Installation Manual
‒
31
‒
31-EN
2
Each time
button is pushed, indoor
unit numbers in the control group change
cyclically. Select the indoor unit to change
settings for.
The fan of the selected unit runs. The indoor
unit can be con
fi
rmed for which to change
settings.
3
Specify CODE No. [
] with TEMP.
/
buttons.
4
Select SET DATA [
] with TIME
/
buttons.
5
Push
button. When the display changes
from
fl
ashing to lit, the setup is completed.
• To change settings of another indoor unit,
repeat from Procedure
2
.
• To change other settings of the selected
indoor unit, repeat from Procedure
3
.
Use button to clear the settings.
To make settings after
button was
pushed, repeat from Procedure
2
.
6
When settings have been completed, push
button to determine the settings.
When
button is pushed, “SETTING”
fl
ashes and then the display content
disappears and the air conditioner enters the
normal stop mode.
(While “SETTING” is
fl
ashing, no operation of
the remote controller is accepted.)
Change of lighting time of
fi
lter
sign
According to the installation condition, the lighting
time of the
fi
lter sign (Noti
fi
cation of
fi
lter cleaning)
can be changed.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
• For the CODE No.. in Procedure
3
, specify [01].
• For the [SET DATA] in Procedure
4
, select the
SET DATA of
fi
lter sign lighting time from the
following table.
SET DATA
Filter sign lighting time
0000
None
0001
150H (Factory setting)
0002
2500H
0003
5000H
0004
10000H
To secure better effect of heating
When it is dif
fi
cult to obtain satisfactory heating
due to installation place of the indoor unit or
structure of the room, the detection temperature of
heating can be raised. Also use a circulator, etc. to
circulate heat air near the ceiling.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
• For the CODE No.. in Procedure
3
, specify [06].
• For the SET DATA in Procedure
4
, select
the SET DATA of shift value of detection
temperature to be set up from the table below.
SET DATA
Detection temp shift value
0000
No shift
0001
+1°C
0002
+2°C (Factory setting)
0003
+3°C
0004
+4°C
0005
+5°C
0006
+6°C