Standard specifications

Common specification

Sinusoidal PWM control

Digital setting: within 

±

0.01% of the max. frequency (-10 to +60

°

C)

Analog setting: within 

±

0.5% of the max. frequency (25

°

±

10

°

C)

Potentiometer on the front panel, external frequency potentiometer (connectable to a potentiometer with a rated impedance 
of 1 - 10k

), 0 - 10Vdc (input impedance: VIA/VIB=30k

), 4 - 20mAdc (Input impedance: 250

).

The characteristic can be set arbitrarily by two-point setting. Possible to set individually for three functions: analog input (VIA and VIB) and communication command.
Three frequencies can be set. Setting of the jump frequency and the range.
Upper-limit frequency: 0 to maximum frequency, lower-limit frequency: 0 to upper-limit frequency
Adjustable within a range of 2.0 to 16.0Hz (default: 12kHz).

Setting of proportional gain, integral gain, differential gain and control wait time. Checking whether the amount of processing amount and the amount of feedback agree.

The RUN and STOP keys on the operation panel are used to start and stop operation. The switching between forward run and 
reverse run can be done from one of the three control units: operation panel, terminal board and external control unit.

In the event of a momentary power failure, the inverter reads the rotational speed of the coasting motor and outputs a frequency appropriate 
to the rotational speed in order to restart the motor smoothly. This function can also be used when switching to commercial power.

Switching between standard motor and constant-torque VF motor, switching between motors 1 and 2, setting of overload 
trip time, adjustment of stall prevention levels 1 and 2, selection of overload stall

Stores data on the past four trips: number of trips that occurred in succession, operation frequency, direction of rotation, load current, input 
voltage, output voltage, information on input terminals, information on output terminals, and cumulative operation time when each trip occurred.

Lamps indicating the inverter status by lighting, such as RUN lamp, MON lamp, PRG lamp, % lamp, Hz lamp, frequency 
setting potentiometer lamp, UP/DOWN key lamp and RUN key lamp. The charge lamp indicates that the main circuit 
capacitors are electrically charged.

Function of resetting by closing contact 1a or by turning off power or the operation panel. This function is also used to save and clear trip records.
Stall prevention, overvoltage, overload, under-voltage, setting error, retry in process, upper/lower limits

Indoor, altitude: 1000m (Max.), not exposed to direct sunlight, corrosive gas, explosive gas / vibration (less than 5.9m/s

2

) (10 to 55Hz)

-10 to +60

°

Note 9,10)

-25 to +70

°

C

20 to 93% (free from condensation and vapor).

Stall prevention, current limitation, over-current, output short circuit, over-voltage, over-voltage limitation, undervoltage, ground fault, power supply phase 
failure, output phase failure, overload protection by electronic thermal function, armature over-current at start-up, load side over-current at start-up, over-
torque, undercurrent, overheating, cumulative operation time, life alarm, emergency stop, braking resistor over-current/overload, various pre-alarms

Over-current, overvoltage, overheating, short-circuit in load, ground fault, overload on inverter, over-current through arm at start-up, over-
current through load at start-up, CPU fault, EEPROM fault, RAM fault, ROM fault, communication error. (Selectable: Over-current 
through braking resistor/overload, emergency stop, under-voltage, low voltage, over-torque, motor overload, output open-phase)

Analog output (1mAdc full-scale DC ammeter or 7.5Vdc full-scale DC voltmeter/rectifier type AC voltmeter, 4 to 20mA/0 
to 20mA output)

Operation frequency, operation frequency command, forward/reverse run, output current, voltage in DC section, output voltage, torque, 
torque current, load factor of inverter, integral load factor of PBR, input power, output power, information on input terminals, information on 
output terminals, version of CPU1, version of CPU2, version of memory, PID feedback amount, frequency command (after PID), integral 
input power, integral output power, rated current, causes of past trips 1 through 4, information on life alarm, cumulative operation time

Frequency: inverter output frequency.
Alarm: stall alarm “C”, overvoltage alarm “P”, overload alarm “L”, overheat alarm “H”.
Status: inverter status (frequency, cause of activation of protective function, input/output voltage, output current, etc.) and parameter settings.
Free-unit display: arbitrary unit (e.g. rotating speed) corresponding to output frequency.

