Installation
Page 22
RES-403
actual value output:
The controller is functioning correctly if the tempera-
ture (which corresponds to the signal change at the
analog output) has a harmonious motion, in other
words it must not jump abruptly, fluctuate or deviate
temporarily in the wrong direction. This kind of beha-
vior would indicate that the U
R
measuring wires
have been wired incorrectly.
If an error code is displayed, please proceed as des-
cribed in section 9.12 "Error messages" on page 31.
9. Burn in the heatsealing band (
ª
"Replacing and "burning in" the heatsealing band"
on page 20) and repeat the AUTOCAL function.
8.13.2 Restart after replacing the heat-
sealing band
To replace the heatsealing band, proceed as described
in section 8.12 "Replacing and "burning in" the heat-
sealing band" on page 20.
Always use a heatsealing band with the cor-
rect alloy, dimensions and copper-plating in
order to avoid malfunctions and overheating.
Continue with section 8.13.1 steps 4 to 9.
The controller is now
ready
!