PIREG 545 cUL Operators Guide 2021
18
5.7. Alarm state
The PIREG
®
-545 enters the Alarm state only when it detects an error. The controller monitors the mains
voltage, the heat seal band temperature, the current and voltage measurements on the heat seal band, the
calibration parameters and the monitor functions.
Here the error’s number, its description and a possible remedy are given.
5.7.1. Possible Alarms
:
Alarm
Code
Alarm Cause
Analog
(Between
Pins 20 & 24)
Fault Area
101
Current signal Ir missing
0.66
1
102
Voltage signal Ur missing
1.33
3
103
Current Ir and voltage Ur signal missing
2.00
2 or 9
104
Current signal Ir too high
6.33 <> 10
Run Autocal
7 or 8
or
Loose Contact
4, 5, or 6
105
Voltage signal Ur to high
106
Current signal Ir and voltage signal Ur too high
107
Temperature step, down
2.66
Loose Contact
4, 5, or 6
108
Temperature step, up
111
Calibration Error: Current signal Ir too low
6.66 <> 10
8
Calibration Error: Current signal Ir too high
112
Calibration Error: Voltage signal Ur too low
7.33 <> 10
7
Calibration Error: Voltage signal Ur too high
Calibration Error: Voltage signal Ur unstable
113
Calibration Error: Current signal Ir and voltage signal Ur
too high
8.00 <> 10
7 or 8
Calibration Error: Current signal Ir and voltage signal Ur
too low
Calibration Error: Current signal Ir too low, Voltage sig-
nal Ur too high
Calibration Error: Current signal Ir too high, Voltage sig-
nal Ur too low
Calibration Error: R20 cannot be determined
Calibration Error: P-factor could not be determined
121
Calibration Error: Reference temperature to high
122
Calibration Error: Range of Tc correction exceeded
123
Calibration Error: Temperature for steadiness and dy-
namic to low