Possible to select from 76 functions, such as forward/reverse run signal input, jog run signal input, operation base signal 
input and reset signal input, to assign to 8 input terminals. Logic selectable between sink and source.

Possible to select from 58 functions, such as upper/lower limit frequency signal output, low speed detection signal output, specified speed 
reach signal output and failure signal output, to assign to FL relay output, open collector output and RY output terminals.

Capable of restarting automatically after a check of the main circuit elements in case the protective function is activated. 10 times (Max.) (selectable with a parameter)
Possible to write-protect parameters and to prohibit the change of panel frequency settings and the use of operation panel for operation, emergency stop or resetting.
Possible to keep the motor running using its regenerative energy in case of a momentary power failure.

When two or more inverters are used to operate a single load, this function prevents load from concentrating on one inverter due to unbalance.

The sum of two analog signals (VIA/VIB) can be used as a frequency command value.
1c-contact output: (250Vac-0.5A-cos 

φ

 = 0.4)

Braking start-up frequency: 0 to maximum frequency, braking rate: 0 to 100%, braking time: 0 to 20 seconds, emergency 
DC braking, motor shaft fixing control

Selectable from among acceleration/deceleration times 1, 2 or 3 (0.0 to 3200 sec.). Automatic acceleration/deceleration function.
S-pattern 1 or 2, and S-pattern value adjustable. Forced rapid deceleration and dynamic rapid deceleration function.

Control and drive circuit is built in the inverter with the braking resistor outside (optional).

Jog mode, if selected, allows jog operation from the operation panel or the terminal board.
Base fre 15-speed operation possible by changing the combination of 4 contacts on the terminal board.

Adjustable within the range of 50 to 600V by correcting the supply voltage (not adjustable above the input voltage)
0.5 to 500.0Hz, default setting: 0.5 to 80Hz, maximum frequency: 30 to 500Hz

0.01Hz: operation panel setting, 0.1Hz: analog input (when the max. frequency is 100Hz).

V/f constant, variable torque, automatic torque boost, vector control, automatic energy-saving, dynamic automatic energy-
saving control. Auto-tuning. Base frequency (25 - 500Hz) adjusting to 1 or 2, torque boost (0 - 30%) adjusting to 1 or 2, 
adjusting frequency at start (0.5 - 10Hz)

Principal control functions

Operation specifications

Protective function

Display function

Environments

Control system
Rated output voltage
Output frequency range
Minimum setting steps of frequency
Frequency accuracy

Voltage/frequency characteristics

Frequency setting signal

Terminal board base frequency
Frequency jump
Upper- and lower-limit frequencies
PWM carrier frequency
PID control

Acceleration/deceleration time 

DC braking

Dynamic braking
Input terminal function 
(programmable)
Output terminal functions 
(programmable)
Forward/reverse run

Jog run
Preset speed operation
Retry operation
Various prohibition settings
Regenerative power ride-through control
Auto-restart operation

Drooping function
Override function
Failure detection signal
Protective function

Electronic thermal characteristic

Reset function
Alarms
Causes of failures

Monitoring function

Past trip monitoring function

Output for frequency meter

4-digit 7-segments LED

Indicator

Use environments
Ambient temperature
Storage temperature
Relative humidity

Specification

Item

3-phase 240V

1-phase 240V

3-phase 600V

Item

Specification

3-phase 240V

VFS11

3-phase 200V to 240V

150%-60 seconds, 200%-0.5 second 

Note 4)

3-phase 200V to 240V - 50/60Hz

V 10%, -15% 

Note 5)

, frequency 

±

5%

IP20 Enclosed type (JEM1030)

Munsel 5Y-8/0.5

Self-cooling

Basic filter 

Note 7)

Forced air-cooled

3.3

(3.3)

