background image

Wired

remote

controller

display

Wireless remote controller

Sensor block display of

receiving unit

Main defective parts

Judging

device

Parts to be checked / error description

Air

conditioner

status

Indication

Operation Timer

Ready

GR GR OR

Flashing

F12

ALT

TS sensor error

Outdoor

TS sensor may be displaced, disconnected or 

short-circuited.

Entire stop

F13

ALT

Heat sink sensor error

Outdoor

Abnormal temperature was detected by the temp. 

sensor of the IGBT heat sink.

Entire stop

F15

ALT

Temp. sensor

connection error

Outdoor

Temp. sensor (TE/TS) may be connected

incorrectly.

Entire stop

F29

SIM

Indoor unit, other 

P.C. board error

Indoor

 Indoor P.C. board --- EEPROM error

Auto-reset

F31

SIM

Outdoor unit P.C. board Outdoor

Outdoor P.C. board ---- In the case of EEPROM

error.

Entire stop

H01

Outdoor unit

compressor

breakdown

Outdoor

Current detect circuit, power voltage --- Minimum 

frequency was reached in the current releasing 

control or short-circuit current (Idc) after direct 

excitation was detected

Entire stop

H02

Outdoor unit

compressor lock

Outdoor

Compressor circuit --- Compressor lock was

detected.

Entire stop

H03

Outdoor unit current

detect circuit error

Outdoor

Current detect circuit, outdoor unit P.C. board --- 

Abnormal current was detected in AC-CT or a

phase loss was detected.

Entire stop

H04

Case thermostat

operation (1)

Outdoor

Malfunction of the case thermostat

Entire stop

H06

Outdoor unit

low-pressure system 

error

Outdoor

Current, high-pressure switch circuit, outdoor P.C.

board --- Pressure sensor error was detected or

low-pressure protective operation was activated.

Entire stop

L03

SIM

Duplicated header

indoor units 

Indoor

Indoor address setting error --- There are two or

more header units in the group.

Entire stop

L07

SIM

Group line in individual

indoor unit  

Indoor

Indoor address setting error --- There is at least

one group-connected indoor unit among individual 

indoor units.

Entire stop

L08

SIM

Indoor group address

not set  

Indoor

Indoor address setting error --- Indoor address

group has not been set.

Entire stop

L09

SIM

Indoor unit capacity

not set

Indoor

Indoor unit capacity has not been set.

Entire stop

L10

SIM

Outdoor unit P.C. board Outdoor

In the case of outdoor P.C. board jumper wire

(for service) setting error

Entire stop

L20

SIM

LAN communication

error

Network

adapter

central

control

Address setting, central control remote controller, 

network adapter --- Duplication of address in 

central control communication

Auto-reset

L29

SIM

Other outdoor unit

error

Outdoor

Other outdoor unit error

Entire stop

1) Communication error between IPDU MCU and

    CDB MCU

Entire stop

2) Abnormal temperature was detected by the heat 

    sink temp. sensor in IGBT.

L30

SIM

Abnormal external

input into indoor unit

(interlock)

Indoor

External devices, outdoor unit P.C. board ---

Abnormal stop due to incorrect external input into 

CN80

Entire stop

L31

SIM

Phase sequence 

error, etc.

Outdoor

Power supply phase sequence, outdoor unit P.C. 

board --- Abnormal phase sequence of the 3-phase 

power supply

Operation

continued

(thermost

at OFF)

Wired

remote

controller

display

Wireless remote controller

Sensor block display of

receiving unit

Main defective parts

Judging

device

Parts to be checked / error description

Air

conditioner

status

Indication

Operation Timer

Ready

GR GR OR

Flashing

P01

ALT

Indoor unit fan error

Indoor

Indoor fan motor, indoor P.C. board --- Indoor AC

fan error (fan motor thermal relay activated) was

detected.

Entire stop

P03

ALT

Outdoor unit discharge

temp. error

Outdoor

An error was detected in the discharge temp.

releasing control.

Entire stop

P04

ALT

Outdoor unit 

high-pressure system 

error

Outdoor

High-pressure switch --- The IOL was activated

or an error was detected in the high-pressure

releasing control using the TE.

