6
If there is other indoor unit to be changed,
repeat procedure
2
to
5
to change the
setup.
When the above setup has
fi
nished, push
to select the indoor UNIT No. before
change of setup, specify CODE No. [
12
], [
13
],
[
14
] in order with TEMP.
/
buttons,
and then check the changed contents.
Address change check Before change:
[
3-3-1
]
→
After change: [
2-2-2
]
Pushing button clears the contents of
which setup was changed.
(In this case, procedure from
2
is repeated.)
Indoor UNIT No. before setup change is displayed.
7
After check of the changed contents, push
button. (setup is determined.) When
button is pushed, the display disappears
and the status becomes the usual stop
status. (when
button is pushed the
operation from the remote controller is not
accepted for approx. 1 minute.)
* If the operation from the remote controller is
not accepted even 1 minute or more passed
after pushing
button, it is considered that
the address setup is incorrect.
In this case, the automatic address must be
again set up.
Therefore repeat procedure of the setup
change from the Procedure
1
.
To recognize the position of the
corresponding indoor unit though the
indoor UNIT No. is known
Check the position during operation stop.
(Stop operation of the set.)
2
1, 3
1
1
Push
+
buttons simultaneously
for 4 seconds or more.
After a while, the display part
fl
ashes and
the display appears as shown below.
In this time, the position can be checked
because fan of the indoor unit operate.
• For the group control, the indoor UNIT No.
is displayed as [
] and fans of all the
indoor units in the group control operate.
Check the displayed CODE No. is [
01
].
• When the CODE No. is other than [
01
],
push
button to erase the display and
repeat procedure from the
fi
rst step.
(After
pushing
button, operation of
the remote controller is not accepted for
approx. 1 minute.)
(* Display changes according to
the model No. of indoor unit.)
2
In the group control, every time
button is pushed, the indoor UNIT No. in
the group control is displayed in order.
In this time, the position of the indoor unit can
be con
fi
rmed because only fan of the selected
indoor unit operate.
(For a group control, No. of the
fi
rstly
displayed indoor unit becomes the header
unit.)
3
After con
fi
rmation, push
button to
return the mode to the usual mode.
When
button is pushed, the display
disappears and the status becomes the usual
stop status.
(When
button is pushed the operation
from the remote controller is not accepted for
approx. 1 minute.)