4.8

(4.4)

8.0

(7.9)

17.5

(16.4)

27.5

(25.0)

33

(33)

54

(49)

66

(60)

2004PM

1.3

2007PM

1.8

2015PM

3.0

2037PM

6.7

2055PM

10

2075PM

13

2110PM

21

2150PM

25

0.4

3.7

(3.3)

2005PM

1.4

0.55

0.75

1.5

11.0

(10.0)

2022PM

4.2

2.2

4.0

5.5

7.5

11

15

Input voltage class

Applicable motor (kW)

Protective method

Cooling method

Color

Built-in filter

Type

Form

Capacity (kVA) 

Note 1)

Output voltage 

Note 3)

Overload current rating

Voltage-frequency

Allowable fluctuation

Rated output current

(A) 

Note 2)

Rating

Power supply

Item

Note 1.

Note 2.

Note 3.

Note 4.

Note 5.

Note 6.

Note 7.

Note 8.

Note 9.

Note10.

Capacity is calculated at 220V for the 240V class, at 440V for the 500V class and at 575V for the 600V models.

Indicates rated output current setting when the PWM carrier frequency (parameter F300) is 4kHz or less.
When exceeding 4kHz, the rated output current setting is indicated in the parenthesis. When the input power voltage of the 500V class model exceeds 480V, it is necessary to further reduce the setting. The default 
setting of the PWM carrier Frequency is 12kHz.

Maximum output voltage is the same as the input voltage.

May differ according to voltage and model.

±

10% when the inverter is used continuously (load of 100%).

If you are using 600V model, be sure to connect an input reactor (ACL).

Built-in standard filter: Core and capacities With RFI noise filter option: Complies EN55011 Class A Group 1(Max.5m*) and Class B Group 1(Max.1m*)
* Length of motor connecting cable.

Built-in high-attenuation EMI filter: Complies EN55011 Class A Group 1(Max.5m*) With RFI noise filter option : Complies EN55011 Class B Group 1(Max.20m*) and Class A Group 1(Max.50m*)
* Length of motor connecting cable.

Above 40

°

C : Remove the protective seal from the top of the inverter. Above 50

°

C: Remove the seal from the top of the inverter and use the inverter with the rated output current reduced.

If inverters are installed side by side (with no sufficient space left between them) installation: Remove the seal from the top of each inverter. 
When installing the inverter where the ambient temperature will rise above 40

°

C, remove the seal from the top of the inverter and use the inverter with the rated output current reduced. 

3-phase 500V

Item

Standard specifications

Input voltage class

Applicable motor (kW)

Protective method

Cooling method

Color

Built-in filter

Type

Form

Capacity (kVA) 

Note 1)

Output voltage 

Note 3)

Overload current rating

Voltage-frequency

Allowable fluctuation

Rated output current

(A) 

Note 2)

Rating

Power supply

Input voltage class

Applicable motor (kW)

Protective method

Cooling method

Color

Built-in filter

Type

Form

Capacity (kVA) 

Note 1)

Output voltage 

Note 3)

Overload current rating

Voltage-frequency

Allowable fluctuation

Rated output current

(A) 

Note 2)

Rating

Power supply

IP20 Enclosed type (JEM1030)

3-phase 500V

3-phase 380V to 500V

150%-60 seconds, 200% -0.5 second 

Note 4)

3-phase 380V to 500V - 50/60Hz

V 10%, -15% 

Note 5)

, frequency 

±

5%

0.75

1.5

2.2

4.0

5.5

7.5

11

15

4007PL

1.8

2.3

(2.1)

0.4

4004PL

1.1

1.5

(1.5)

4015PL

3.1

4.1

(3.7)

4022PL

4.2

5.5

(5.0)

4037PL

7.2

4055PL

11

4075PL

13

4110PL

21

4150PL

25

9.5

(8.6)

14.3

(13.0)

17.0

(17.0)

27.7

(25.0)

33

(30)

Forced air-cooled

Munsel 5Y-8/0.5

High-attenuation EMI filter 

Note 8)

