background image

– 30 –

11

UNIT No. display

The selected indoor unit number is displayed.

Also number of indoor or outdoor unit which an 

error occurs is displayed.

12

Central control display

Displayed when the air conditioner is used under 

the central control in combination with a central 

control remote controller.
In case the remote controller is disabled by the 

central control system, 

 flashes.

The button operation is not accepted. 
Even when ON / OFF, MODE, or TEMP. button is 

pushed, and the button operation is not accepted. 

(Settings made by the remote controller vary with 

the central control mode. For details, refer to the 

Owner’s Manual of the central control remote 

controller.)

13

Remote controller sensor display

Displayed while the sensor of the remote controller 

is used.

14

Pre-heat display

Displayed when the heating mode is energized or 

defrost cycle is initiated.

While this icon is displayed, the indoor fan stops.

15

No function display

Displayed when the function requested is not 

available on that model.

16

1

6

4

2

3

5

7

13

15

14

9

12 1110

8

16

17

Operation section

Push each button to select a desired operation.

The control saves commands in memory and after the initial setting, there is no need for any additional 

settings unless changes are desired. The air conditioner can be operated by pushing the 

 button.

1

 button (Temperature set button)

Adjusts the set point.

Select the desired set point by pushing  TEMP. 

 or  TEMP. 

.

2

 button (Timer set button)

Use to setup the timer.

3

 button (Filter reset button)

Resets “ ” display after cleaning filter.

4

 button (Test button)

Use only for service. 

(During normal operation, do not use this button.)

5

 button

When the button is pushed, the operation starts, 

and it stops by pushing the button again.

When the operation has stopped, the operation 

lamp and all the displays disappear.

6

Operation lamp

Green light illuminates when unit is on.

Although it flashes when operating the protection 

device or an error occurs.

7

 button (Operation mode button)

Selects desired operation mode.

8

 button (Fan speed button)

Selects the desired Fan speed.

9

 button (Ventilation button)

Use when a power ventilation kit (locally procured) 

is connected.

If “

” is displayed on the remote controller 

when this button is pushed, no vent kit 

connected.

10

 button (Power save operation)

Use to initiate power saving mode.

11

 button (Unit / Louver select button)

Selects a unit number (left) and louver number 

(right).

UNIT:

 

Selects an indoor unit when multiple indoor units 

are controlled with one remote controller.

LOUVER: 

No Function.

12

 button (Swing / Louver direction 

button)

No Function.

OPTION:

Remote controller sensor

Usually the temperature sensor of the indoor unit 

senses the temperature. The temperature on the 

surrounding of the remote controller can also be 

sensed.

For details, contact the dealer from which you have 

purchased the air conditioner.

8

6

4

3

2

7

10
12

1

11

59-EN

60-EN

Service display

17

Operation ready display

This display appears on some models.

Summary of Contents for RAV-SM1106BTP-E

Page 1: ...Model name Concealed Duct Type English 1115466001 1 RAV SM406BTP E RAV SM406BTP E1 RAV SM456BTP E RAV SM456BTP E1 RAV SM566BTP E RAV SM566BTP E1 RAV SM806BTP E RAV SM806BTP E1 RAV SM1106BTP E RAV SM1106BTP E1 RAV SM1406BTP E RAV SM1406BTP E1 RAV SM1606BTP E RAV SM1606BTP E1 ...

Page 2: ...6 Power saving mode 32 ADOPTION OF NEW REFRIGERANT This Air Conditioner uses R410A an environmentally friendly refrigerant This appliance is not intended for use by person including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their...

Page 3: ...alified service person The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install repair maintain relocate and remove the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such operations by an individual or individua...

Page 4: ...nce there is high voltage inside the unit you may get electric shock when removing the cover and main unit Use of a stand more than 50 cm high to clean the filter of the indoor unit or to carry out other such jobs constitutes working at heights Due to the danger of falling off the stand and injuring yourself while working at heights this kind of work should not be done by unqualified individuals W...

Page 5: ...deteriorated after being used for a long time Leaving them such condition may result in the unit s falling down and causing injury Do not leave flammable sprays or other flammable materials near the air conditioner and do not spray flammable aerosol directly to the air conditioner They may catch fire Stop running the air conditioner and turn off the breaker before cleaning Otherwise injury may res...

Page 6: ...nne d entretien qualifiée est une personne qui installe répare entretient déplace et enlève les climatiseurs fabriqués par Toshiba Carrier Corporation Il ou elle a été formé pour installer réparer entretenir déplacer et enlever les climatiseurs fabriqués par Toshiba Carrier Corporation ou alternativement il ou elle a reçu des consignes pour de telles opérations par une ou des personnes qui ont été...

