Jog
The jogging frequency is immediately output when the remote JOG is activated. The
functions [:JOG] and [:J.StP] must be preset. In addition, the JOG(SS2) terminal must
be set for "JOG". This is accomplished by setting the function parameter [:l.tb] to 1 or 3.
The terminal connections are shown below:
Terminal Connections Required For Remote Jog
ST
F
R
CC
SS1
JOG
(SS2)
AD2
(SS3)
ST
F
R
Hz
Jogging run
frequency (JOG)
set by keypad
Run frequency
setting from
terminals
R-CC
ST-CC
F-CC
PP, RR, IV
Terminal
inputs
TIME
JOG-CC
OUTPUT FREQUENCY
Notes:
1)
A jogging run cannot be engaged by closing the JOG switch during a run.
2)
The inverter will decelerate at the selected rate during: deceleration stop, coast to stop, and DC
injection stop.
3)
F-CC must be broken for DC injection to be applied; breaking only JOG(SS2)-CC allows the
inverter to accept other input signals and is not a "true" off.
4)
See table on next page for terminal inputs and actions.
10.5
Resetting After a Trip
Pressing reset on the keypad resets the inverter faults. Momentarily closing a normally
open dry contact between terminals RST and COM resets the inverter faults remotely.
Warning:
When the inverter trips due to an emergency stop or the activation of one
or more of its protective functions, the cause of the fault must be corrected before
resetting the inverter. A forced restart with out prior fault correction measures
could damage the inverter and connected devices.