Specification

VFS11

1-phase 240V

3-phase 600V 

Note 6)

VFS11S

VFS11

3-phase 200V to 240V

1-phase 200V to 240V – 50/60Hz

3-phase 525V to 600V – 50/60Hz

3-phase 525V to 600V

0.2

0.4

0.75

1.5

2.2

2002PL

0.6

1.5

(1.5)

2004PL

1.3

3.3

(3.3)

2007PL

1.8

4.8

(4.4)

2015PL

3.0

8.0

(7.9)

2022PL

4.2

11.0

(10.0)

0.75

6007P

1.7

1.7

(1.5)

1.5

6015P

2.7

2.7

(2.4)

2.2

6022P

3.9

3.9

(3.5)

4.0

6037P

6.1

6.1

(5.5)

5.5

6055P

9.0

9.0

(8.1)

7.5

6075P

11

11.0
(9.9)

11

6110P

17

17.0

(15.3)

15

6150P

22

22.0

(19.8)

Self-cooling

Forced air-cooled

Forced air-cooled

IP20 Enclosed type (JEM1030)

 

150%-60 seconds, 200%-0.5 second 

Note 4)

 

V 10%, -15% 

Note 5)

, frequency

±

5%

Munsel 5Y-8/0.5

IP20 Enclosed type (JEM1030)

 

150%-60 seconds, 200%-0.5 second 

Note 4)

 

V 10%, -15% 

Note 5)

, frequency

±

5%

Munsel 5Y-8/0.5

 

High-attenuation EMI filter 

Note 8)

 

No filter

Specification

Type

Form

S

V

F

11 S

2

0

0

7

P

L

E

W N

TOSVERT

VF-S11 Series

S:

1-phase

None: 3-phase

2: 240V class
     (200 to 240V)
4: 500V class
     (380V to 500V)
6: 600V class
     (525V to 600V)

None: No filter 
L: High-attenuation EMI 

filter inside

M: Basic filter inside

WN: Sink(Negative)
WP: Source(Positive)

P: Provided

Note) Interface logic can be 
         switched by  slide switch easily.

002: 0.2kW
004: 0.4kW
005: 0.55kW
007: 0.75kW
015: 1.5kW
022: 2.2kW
037: 4.0kW
055: 5.5kW
075: 7.5kW
110: 11kW
150: 15kW

Model name

Number of power phases

Input voltage

Applicable motor capacity

Additional functions

Ⅰ 

None: Standard type
E: Totally enclosed type
U: Open type

Additional functions

Ⅱ 

Interface logic

(Shipment setting)

Operation panel

Contents of the product code

Standard specifications

Summary of Contents for TOSVERT VF-S11

Page 1: ...ns must be studied carefully When using our inverters for critical equipment even though the inverters are manufactured under strict quality control always fit your equipment with safety devices to prevent serious accident or loss should the inverter fail such as issuing an inverter failure signal Do not use our inverters for any load other than three phase induction motors None of Toshiba its sub...

Page 2: ...ditioning systems and plant line control systems As well as being highly expandable the VF S11 uses a detachable type of control terminal board which allows you to easily mount optionally available communication boards RS 485 DeviceNet and LonWorks DeviceNet is a registered trademarks of ODVA Open DeviceNet Vendor Association For users who need a wide capacity and range of models For obtaining spa...

Page 3: ...omentary monitor values for when a trip occurs can be viewed Ten monitor values are stored in memory for the last four inverter operations which is effective in pin pointing the cause of a trip Storage of user parameter settings All parameter settings made by the user can be stored in memory Stored parameters can be immediately called even they have been changed History function This function is f...

Page 4: ...the range of 50 to 600V by correcting the supply voltage not adjustable above the input voltage 0 5 to 500 0Hz default setting 0 5 to 80Hz maximum frequency 30 to 500Hz 0 01Hz operation panel setting 0 1Hz analog input when the max frequency is 100Hz V f constant variable torque automatic torque boost vector control automatic energy saving dynamic automatic energy saving control Auto tuning Base f...

