22
Super Digital Inverter
EN
EN
7
ELECTRICAL WORK
WARNING
1. Using the specified wires, ensure that the wires are
connected, and fix wires securely so that the external
tension to the wires does not affect the connecting
part of the terminals.
Incomplete connection or fixation may cause a fire, etc.
2. Be sure to connect the earth wire. (grounding work)
Incomplete grounding may lead to electric shock.
Do not connect ground wires to gas pipes, water pipes,
lightning rods or ground wires for telephone wires.
3. The appliance shall be installed in accordance with
national wiring regulations.
Capacity shortages of the power circuit or an incomplete
installation may cause an electric shock or fire.
CAUTION
•
Wrong wiring may cause a burn-out of some electrical
parts.
•
Be sure to use the cord clamps attached to the product.
•
Do not damage or scratch the conductive core or inner
insulator of the power and inter-connecting wires when
peeling them.
•
Use the power and Inter-connecting wires with specified
thicknesses, specified types and protective devices
required.
•
Remove the panel, and you can see electric parts on the
front side.
•
A metal pipe can be installed through the hole for wiring.
If the hole size does not fit the wiring pipe to be used, drill
the hole again to an appropriate size.
•
Be sure to clamp the power wires and indoor/outdoor
connecting wires with a banding band along the
connecting pipe so that the wires do not touch the
compressor or discharge pipe.
(The compressor and the discharge pipe become hot.)
Furthermore, be sure to secure these wires with the pipe
valve fixing plate and cord clamps stored in the electric parts
box.
Wiring between Indoor Unit and Outdoor Unit
The dashed lines show on-site wiring.
•
Connect the indoor/outdoor connecting wires to the identical terminal numbers on the terminal block of each unit.
Incorrect connection may cause a failure.
For the air conditioner, connect a power wire with the following specifications.
*
Number of wire
×
wire size
Electric parts box
Pipe valve fixing
plate
Cord clamp
Pipe hole
Panel
2
1
3
2
1
3
N
Β
Α
L2
L3
L1
Outdoor unit
Wired remote controller
Indoor unit
Leakage breaker
Input power
380-415 V 3N~, 50Hz
Model (RAV-SP Type)
110AT8
140AT8
160AT8
Power supply
380-415 V 3N~
50 Hz
Maximum running current
16.4 A
Recommended field fuse
20 A
Power wire*
5
×
2.5 mm
2
or more
(H07 RN-F or 60245 IEC 66)
Indoor/outdoor connecting wires*
4
×
1.5 mm
2
or more
(H07 RN-F or 60245 IEC 66)