Entire stop

P05

ALT

Open phase detected

Outdoor

The power wire may be connected incorrectly.

Check open phase and voltages of the power

supply.

Entire stop

P07

ALT

Heat sink overheat

Outdoor

Abnormal temperature was detected by the temp. 

sensor of the IGBT heat sink.

Entire stop

P10

ALT

Indoor unit water

overflow detected

Indoor

Drain pipe, clogging of drainage, float switch

circuit, indoor P.C. board --- Drainage is out of

order or the float switch was activated.

Entire stop

P12

ALT

The fan error of the

indoor unit

Indoor

Abnormal operation of the indoor fan motor, indoor

P.C. board, or indoor DC fan (over current or lock,

etc.) is detected.

Entire stop

P15

ALT

Gas leakage detected

Outdoor

There may be gas leakage from the pipe or

connecting part. Check for gas leakage.

Entire stop

P19

ALT

4-way valve error

Outdoor

(Indoor)

4-way valve, indoor temp. sensors (TC/TCJ) --- An 

error was detected due to temperature drop of the 

indoor unit heat exchanger sensor when heating.

Auto-reset

P20

ALT

High-pressure

protective operation

Outdoor

High-pressure protection

Entire stop

P22

ALT

Outdoor unit fan error

Outdoor

Outdoor unit fan motor, outdoor unit P.C. board --- 

An error (overcurrent, locking, etc.) was detected in 

the outdoor unit fan drive circuit.

Entire stop

P26

ALT

Outdoor unit inverter

Idc activated

Outdoor

IGBT, outdoor unit P.C. board, inverter wiring,

compressor --- Short-circuit protection for

compressor drive circuit devices (G-Tr/IGBT) was 

activated.

Entire stop

P29

ALT

Outdoor unit position

error

Outdoor

Outdoor unit P.C. board, high-pressure switch ---

Compressor motor position error was detected.

Entire stop

P31

ALT

Other indoor unit error

Indoor

Another indoor unit in the group is raising an alarm.  Entire stop
E03/L07/L03/L08 alarm check locations and error 

description

Auto-reset

  : Lighting     : Flashing     : OFF    : The air conditioner automatically enters the auto-address setting mode.

ALT : When two LEDs are flashing, they flash alternately.  SIM : When two LEDs are flashing, they flash in synchronization.

Receiving unit display OR : Orange   GR : Green

� 27 �

53-EN

54-EN

1115350171_EN,FR,ES.indd   28

19/3/2565   9:38:48

Summary of Contents for RAV-SM182UTP-UL

Page 1: ...name 4 way Cassette type RAV SM182UTP UL RAV SM242UTP UL RAV SM302UTP UL RAV SM362UTP UL RAV SM422UTP UL RAV SM482UTP UL For commercial use Pour usage commercial Para uso comercial Installation Manual 1 English 1115350171 1115350171_EN FR ES indd 1 19 3 2565 9 37 17 ...

Page 2: ...for safety follow the Installation Manual attached to the outdoor unit ADOPTION OF NEW REFRIGERANT This Air Conditioner uses R410A an environmentally friendly refrigerant Contents 1 Precautions for safety 3 2 Accessory parts 7 3 Selection of installation place 8 4 Installation 9 5 Drain piping 11 6 Refrigerant piping 13 7 Electrical connection 14 8 Applicable controls 16 9 Test run 23 10 Maintenan...

Page 3: ...he qualified service person who is allowed to do the electrical work involved in installation repair relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or s...

Page 4: ...led for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body Before opening the intake grille of the indoor unit or service panel of the outdoor unit set the circuit breaker to the OFF position Failure to set the circuit breaker to the OFF position may result in e...

Page 5: ...se by lay persons When the air conditioner is installed in a small room provide appropriate measures to ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level Do not install in a location where flammable gas leaks are possible If the gas leak and accumulate around the unit it may ignite and cause a fire To transport the air conditioner wear shoes ...

Page 6: ...irtight test The charge hose must be connected tightly and in a proper manner To connect the electrical wires repair the electrical parts or undertake other electrical jobs wear gloves to provide protection for electricians and from heat insulating shoes and clothing to provide protection from electric shocks Failure to wear this protective gear may result in electric shocks Use wiring that meets ...

