Electrical Control Function
Electrical Control System
99
2. T4<3
ć
3. Compressor is on
4. T3
TempEnterDefrost_ADD
ć
Cleared conditions (Meet any one of the following conditions)
1. Compressor is off and T3
˚
TempEnterDefro2
last for 20 minutes
ć
2. Running in cooling mode.
3. Compressor is off for 1 hour.
Condition of entry defrosting:
time1+ time2
40 minutes, When defrosting is end,time1 and time2 are cleared.
Defrosting action
φ
4-Way valve
Indoor fan
Outdoor fan
480P
PMV
PMV running
8 mins with 300P
Compressor
10S 30S
TimeA
10S
no longer than 10min
Condition of ending defrosting:
If any one of following items is satisfied, defrosting will stop and the machine will turn to normal heating
mode.
Ś
The defrosting time achieves 10min;
ĸ
T3
ı
15
ć
;
Ĺ
T3
ı
7
ć
for 60seconds.
1.3.3.5 High evaporator coil temp.T2 protection:
T2>60
đ
, the compressor will stop and restart when T2<54
đ
.
1.3.4 Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed between
17~30
đ
.
In auto mode, the machine will choose cooling, heating or fan-only mode according to
ǻ
T (
ǻ
T =T1-Ts).
Summary of Contents for CCT 100HINVi
Page 1: ...Service Manual MODEL CCT 50HINVi o CCT 70HINVi o CCT 100HINVi o...
Page 7: ...Indoor Units 6 Indoor Units Part 2 Indoor Units Super Slim Cassette Type 7...
Page 13: ...Dimensions 12 Indoor Units 2 Dimensions Model A H 18 205 235 24 205 235 36 245 275...
Page 14: ...Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Page 15: ...Wiring Diagrams 14 Indoor Units 4 Wiring Diagrams CCT 50HINVi CCT 70HINVi CCT 100HINVi...
Page 20: ...Field Wiring Indoor Units 19 9 Field Wiring...
Page 25: ...Wiring Diagrams Outdoor Units 57 4 Wiring Diagrams CCT 50HINVo CCT 70HINVo...
Page 26: ...Wiring Diagrams 58 Outdoor Units CCT 100HINVo...
Page 45: ...Troubleshooting 108 Electrical Control System 2 4 1 2 Outdoor unit malfunction...
Page 50: ...Troubleshooting Electrical Control System 113 2 4 2 3 Up down panel is not closed...
Page 54: ...Troubleshooting Electrical Control System 117 2 4 4 3 E3 malfunction...
Page 55: ...Troubleshooting 118 Electrical Control System 2 4 4 4 E4 malfunction...
Page 60: ...Troubleshooting Electrical Control System 123 2 4 4 9 P1 malfunction For 36k models...
Page 61: ...Troubleshooting 124 Electrical Control System 2 4 4 10 P2 malfunction For 36k models...
Page 62: ...Troubleshooting Electrical Control System 125 2 4 4 11 P3 malfunction...