Electrical Control Function
Electrical Control System
95
1. Electrical Control Function
1.1 Definition
T1: Indoor room temperature
T2: Coil temperature of indoor heat exchanger middle.
T2B: Coil temperature of indoor heat exchanger outlet.
T3: Coil temperature of condenser
T4: Outdoor ambient temperature
T5: Compressor discharge temperature
1.2 Main Protection
1.2.1 Time delay at restart for compressor.
1.2.2 Temperature protection of compressor top
The unit will stop working when the compressor top temp. protector cut off, and will restart after the
compressor top temp. protector restart.
1.2.3 Temperature protection of compressor discharge
When the compressor discharge temp. is getting higher, the running frequency will be limited as below rules:
----If 102
đ
<T5<115
đ
, decrease the frequency to the lower level every 2 minutes till to F1.
---If T5>115
đ
for 10 seconds, the compressor will stop and restart till T5<90
đ
.
1.2.4 Sensor protection at open circuit and breaking disconnection.
1.2.5 Indoor fan delayed open function
When the unit starts up, the louver will be active immediately and the indoor fan will open 10s later.
If the unit runs in heating mode, the indoor fan will be also controlled by anti-cold wind function.
1.2.6 Fan Speed is out of control(for DC motor)
When Indoor Fan Speed keeps too low (For A5 duct&Ceiling&floor,300RPM,For
Super slim cassette,200RPM
)
for 50s, the unit will stop and the LED will display the failure
Summary of Contents for CCT 100HINVi
Page 1: ...Service Manual MODEL CCT 50HINVi o CCT 70HINVi o CCT 100HINVi o...
Page 7: ...Indoor Units 6 Indoor Units Part 2 Indoor Units Super Slim Cassette Type 7...
Page 13: ...Dimensions 12 Indoor Units 2 Dimensions Model A H 18 205 235 24 205 235 36 245 275...
Page 14: ...Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Page 15: ...Wiring Diagrams 14 Indoor Units 4 Wiring Diagrams CCT 50HINVi CCT 70HINVi CCT 100HINVi...
Page 20: ...Field Wiring Indoor Units 19 9 Field Wiring...
Page 25: ...Wiring Diagrams Outdoor Units 57 4 Wiring Diagrams CCT 50HINVo CCT 70HINVo...
Page 26: ...Wiring Diagrams 58 Outdoor Units CCT 100HINVo...
Page 45: ...Troubleshooting 108 Electrical Control System 2 4 1 2 Outdoor unit malfunction...
Page 50: ...Troubleshooting Electrical Control System 113 2 4 2 3 Up down panel is not closed...
Page 54: ...Troubleshooting Electrical Control System 117 2 4 4 3 E3 malfunction...
Page 55: ...Troubleshooting 118 Electrical Control System 2 4 4 4 E4 malfunction...
Page 60: ...Troubleshooting Electrical Control System 123 2 4 4 9 P1 malfunction For 36k models...
Page 61: ...Troubleshooting 124 Electrical Control System 2 4 4 10 P2 malfunction For 36k models...
Page 62: ...Troubleshooting Electrical Control System 125 2 4 4 11 P3 malfunction...