PIREG 545 cUL Operators Guide 2021
42
Advance Config. Menu 315 –
Total Life Cycles
ADVANCE CONFIG. 315
Tot.cycles:888888888
Total counter of executed sealing cycles. It is not possibly to set
counter to zero.
Advance Config. Menu 316 –
PIREG 545 Software Version
ADVANCE CONFIG. 316
PIREG-545-100
1.09 1.17 2.01 2.00
www.TOSSHEATSEAL.com
Type of resistance temperature controller PIREG
®
-545
Line 3:
Version of device and program versions
Line 4:
Address of Web-site of the Company.
Advance Config. Menu 317 –
Reset Input Function
ADVANCE CONFIG. 317
Reset Input:
Reset
(Reset/M.Pause/Sig.)
Selection of the following functions of the Reset input. The selection
is confirmed as always with the button
≡
.
(1) Reset: With a signal at the input the PIREG
®
-545 executes a re-
set.
(2) Measurement pause: With a high signal at the Reset input (26)
in the Off state, the PIREG
®
-545 stops the resistance measurement
making it possible to interrupt the heat seal band circuit without gen-
erating an alarm. If the measurement pause is activated, the symbol
Π
is shown on the right side of the cooling line on the Home screen.
See
Section 6.2
(3) Select Signal, Calibration Switching: Selection of the calibration
1 or 2. The PIREG
®
-545 has the possibility to handle the calibration
of two heat seal bands.
In configuration menu 317a select the time delay for the change be-
tween calibration 1 and 2.
Advance Config. Menu 317a –
Reset Input Time Delay
ADVANCE CONFIG. 317a
Time delay: 88s
(Off/1...99s)
Setting of the time delay at the change between the calibration 1 and
2.