Page 7: ...couvercle et l unité principale Utilisez un support de plus de 50 cm de haut pour nettoyer le filtre de l unité intérieure ou pour effectuer d autres travaux nécessitant un travail en hauteur Etant donné que le support risque de tomber et de vous blesser lors d un travail en hauteur ce genre de travail ne peut pas être réalisé par des personnes non qualifiées Lorsque ce type de travail doit être r...

Page 8: ... dans une telle condition peut entraîner une chute de l unité et causer des blessures Ne laissez pas des vaporisateurs inflammables ou d autres matériaux inflammables près du climatiseur et ne vaporisez pas un aérosol inflammable directement sur le climatiseur Ils pourraient prendre feu Arrêtez le fonctionnement du climatiseur et de couper le disjoncteur avant le nettoyage Sinon cela pourrait entr...

Page 9: ...ründliche Kenntnisse die ihn zur Ausführung dieser Arbeiten befähigen Qualifizierter Servicetechniker Der Kundendienstfachmann ist eine Person die Klimageräte der Toshiba Carrier Corporation einbaut repariert wartet umzieht und ausbaut Die Person ist im Einbau in der Reparatur und in der Wartung sowie im Umzug und Ausbau von Klimageräten der Toshiba Carrier Corporation geschult oder wurde von eine...

Page 10: ... eines der Geräte selbst auszubauen bzw instand zu setzen Da im Inneren des Geräts Hochspannung anliegt können Sie beim Abnehmen der Abdeckung und der Demontage des Hauptgeräts einen Stromschlag bekommen Das Besteigen einer Erhöhung die höher als 50 cm ist zum Zweck der Reinigung des Innengerätfilters fällt unter so genannte Arbeiten in der Höhe Wegen der Sturzgefahr bei Arbeiten in der Höhe soll ...

Page 11: ... Überprüfen Sie ob der Zustand der Installationsgrundplatte und anderer Ausrüstungsteile sich nach längerer Verwendung verschlechtert haben Wenn Sie sie in einem solchen Zustand belassen kann dies dazu führen dass das Gerät herunterfällt und Verletzungen hervorruft Lassen Sie keine entflammbaren Sprays oder andere entflammbare Stoffe in der Nähe des Klimageräts und sprühen Sie kein entflammbares A...

Page 12: ...i assistenza qualificato è una persona che installa ripara effettua la manutenzione sposta e rimuove i condizionatori d aria costruiti da Toshiba Carrier Corporation Ha ricevuto la formazione necessaria per installare riparare manutenere spostare e rimuovere i condizionatori d aria costruiti da Toshiba Carrier Corporation o in alternativa è stato addestrato da uno o più individui in possesso della...

Page 13: ... installatore qualificato 1 o il personale di assistenza qualificato 1 Non tentare di spostare o riparare l unità da soli All interno dell unità è presente alta tensione pertanto la rimozione del coperchio e lo spostamento dell unità principale potrebbero esporre al rischio di elettrocuzione Per pulire il filtro dell unità interna o per eseguire altre attività considerate come lavori in altezza ut...

Page 14: ...he la base d installazione e ogni altra parte ancora non si sia deteriorata Lasciarle in tale condizione ne potrebbe causare il ribaltamento con conseguente pericolo per le persone Non lasciare prodotti spray né altri materiali infiammabili nei pressi del condizionatore né spruzzarli direttamente dentro le unità Si potrebbero infatti incendiare Prima di pulire il condizionatore lo si deve spegnere...

Page 15: ...e mantenimiento cualificado es una persona que se dedica a la instalación reparación mantenimiento traslado y retirada de los aparatos de aire acondicionado fabricados por Toshiba Carrier Corporation Dicha persona habrá recibido formación relativa a la instalación reparación mantenimiento traslado y retirada de aparatos de aire acondicionado fabricados por Toshiba Carrier Corporation o de otro mod...

Page 16: ...ninguna unidad usted mismo Dado que en el interior de la unidad hay alta tensión podría recibir una descarga eléctrica al retirar la cubierta y la unidad principal El uso de una plataforma de más de 50 cm de altura para limpiar el filtro de la unidad interior o para realizar otros trabajos similares constituye un trabajo en alturas Para evitar el peligro de caída de la plataforma y posibles lesion...

Page 17: ...as Revise si la base de instalación y el resto del equipo presentan deterioro después de un lapso prolongado de funcionamiento Si no toma las medidas necesarias la unidad podría caerse y provocar lesiones No deje pulverizadores inflamables ni otro tipo de material inflamable cerca del acondicionador de aire ni pulverice aerosoles inflamables directamente sobre él Podría incendiarse Apague el apara...

