 205 235 36 245 275...
Page 14: ...Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Page 15: ...Wiring Diagrams 14 Indoor Units 4 Wiring Diagrams CCT 50HINVi CCT 70HINVi CCT 100HINVi...
Page 20: ...Field Wiring Indoor Units 19 9 Field Wiring...
Page 25: ...Wiring Diagrams Outdoor Units 57 4 Wiring Diagrams CCT 50HINVo CCT 70HINVo...
Page 26: ...Wiring Diagrams 58 Outdoor Units CCT 100HINVo...
Page 45: ...Troubleshooting 108 Electrical Control System 2 4 1 2 Outdoor unit malfunction...
Page 50: ...Troubleshooting Electrical Control System 113 2 4 2 3 Up down panel is not closed...
Page 54: ...Troubleshooting Electrical Control System 117 2 4 4 3 E3 malfunction...
Page 55: ...Troubleshooting 118 Electrical Control System 2 4 4 4 E4 malfunction...
Page 60: ...Troubleshooting Electrical Control System 123 2 4 4 9 P1 malfunction For 36k models...
Page 61: ...Troubleshooting 124 Electrical Control System 2 4 4 10 P2 malfunction For 36k models...
Page 62: ...Troubleshooting Electrical Control System 125 2 4 4 11 P3 malfunction...