Page 7: ...check the insulation resistance and water drainage Then conduct a test run to check that the air conditioner is operating properly Upon completion of the installation work tell the user where the circuit breaker is located If the user does not know where the circuit breaker is he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner If the fan grille ...

Page 8: ...tion of at least 0 1 3 mm The installation fuse all types can be used must be used for the power supply line of this conditioner Part name Q ty Shape Usage Installation Manual 1 This manual Hand over to customers Owner s Manual 1 Hand over to customers Insulation pipe 2 For heat insulation of pipe connecting section Installation pattern 1 For confirmation of ceiling opening and indoor unit positio...

Page 9: ...es private power generators medical equipment and communication equipment and inverter type fluorescent light is installed A malfunction of the air conditioner abnormal control or problems due to noise to such appliances equipment may occur When the wireless remote controller is used in a room equipped with an inverter type fluorescent light or at a place exposed to direct sunlight signals from th...

Page 10: ...ge of the indoor units and human injury Do not put a heavy article on the indoor unit Even units are packaged Carry in the indoor unit as it is packaged if possible If carrying in the indoor unit unpacked by necessity be sure to use buffering cloth etc to not damage the unit To move the indoor unit hold the hooking metals 4 positions only Do not apply force to the other parts refrigerant pipe drai...

Page 11: ...oard Use M10 hanging bolts 4 pcs locally procured Matching to the existing structure set pitch according to size in the unit external view as shown below Hole New concrete slab Install the bolts with insert brackets or anchor bolts Steel flame structure Use existing angles or install new support angles Existing concrete slab Use a hole in anchors hole in plugs or a hole in bolts Rubber Anchor bolt...

Page 12: ...stance within approx 26 2 8 m Based upon it determine a place where the remote controller is operated and the installation place Operate the remote controller confirm that the indoor unit receives a signal surely and then install it Keep 3 3 1 m or more from the devices such as television stereo etc Disturbance of image or noise may generate To prevent a malfunction select a place where is not inf...

Page 13: ...ound of the drain pump motor If the operation sound changes from continuous sound to intermittent sound water is normally drained After the check the drain pump motor runs connecting the float switch connector In case of check by pulling out the float switch connector be sure to return the connector to the original position As shown in the figure cover the flexible hose and hose band with the atta...

Page 14: ...mpleted If the indoor unit is powered on the pulse motor valve is fully closed which extends the time for vacuuming Apply the heat insulation to the pipe connecting section of the indoor unit securely up to the root without exposure of the pipe The pipe exposed to the outside causes water leak Wrap heat insulator with its slits facing up ceiling side Wrap the pipe with the attached heat insulator ...

Page 15: ...the conductive core and inner insulator of power and system interconnection wires during peeling them Perform the electric wiring so that it does not come to contact with the high temperature part of the pipe The coating may melt resulting in an accident Do not turn on the power of the indoor unit until vacuuming of the refrigerant pipes completes Number of wire wire size CAUTION CAUTION Remote co...

Page 16: ...g connecting port Screws 2 positions Hinge Louver connector CN510 White Adhered surface Notched section Cord clamp Remote controller terminal block Power supply terminal block Side D Space 0 33 8 5 mm Side C Space 0 15 4 mm Select side C or D for the power cable clamping position referring to the following table according to the cable type and diameter Cable clamp can be attached on either right o...

Page 17: ...No not listed is set it may not be possible to operate the air conditioner or other trouble with the product may result When the power is turned on from the second time It takes about 1 minute before the remote control becomes operable Change the settings while the air conditioner is not working Stop the air conditioner before making settings Normal settings were made when the indoor unit was ship...

Page 18: ...r sign term from the following table When it is difficult to obtain satisfactory heating due to installation place of the indoor unit or structure of the room the detection temperature of heating can be raised Also use a circulator etc to circulate heat air near the ceiling Follow the basic operation procedure 1 2 3 4 5 6 For the CODE No in Procedure 3 specify 06 For the SET DATA in Procedure 4 se...