Page 5: ...g across F CC causes forward rotation open causes slowdown and stop Shorting across R CC causes reverce rotation open causes slowdown and stop RES S1 S2 S3 Shorting across S1 CC causes preset speed operation Shorting across S2 CC causes preset speed operation Shorting across S3 CC causes preset speed operation CC PLC Control circuit s equipotential terminal sink logic 3 common terminals for input ...

Page 6: ... 5 5 0 5 1 9 6 9 6 1 0 1 0 1 2 1 4 2 2 1 3 1 3 2 1 2 2 4 7 4 7 8 8 8 8 3 phase 240V 3 phase 500V Input voltage Applicable motor kW Type H W D H1 H2 Approx weight kg W1 D2 Drawing Dimensions mm 0 4 0 55 0 75 1 5 2 2 4 0 5 5 7 5 11 15 0 4 0 75 1 5 2 2 4 0 5 5 7 5 11 15 0 2 0 4 0 75 1 5 2 2 0 75 1 5 2 2 4 0 5 5 7 5 11 15 VFS11 2004PM VFS11 2005PM VFS11 2007PM VFS11 2015PM VFS11 2022PM VFS11 2037PM VF...

Page 7: ...rs Protection parameters Set to generate high torque to match load or motor Torque up parameters Set if changing units displayed or various display methods Panel display parameters List of parameters 12 DC Braking parameters Title Function Adjustment range Default setting DC braking starting frequency DC braking current DC braking time Motor shaft fixing control 0 0 Hz 0 100 A 0 0 20 0 s 0 Invalid...

Page 8: ...put and output cables etc of the inverter To prevent current leakage it is recommended to take the following measures Effects of leakage current Leakage current which increases when an inverter is used may pass through the following routes Route 1 Leakage due to the capacitance between the ground and the noise filter Route 2 Leakage due to the capacitance between the ground and the inverter Route ...

Page 9: ...CL High attenuation radio noise filter NF type Braking resistor Conduit pipe attachment kit Motor end surge voltage suppression filter for 500V class only Zero phase reactor ferrite core type EMC noise filter Compliant with European standards P 17 P 18 P 18 P 9 P 20 P 20 P 19 P 18 P 19 P 19 P 19 P 20 Used to improve the input power factor reduce the harmonics and suppress external surge on the inv...

Page 10: ...ox with cover 4 ØF holes AC reactor Power source AC reactor Power source P Earth terminal Power source LC filter Model Rated current A Inverter type Diagram Terminals Approx weight kg Dimensions mm W H D X Y d1 d2 DCLS 2002 DCL 2007 DCL 2022 DCL 2037 DCL 2055 DCL 2110 DCL 2220 DCL 2007 DCL 2022 DCL 4110 DCL 4220 2 5 7 14 22 5 38 75 150 7 14 38 75 79 92 86 86 75 100 117 92 86 95 105 50 65 110 110 1...

Page 11: ...devices 19 Devices External dimensions and connections Motor end surge voltage suppression filter for 500V class only Parameter writer Extension panel Motor end surge voltage suppression filter l Invertor type Approx weight kg MSF 4015Z MSF 4037Z MSF 4075Z MSF 4150Z Dimensions mm Depth 12 20 30 40 Terminal screw M4 M4 M5 M5 Grounding screw M4 M4 M5 M5 VFS11 4004 4015PL VFS11 4022 4037PL VFS11 4055...

Page 12: ...it breaker Minimum wiring Cooling structure Self cooling type 22 21 Command mode selection Frequency setting mode selection 1 0 Function VF S11 Standard type 0 2 VF S11 otally enclosed type Title External dimensions Fig F 3ph 240V 3ph 500V 1ph 240V VFS11 2004PME VFS11 2007PME VFS11 2015PME VFS11 2022PME VFS11 2037PME VFS11 4007PLE VFS11 4015PLE VFS11 4022PLE VFS11 4037PLE VFS11 4055PLU VFS11 4075P...

Reviews: