4.1.2 Installing the Main Body Unit
Fig. 4.4
(1) Install the hoisting stand on the hoisting screw by using nuts and gaskets at
both the upper and lower sides of the hoisting stand. To prevent the gasket
from breaking off, a gasket anchor board can be helpful.
(2) Install the paper template on the unit, and fix the drain pipe at the outlet vent.
(3) Adjust the unit to the best position.
(4) Check if the unit is installed horizontally at four directions. If not, the water
pump and the float switch would function improperly and even lead to water
leakage.
(5) Remove the gasket anchor board and tighten the nut remained.
(6) Remove the paper template.
4.1.3 Installing the Suspension Bolts
(1) Using the installation template, drill holes for bolts (four holes) (Fig. 4.5).
(2) Install the bolts to the ceiling at a place strong enough to hang the unit. Mark
the bolt positions from the installation template. With a concrete drill, drill for
12.7mm (1/2inch) diameter holes (Fig. 4.6).