Page 18: ...qualificado O técnico de assistência qualificado é uma pessoa que instala repara dá manutenção a muda de lugar e remove os ares condicionados fabricados pela Toshiba Carrier Corporation Esta pessoa deve ter formação para instalar reparar dar manutenção a mudar de lugar e remover ares condicionados fabricados pela Toshiba Carrier Corporation ou como alternativa deve ter sido instruído nessas operaç...

Page 19: ...éctrico aquando da remoção da tampa e da unidade principal A utilização de um banco com mais de 50 cm de altura para limpar o filtro da unidade interior ou para realizar outras tarefas semelhantes constitui trabalho em altura Devido ao perigo de cair do banco e de se magoar ao trabalhar em altura este tipo de trabalho não deve ser feito por pessoas não qualificadas Quando for necessário realizar e...

Page 20: ...s a utilização durante um longo período de tempo Deixá los em más condições pode resultar na queda da unidade e provocar ferimentos Não deixe sprays inflamáveis ou outros materiais inflamáveis perto do ar condicionado e não borrife um aerossol inflamável directamente sobre o ar condicionado Isso pode causar um incêndio Certifique se de desligar o aparelho de ar condicionado e o disjuntor de circui...

Page 21: ...ersoon is een persoon die door Toshiba Carrier Corporation gemaakte airconditioners installeert repareert onderhoudt verplaatst en verwijderd Hij of zij is opgeleid om door Toshiba Carrier Corporation gemaakte airconditioners te installeren repareren onderhouden verplaatsen en te verwijderen Deze persoon kan ook iemand zijn die in dergelijke taken is geïnstrueerd door een persoon of personen die z...

Page 22: ...nderhoudsmonteur 1 Verplaats of herstel het apparaat niet zelf Omdat er onderdelen met hoogspanning in het apparaat aanwezig zijn loopt u gevaar van elektrische schokken wanneer u de behuizing en de hoofdunit verwijdert Gebruik een platform van minstens 50 cm hoog om het filter van de binnenunit te reinigen of soortgelijke taken op hoogte uit te voeren Dit werk mag alleen door bevoegde personen wo...

Page 23: ... namelijk kunnen vallen met ongelukken als gevolg indien gerelateerde onderdelen zijn beschadigd Zorg dat er geen ontvlambare spray s of materialen in de buurt van de airconditioner zijn en spuit geen ontvlambare middelen direct naar de airconditioner Dit soort middelen kan namelijk brand veroorzaken Stop de airconditioner alvorens te reinigen beslist en schakel de circuitonderbreker uit De ventil...

Page 24: ...ένος τεχνικός σέρβις Ο εξειδικευμένος τεχνικός επισκευών είναι ένα άτομο που πραγματοποιεί εργασίες εγκατάστασης επισκευής συντήρησης αλλαγής θέσης και αφαίρεσης των κλιματιστικών που κατασκευάζει η Toshiba Carrier Corporation Το άτομο αυτό έχει εκπαιδευτεί στην εγκατάσταση επισκευή συντήρηση αλλαγή θέσης και αφαίρεση των κλιματιστικών που κατασκευάζει η Toshiba Carrier Corporation ή εναλλακτικά έ...

Page 25: ...σία υψηλής τάσης στο εσωτερικό της μονάδας μπορεί να σας προκαλέσει ηλεκτροπληξία όταν αφαιρέσετε το κάλυμμα και την κεντρική μονάδα Χρησιμοποιήστε μια βάση με ύψος 50 cm ή περισσότερο για να καθαρίσετε το φίλτρο της εσωτερικής μονάδας ή για να εκτελέσετε άλλες εργασίες που απαιτούν την εργασία σε ύψη Λόγω του κινδύνου πτώσης από τη βάση και τραυματισμού σας κατά την εργασία σε ύψη αυτού του είδου...

Page 26: ...ό μακροχρόνια χρήση Αν τα αφήσετε σε μια τέτοια κατάσταση η μονάδα μπορεί να πέσει και να προκληθεί τραυματισμός Μην αφήνετε εύφλεκτα σπρέι ή άλλα εύφλεκτα υλικά κοντά στο κλιματιστικό και μην ψεκάζετε εύφλεκτο αερόλυμα απευθείας στο κλιματιστικό Μπορεί να πιάσουν φωτιά Σταματήστε τη λειτουργία του κλιματιστικού και απενεργοποιήστε τον ασφαλειοδιακόπτη πριν τον καθαρισμό Διαφορετικά μπορεί να προκ...