Page 19: ...h the CANCEL button The screen returns to the menu screen 1 Push the Swing OFF F2 button on the Individual louver screen 2 Push the CANCEL button The screen returns to the menu screen 1 Push the button to select 2 Individual louver on the menu screen push the Set F2 button 2 Push the Louver No F1 button to select the louver to set The display changes as follows each time the button is pushed 3 Pus...

Page 20: ... then push the Set F2 button 3 Push the Louver No F1 button to select the louver to set The display changes as follows each time the button is pushed No function appears on the display for the models not equipped with the Swing type setting Push the CANCEL button to stop the setting procedure No setting has been made and the screen returns to Louver setting NOTE Electrical control box Refrigerant ...

Page 21: ...eturn to the Field setting menu screen 1 Push the button to select 2 Energy saving ratio on the Energy saving operation screen then push the Set F2 button 3 Push the MENU button Setting appears on the screen then the screen returns to the Energy saving operation screen 2 Push the F1 F2 button to set the value The Energy saving ratio can be set within the range from 50 to 100 by 1 The lower the val...

Page 22: ... allows simultaneous ON OFF operation of the indoor units The following system patterns are available Two indoor units for the twin system Three indoor units for the triple system Four indoor units for the double twin system One remote controller can control maximum 8 indoor units as a group Required time up to the finish of automatic addressing is approx 5 minutes For wiring procedure and wiring ...

Page 23: ...DN with the F1 button then set Code DN with the button CODE No 14 Group address 2 Change the SET DATA from 0001 to 0002 with Move the cursor to select Data with the F2 button then set Data with the button SET DATA Header unit 0001 Follower unit 0002 3 Push the MENU button to set the other Code DN and Data After Continue is displayed on the screen push the Yes F1 button 6 If there is other indoor u...

Page 24: ... setting menu Push and hold the buttons for more than 4 seconds 1 Push the MENU button to display the menu screen Push and hold the MENU button and the button at the same time to display the Field setting menu Push and hold the buttons for more than 4 seconds Push the CANCEL button to return SET DATA 46 F 8 C Operation setting 0000 None Factory default 0001 46 F 8 C Operation setting 9 Test run Do...

Page 25: ...Cleaning of air filters Preparation Preparation 1 Turn off the air conditioner by the remote controller 2 Open the air intake grille Slide the button of the air intake grille inward and open the air intake grille slowly while holding it After rinsing the air filters with water dry them in the shade Set the air filter into the air conditioner Wipe down the panel and air filter with a sponge or towe...

Page 26: ... involves the owner s expense Failure to clean the indoor and outdoor units regularly will result in poor performance freezing water leakage and even compressor failure Inspection before maintenance Following inspection must be carried out by a qualified installer or qualified service person Parts Inspection method Heat exchanger Access from inspection opening and remove the access panel Examine t...

Page 27: ...self address was detected Auto reset E09 Duplicated header remote controllers Remote controller Remote controller address setting error Two remote controllers are set as header in the double remote controller control The header indoor unit stops raising alarm and follower indoor units continue to operate E10 CPU CPU communication error Indoor Indoor P C board Communication error between main MCU a...

Page 28: ...nput into CN80 Entire stop L31 SIM Phase sequence error etc Outdoor Power supply phase sequence outdoor unit P C board Abnormal phase sequence of the 3 phase power supply Operation continued thermost at OFF Wired remote controller display Wireless remote controller Sensor block display of receiving unit Main defective parts Judging device Parts to be checked error description Air conditioner statu...

Page 29: ...hen there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas opening without a door or an opening 0 15 or larger than the respective floor spaces at the top or bottom of the door 3 If an indoor unit is installed in each partitioned room and the refrigerant piping is interconnected the smallest room of course becomes the object But when a mechanical ventilatio...

Page 30: ...E NO 5d NO CHANGE 0000 STANDARD 0001 HIGH CEILING 1 0002 HIGH CEILING 3 0003 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to APPLICABLE CONTROLS in this manual Filter sign lighting time CODE NO 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time C...

Page 31: ...1115350171 144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1115350171_EN FR ES indd 92 19 3 2565 9 42 16 ...

Reviews: