Configuration Menu 207 –
Low Temperature Deviation
CONFIGURATION 207
Set achieved: -88K
(-99...-5K)
Configuration menu 207 is used for setting of the lowest allowable
temperature deviation in relation to “Set” Temp. This setting is only
applied when “temperature diagnosis” is programmed ON in Con-
figuration menu 217.
This lower limit is even used for preheat control.
Press the Menu Scroll
to change to Configuration menu 208
Configuration Menu 208 –
High Temperature Deviation
CONFIGURATION 208
Set exceeded: 88K
(6...99K)
Configuration menu 208 is used for setting of the highest allowable
temperature deviation in relation to “Set” Temp. This setting is only
applied when “temperature diagnosis” is programmed ON in Con-
figuration menu 217.
This highest limit is even used for preheat control.
Press the Menu Scroll
to change to Configuration menu 209
Configuration Menu 209 –
Time Control
CONFIGURATION 209
Time control: OFF
(OFF/ON/ON w.st.su.)
Configuration menu 209 is used for selection point of time control
(sequence control) is activated with (“ON”) and with start control
(“ON / w. start supervising”) and deactivating with (“OFF”).
Press Menu Scroll
to change to Configuration menu with:
- time control turned Off advance to Configuration menu 212
- time control turned On advance to Configuration menu 210
Configuration Menu 210 –
Cool Mode Selection
CONFIGURATION 210
Cool mode: absolute
(no/abs./rel./time)
Selection point for cooling mode:
Absolute: Cooling is set to a desired temperature.
Relative: Cooing is set as a percentage of sealing temperature.
Time : Cooling is set to time.
Press the Menu Scroll
to advance to Configuration menu 211
Configuration Menu 211 –
Start of Sealing Timer
CONFIGURATION 211
Sealing time starts
at set-temp.achieved
Selection for the start of sealing time.
“at start heating”: Sealing time starts upon a start signal.
"at set-temp. achieved“: sealing time starts when temperature of
heating band exceeds 95% of rated value.
Press the Menu Scroll
to advance to Configuration menu 212
Configuration Menu 212 – K1
Relay Function
CONFIGURATION 212
Relay K1 OFF
Selection function of Relay K1: For complete list of options refer to
Section 5.10. “Relay and Output Functions”.
Press the Menu Scroll
to advance to Configuration 213 menu. If
the Relay K1 function is programmed to generate seal phase im-
pulse (5) or cooling phase impulse (6), press Menu Scroll
to
advance to Configuration Menu 212a to set duration time of pulse.