Page 27: ...специалист по обслуживанию это лицо которое устанавливает ремонтирует обслуживает перемещает и демонтирует кондиционеры производства компании Toshiba Carrier Corporation Он или она прошел обучение по вопросам установки ремонта технического обслуживания переустановки и демонтажа кондиционеров производства компании Toshiba Carrier Corporation или же был обучен таким действиям лицом или лицами получи...

Page 28: ...стройства может привести к поражению электрическим током Использование подставки высотой более 50 см для чистки фильтра внутреннего блока или выполнения других работ относится к категории высотных работ Из за опасности падения и сопутствующих этому травм эту работу не должны выполнять неквалифицированные лица Когда возникает необходимость в такой работе не делайте ее самостоятельно а обратитесь к ...

Page 29: ...олжительной эксплуатации проверяйте установочную платформу и другое оборудование на предмет износа Если оставить их в подобном состоянии блок может упасть и стать причиной травмы Не оставляйте легковоспламеняющиеся аэрозоли и другие горючие материалы вблизи кондиционера и не распыляйте легковоспламеняющиеся аэрозоли непосредственно на кондиционер Они могут воспламениться Перед выполнением чистки в...

Page 30: ...While this icon is flashing the model is being automatically confirmed Wait till icon has disappeared to use the remote controller 1 Operation mode The selected operation mode is displayed 2 Error display Displayed while the protective device works or an error occurs 3 SETTING display Displayed during setup of the timer or other settings 4 TEST run display Displayed during a test run 5 Timer displ...

Page 31: ... desired set point by pushing TEMP or TEMP 2 button Timer set button Use to setup the timer 3 button Filter reset button Resets display after cleaning filter 4 button Test button Use only for service During normal operation do not use this button 5 button When the button is pushed the operation starts and it stops by pushing the button again When the operation has stopped the operation lamp and al...

Page 32: ...mand for heating unit will start approximately 3 to 5 minutes after the mode is selected After the heating operation has stopped fan may continue to run for approx 30 seconds When the room temperature reaches the set temperature the outdoor unit stops and the indoor unit fan runs at extremely low speed During defrost operation the fan stops so that cool air is not discharged Pre heat is displayed ...

Page 33: ...ain after about 5 seconds This is due to normal processing of the remote controller Off timer The unit stops when the set time is reached Repeat Off timer The unit stops daily when the set time is reached On timer The unit starts when the set time is reached 1 3 2 4 shows 1 day 24 hours shows 10 hours Total 34 hours Off timer On timer Repeat Off timer No display Off Off On Number of days Time 6 Po...

Page 34: ...ng air filters Clogged air filters will reduce the cooling and heating performance 1 If is displayed on the remote controller clean the air filters 2 When the cleaning of air filters has been completed push button disappears When not used for a long time 1 Perform the fan operation for a couple of hours to dry inside 2 Push button on the remote controller to stop running and turn off the circuit b...

Page 35: ... a sound generated when the heat exchanger or other part expands and contracts slightly due to temperature change Various smells from the walls carpet clothes cigarette cosmetics or other things adhere to the air conditioner The unit does not run Has a blackout occurred Has the circuit breaker blown Has the protective device been activated The operation indicator and on the remote controller are b...

Page 36: ...s If air conditioner is used outside of the above conditions safety protection may work Cooling operation Outdoor temperature 15 C to 43 C Dry bulb temp Room temperature 21 C to 32 C Dry bulb temp 15 C to 24 C Wet bulb temp CAUTION Room relative humidity less than 80 If the air conditioner operates in excess of this figure the surface of the air conditioner may cause dewing Heating operation Outdo...

Page 37: ...Estate PLYMOUTH Devon PL6 7DB United Kingdom Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type RAV SM406BTP E RAV SM456BTP E RAV SM566BTP E RAV SM806BTP E RAV SM1106BTP E RAV SM1406BTP E RAV SM1606BTP E RAV SM406BTP E1 RAV SM456BTP E1 RAV SM566BTP E1 RAV SM806BTP E1 RAV SM1106BTP E1 RAV SM1406BTP E1 RAV SM1606BTP E1 Commercial name Digital Inverter ...

Page 38: ... 37 MEMO ...

Page 39: ... 38 MEMO 00EH99939501_01EN book Page 38 Wednesday February 8 2012 10 26 AM ...

Page 40: ... Muang Pathumthani 12000 Thailand d t L K U r e i r r a C a b i h s o T U E n i r o t u b i r t s i D r e t r o p m I e h t f o e m a N Address city country Porsham Close Belliver Industrial Estate PLYMOUTH Devon PL6 7DB United Kingdom 1115466001 1 TOSHIBA CARRIER THAILAND CO LTD 144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...

Reviews: