15
Super Digital Inverter
Serial installation in front and rear
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the unit
should be lower than the height of the outdoor unit.
Standard installation
Installation of Outdoor Unit
•
Before installation, check the strength and horizontalness
of the base so that abnormal sounds do not emanate.
•
According to the following base diagram, fix the base
firmly with the anchor bolts.
(Anchor bolt, nut: M10 x 4 pairs)
•
As shown in the figure below, install the foundation and
vibration-proof rubber pads to directly support the bottom
surface of the fixing leg that is in contact with and
underneath the bottom plate of the outdoor unit.
*
When installing the foundation for an outdoor unit with
downward piping, consider the piping work.
Set the out margin of the anchor bolt to 15 mm or less.
1,000 or
more
300 or
more
1,500 or
more
2,000 or
more
200 or
more
150
150
600
525
45
365
400
Drain nipple
mounting hole
Drain hole
Drain hole
GOOD
Fixing leg
Absorb vibration
with vibration-proof
rubber pads
Foundation
GOOD
Bottom plate of
outdoor unit
Foundation
Support the bottom surface of the
fixing leg that is in contact with and
underneath the bottom plate of the
outdoor unit.
NO GOOD
If only the end of the
fixing leg is supported, it
may deform.
Do not support the
outdoor unit only with
the fixing leg.
Foundation
15 or less
EN-15